HomeMy WebLinkAboutEngineered Plan - 2015IN.
LEGEND
-�--{}�- PROPOSED CONTOUR
® PROPOSED SPOT GRADE
----98 -- EXISTING CONTOUR
+ 96.52 EXISTING SPOT GRADE
W---- EXISTING WATER SERVICE
TEST PIT
SOUTH YARMOUTH
ST -9
LOCUS
105 STATON AVE.
� rA.
MEMOR\P�
LOCUS MAP
LOCUS INFORMATION
PLAN REF: BK 25967 PG 336
PARCEL ID: MAP 69 PAR. 20
SEPTIC SYSTEM
REPAIR PLAN
LOCATED AT:
105 STATION AVENUE
SOUTH YARMOUTH, MA
PREPARED FOR
GRIMES/DONE RIGHT EXC.
JULY 10, 2015
hok—
MEYER & SONS, INC.
P.O. BOX 981
EAST SANDWICH, MA. 02537
PH: (508)360-3311
FAX: (774)413-9468
meyerandsonstitle50gmail.com
www.meyerandsons.com
SNFF'T 1 !1P" 7 1 114 -7 A A
NOTE: MAGNETIC TAPE TO BE PLACED OVER ALL COVERS
T.O.F. EL.=30.0t SEPTIC TANK PROPOSED D -80X
INSTALL RISERS & COVERS OVER INLET & INSTALL RISER & COVER
OUTLET AND SET TO 6" OF FINISH GRADE SET TO 6" OF GRADE
F.G. EL.=28.0t F.G. EL.=29.51
NOTES: 1) CONTRACTOR SHALL VERIFY ALL EXISTING
PIPE INVERTS PRIOR TO CONSTRUCTION
2) TANK AND D -BOX SHALL BE SET LEVEL AND
TRUE TO GRADE ON A MECHANICALLY COMPACTED
SIX INCH CRUSHED STONE BASE, AS SPECIFIED IN
310 CMR 15.221(2)
3) INSTALL INLET & OUTLET TEES W/
GAS BAFFLE AS REQUIRED
0 S-1X((MN.)
4"SCH40 PVC
11.3' TO
INVERT
INV.=25.11 -
;s -e s
D-80 •
M=5
s
NOTE: TO PREVENT BREAKOUT, THE PROPOSED
FINISH GRADE SHALL NOT BE < EL: 25.5
FOR A DISTANCE OF 15' AROUND THE PERIMETER OF THE S.A.S.
PROPOSED S.A.S.
INSTALL A 4" DIAMETER INSPECTION PORT OVER
ONE CHAMBER (MIN.) AND SET TO 3" OF F.G. GENERAL NOTES:
F.G. EL: 28.5 (MAX.) 1. ALL CHANGES TO THIS PLAN MUST BE APPROVED BY THE LOCAL
BOARD OF HEALTH AND THE DESIGN ENGINEER.
2. ALL WORK AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS
OF THE STATE ENVIRONMENTAL CODE, TITLE V. AND ANY APPLICABLE
INSTALL TWOINSPECTION PORTS (MIN.) LOCAL RULES AND REGULATIONS.
4 ROWS OF 4 UNITS AT 6.25'/UNIT = 25'/ROW
SOIL ABSORPTION SYSTEM (PROFILE)
RESTORE VEGETATIVE COVER
TO TOP OF CHAMBERS PERC SAND
BREAKOUT -TOP ELEV.- 25.5
�• a .
INV. ELEV.= 25.11 •-
BOTTOM ELEV.= 24.17 EXISTING SUITABLE
5' MIN. ABOVE BOTTOM OF 2.83' MATERIAL
T.P. EXCAVATION OR G.W. EFFECTIVE NDTH = 4 x 2? 3'
(6.83 PROVIDED) USE 4 ROWS OF 4 -HIGH CAPACITY
BOTTOM OF TESTHOLE: EL:17.34 = INFILTRATOR (H20) UNITS W/ ENDCAP-NO STONE
SEPTIC SYSTEM PROFILE
N.T.S.
DESIGN CRITERIA
NUMBER OF BEDROOMS: 3 BEDROOM DESIGN
DESIGN FLOW: RESIDENTIAL: 3 BEDROOMS 0 110 GPD/BR = 330 GPD
DESIGN PERCOLATION RATE: <2 MIN/IN SOIL TEXTURAL CLASS: CLASS I
GARBAGE GRINDER: NO (not designed for garbage grinder)
DISTRIBUTION BOX: USE DB -5 (H20)
SEPTIC TANK: 330 gpd x 200% - 660 gpd USE NEW 1,50OG SEPTIC TANK
(0.74 GPD/SF)
LEACHING AREA REQUIRED: (330)/.74 = 445.94 S.F.
PRIMARY S.A.S.
USE 4 ROWS OF 4 - HI -CAP INFILTRATOR H-20 UNITS -NO STONE
BOTTOM AREA:
(CHAMBER)
(GENERAL USE APPROVAL FOR, 4.73 SF/LF OF CHAMBER)
16 UNITS x 6.25 LF x-4.73 SF/LF = 473.0 SF
DESIGN FLOW PROVIDED:
rr.rs.
SOIL LOGS
DATE: JULY 1, 2015
SOIL EVALUATOR: DARREN M. MEYER, CSE 1614
WITNESS: A. VONHONE, YARMOUTH HEALTH
a-. TP --1 oe;m
28.50 0"
TOTAL AREA = 473 SF
0.74GPD/SF(473SF) = 350 GPD > 330 GPD req'd
9 MIN COVER/
O S-1 X MIN.)
-1X (PVC
36" MAX COVER
E" 27'�
L - 30'
0 S -IX (MIN.)
4"S
a
4"SCH40 PVC
LOAMY SAND
10
26.17
28'
UQUID
INV.=26.50
LEVEL
Lv.ol.=26.751448"
GAS BAFFLE
P14"f L.G
INV.=26.201
PROPOSED
EXIST. SEWER OUTLET
1.500 GALLON ON SEP
TANK
INV.=27.50
NOTES: 1) CONTRACTOR SHALL VERIFY ALL EXISTING
PIPE INVERTS PRIOR TO CONSTRUCTION
2) TANK AND D -BOX SHALL BE SET LEVEL AND
TRUE TO GRADE ON A MECHANICALLY COMPACTED
SIX INCH CRUSHED STONE BASE, AS SPECIFIED IN
310 CMR 15.221(2)
3) INSTALL INLET & OUTLET TEES W/
GAS BAFFLE AS REQUIRED
0 S-1X((MN.)
4"SCH40 PVC
11.3' TO
INVERT
INV.=25.11 -
;s -e s
D-80 •
M=5
s
NOTE: TO PREVENT BREAKOUT, THE PROPOSED
FINISH GRADE SHALL NOT BE < EL: 25.5
FOR A DISTANCE OF 15' AROUND THE PERIMETER OF THE S.A.S.
PROPOSED S.A.S.
INSTALL A 4" DIAMETER INSPECTION PORT OVER
ONE CHAMBER (MIN.) AND SET TO 3" OF F.G. GENERAL NOTES:
F.G. EL: 28.5 (MAX.) 1. ALL CHANGES TO THIS PLAN MUST BE APPROVED BY THE LOCAL
BOARD OF HEALTH AND THE DESIGN ENGINEER.
2. ALL WORK AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS
OF THE STATE ENVIRONMENTAL CODE, TITLE V. AND ANY APPLICABLE
INSTALL TWOINSPECTION PORTS (MIN.) LOCAL RULES AND REGULATIONS.
4 ROWS OF 4 UNITS AT 6.25'/UNIT = 25'/ROW
SOIL ABSORPTION SYSTEM (PROFILE)
RESTORE VEGETATIVE COVER
TO TOP OF CHAMBERS PERC SAND
BREAKOUT -TOP ELEV.- 25.5
�• a .
INV. ELEV.= 25.11 •-
BOTTOM ELEV.= 24.17 EXISTING SUITABLE
5' MIN. ABOVE BOTTOM OF 2.83' MATERIAL
T.P. EXCAVATION OR G.W. EFFECTIVE NDTH = 4 x 2? 3'
(6.83 PROVIDED) USE 4 ROWS OF 4 -HIGH CAPACITY
BOTTOM OF TESTHOLE: EL:17.34 = INFILTRATOR (H20) UNITS W/ ENDCAP-NO STONE
SEPTIC SYSTEM PROFILE
N.T.S.
DESIGN CRITERIA
NUMBER OF BEDROOMS: 3 BEDROOM DESIGN
DESIGN FLOW: RESIDENTIAL: 3 BEDROOMS 0 110 GPD/BR = 330 GPD
DESIGN PERCOLATION RATE: <2 MIN/IN SOIL TEXTURAL CLASS: CLASS I
GARBAGE GRINDER: NO (not designed for garbage grinder)
DISTRIBUTION BOX: USE DB -5 (H20)
SEPTIC TANK: 330 gpd x 200% - 660 gpd USE NEW 1,50OG SEPTIC TANK
(0.74 GPD/SF)
LEACHING AREA REQUIRED: (330)/.74 = 445.94 S.F.
PRIMARY S.A.S.
USE 4 ROWS OF 4 - HI -CAP INFILTRATOR H-20 UNITS -NO STONE
BOTTOM AREA:
(CHAMBER)
(GENERAL USE APPROVAL FOR, 4.73 SF/LF OF CHAMBER)
16 UNITS x 6.25 LF x-4.73 SF/LF = 473.0 SF
DESIGN FLOW PROVIDED:
rr.rs.
SOIL LOGS
DATE: JULY 1, 2015
SOIL EVALUATOR: DARREN M. MEYER, CSE 1614
WITNESS: A. VONHONE, YARMOUTH HEALTH
a-. TP --1 oe;m
28.50 0"
TOTAL AREA = 473 SF
0.74GPD/SF(473SF) = 350 GPD > 330 GPD req'd
17.341-- 134"
PERC RATE <2 MIN/IN. (C1' HORIZON)
NO GROUNDWATER OBSERVED
**RE -USE PER HEAT
• 1, Darren M. Meyer, R.S.. CSE, hereby certify that I am currently approved by MADEP pursuant to 310 CMR 15.017
to conduct soil evaluations and that the above analysis has been performed by me consistent with the
requirements of 310 CMR 15.017. 1 further certify that I have passed the Sail Evol. Exam in October, 1999.
3. THE SEWAGE DISPOSAL SYSTEM SHALL NOT BE BACKFILLED PRIOR
TO INSPECTION AND APPROVAL BY THE BOARD OF HEALTH AND THE
DESIGN ENGINEER.
4. ANY CONDITIONS ENCOUNTERED DURING CONSTRUCTION DIFFERING
FROM THOSE SHOWN HEREON SHALL BE REPORTED TO THE DESIGN
ENGINEER BEFORE CONSTRUCTION CONTINUES.
5. ALL ELEVATIONS BASED ON ASSUMED DATUM.
6. THE DESIGN ENGINEER IS NOT RESPONSIBLE FOR THE FAILURE OF
THE CONTRACTOR OR OWNER TO NOTIFY THE LOCAL BOARD OF
HEALTH FOR PROPER INSPECTIONS DURING CONSTRUCTION.
7. DWELLING IS SERVICED BY MUNICIPAL WATER SUPPLY.
8. ALL AREAS DISTURBED DURING CONSTRUCTION SHALL BE RESTORED
TO A CONDITION AGREED UPON BETWEEN OWNER AND CONTRACTOR.
9. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE
LOCATION OF ALL UNDERGROUND UTILITIES. PRIOR TO STARTING WORK.
10. EXISTING LEACHING TO BE PUMPED, CRUSHED AND REMOVED PER TITLE 5.
REPLACE WITH CLEAN MEDIUM SAND PER TITLE 5 REQUIREMENTS.
11. 48 HOUR NOTICE FOR ENGINEER CERTIFICATION
12. THIS PLAN IS TO BE USED FOR SEPTIC SYSTEM PURPOSES ONLY
AND IS NOT TO BE CONSIDERED A PROPERTY UNE SURVEY
13. NO KNOWN PRIVATE WELLS WITHIN 100 FT. OF PROPOSED LEACHING
14. ALL PIPING TO BE 4" SCH 40 0 1/8"/FT (UNLESS SPEC. )
15. THE DESIGN OF THIS SYSTEM DOES NOT ALLOW
FOR THE USE OF A GARBAGE GRINDER.
16. NO WETLANDS WITHIN 150 FT. OF PROPOSED LEACHING
f
I PROPOSED SEPTIC SYSTEM UPGRADE PLAN
105 STATON AVENUE, SOUTH YARMOUTH, MA
Prepared for: Grimes Done Right Exc.
System Design and Site Plan by: SCALE DRAWN DATE
MEYER &SONS, INC. N.T.S. DMM 07/10/15
PO BOX 981
EAST SANDWICH, MA 02537 REV DATE CHECKED SHEET NO.
50B•3822922 DMM 2 of 2
LOAMY SAND
10YR 3/2
27.87
a
8"
LOAMY SAND
tCYR S/6
26.17
28'
C
MEDIUM
6�4
2.5Y
17.341-- 134"
PERC RATE <2 MIN/IN. (C1' HORIZON)
NO GROUNDWATER OBSERVED
**RE -USE PER HEAT
• 1, Darren M. Meyer, R.S.. CSE, hereby certify that I am currently approved by MADEP pursuant to 310 CMR 15.017
to conduct soil evaluations and that the above analysis has been performed by me consistent with the
requirements of 310 CMR 15.017. 1 further certify that I have passed the Sail Evol. Exam in October, 1999.
3. THE SEWAGE DISPOSAL SYSTEM SHALL NOT BE BACKFILLED PRIOR
TO INSPECTION AND APPROVAL BY THE BOARD OF HEALTH AND THE
DESIGN ENGINEER.
4. ANY CONDITIONS ENCOUNTERED DURING CONSTRUCTION DIFFERING
FROM THOSE SHOWN HEREON SHALL BE REPORTED TO THE DESIGN
ENGINEER BEFORE CONSTRUCTION CONTINUES.
5. ALL ELEVATIONS BASED ON ASSUMED DATUM.
6. THE DESIGN ENGINEER IS NOT RESPONSIBLE FOR THE FAILURE OF
THE CONTRACTOR OR OWNER TO NOTIFY THE LOCAL BOARD OF
HEALTH FOR PROPER INSPECTIONS DURING CONSTRUCTION.
7. DWELLING IS SERVICED BY MUNICIPAL WATER SUPPLY.
8. ALL AREAS DISTURBED DURING CONSTRUCTION SHALL BE RESTORED
TO A CONDITION AGREED UPON BETWEEN OWNER AND CONTRACTOR.
9. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE
LOCATION OF ALL UNDERGROUND UTILITIES. PRIOR TO STARTING WORK.
10. EXISTING LEACHING TO BE PUMPED, CRUSHED AND REMOVED PER TITLE 5.
REPLACE WITH CLEAN MEDIUM SAND PER TITLE 5 REQUIREMENTS.
11. 48 HOUR NOTICE FOR ENGINEER CERTIFICATION
12. THIS PLAN IS TO BE USED FOR SEPTIC SYSTEM PURPOSES ONLY
AND IS NOT TO BE CONSIDERED A PROPERTY UNE SURVEY
13. NO KNOWN PRIVATE WELLS WITHIN 100 FT. OF PROPOSED LEACHING
14. ALL PIPING TO BE 4" SCH 40 0 1/8"/FT (UNLESS SPEC. )
15. THE DESIGN OF THIS SYSTEM DOES NOT ALLOW
FOR THE USE OF A GARBAGE GRINDER.
16. NO WETLANDS WITHIN 150 FT. OF PROPOSED LEACHING
f
I PROPOSED SEPTIC SYSTEM UPGRADE PLAN
105 STATON AVENUE, SOUTH YARMOUTH, MA
Prepared for: Grimes Done Right Exc.
System Design and Site Plan by: SCALE DRAWN DATE
MEYER &SONS, INC. N.T.S. DMM 07/10/15
PO BOX 981
EAST SANDWICH, MA 02537 REV DATE CHECKED SHEET NO.
50B•3822922 DMM 2 of 2