HomeMy WebLinkAbout355 Great Island Road Site Plan 2SYSTEM DESIGN: GARBAGE DISPOSER IS NOT ALLOWED DESIGN FLOW: 4 BEDROOMS ® 110 GPD = 440 GPD USE A 440 GPD DESIGN FLOW SEPTIC TANK: 440 GPD (2) = 880 USE A 1500 MIN. GAL: SEPTIC TANK BOTTOM AREA ONLY: 13.5' (+/-) X 50.3'= 602 SF X (.74) = 446 GPD USE A 602 SF LEACHING FIELD AS SHOWN MA APPROVED DATE BOARD OF HEALTH NOTES 2. MUNICIPAL WATER IS AVAILABLE 3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT. 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS - 99-- TO BE AASHO H -LQ. 4"SCH40 5. PIPE JOINTS TO BE MADE WATERTIGHT. RISERS (TYP.) 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH (98.4] 310 CMR 15.000 (TITLE V.) \ 7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO BE USED FOR LOT LINE STAKING OR ANY OTHER FLOOD VENTS WITHIN 12" GRADE PURPOSE. �0-) 8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC. NOTE: 500E GAL RESERVE 9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED 2'm WITHOUT INSPECTION BY BOARD OF HEALTH AND ALARM AND CONTROL PANEL PERMISSION OBTAINED FROM BOARD OF HEALTH. 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING / DIGSAFE (1-888-344-7233) AND VERIFYING THE BUILDING. ALARM TO BE ON INV. IN LOCATION OF ALL UNDERGROUND & OVERHEAD UTILITIES (GROUND AT EL. 7.4) REQ. PRIOR TO COMMENCEMENT OF WORK. 11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE ' ZABEL FILTER FLOAT SNITCH ALARM ON (A100) REMOVED 5' BENEATH AND AROUND THE PROPOSED SLOPE TO DRAIN BACK LEACHING FACILITY. WEEP HOLE 12. EXISTING LEACHING FACILITY SHALL BE PUMPED AND THIS SIDE OF BAFFLE REMOVED OR PUMPED AND FILLED WITH CLEAN SAND. 13..NO"BASEMENT" ALLOWED. FLOODZONE RESISTANT CAP ENDS DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN (ACCORDANCE WITH FEMA REGULATIONS AS SHOWN. 14. ALL RUN-OFF TO BE CONTAINED ON-SITE (ON BLOCK) DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS. DOSE (5" WORKING RANGE) 15. DRYWELLS (OR DRIP TRENCHES) SHALL BE INSTALLED TO CONTAIN ROOF RUN-OFF. 16. CONTRACTOR TO COORDINATE ALL UTILITY DISCONNECTS SEPTIC TANK/PC AND NEW SERVICES WITH APPROPRIATE VENDORS. 17. CONTRACTOR TO NOTE ORDER OF CONDITIONS COVERING ANY WORK ON SITE TO BE ISSUED BY THE TOWN OF YARMOUTH TEST HOLE LOGS CONSERVATION COMMISSION. COPY OF ORDER TO BE ONSITE AND ALL CONDITIONS AND SPECIAL CONDITIONS SHALL BE ADHERED TO. REQUIRED INSPECTIONS AND CERTIFICATIONS 1. ENGINEER SHALL INSPECT WHEN REQUIRED EXCAVATION IS COMPLETE. 2. ENGINEER SHALL STAKE FOOTING PRIOR TO POURING 3. ENGINEER SHALL INSPECT FOOTING AND REBAR PRIOR TO POURING OF WALL 4. ENGINEER SHALL INSPECT WHEN CLEAN FILL HAS BEEN PROPERLY DEPOSITED 5. ENGINEER SHALL INSPECT AND CERTIFY SEPTIC COMPONENTS AND PUMP MECHANISMS AFTER INSTALLATION ENGINEER SHALL CERTIFY TO YARMOUTH HEALTH DEPARTMENT THAT THE RETAINING WALL, SEPTIC SYSTEM AND PUMP MECHANISMS HAVE BEEN INSTALLED IN SUBSTANTIAL COMPLIANCE WITH THE APPROVED PLAN. I *THE INSTALLER SHALL VERIFY THE LOCATIONS OF ALL UTILITIES AND ALL BUILDING SEWER OUTLETS AND ELEVATIONS PRIOR TO INSTALLING ANY PORTION OF SEPTIC SYSTEM FIRST FLOOR BLDG ELEV. 11.0' CONCRETE ACCESS COVERS TO WITHIN 6" OF FIN. GRADE RAWLSPACE SLAB .6' TOP FOUNDATION 10.Ot WITHIN 20' OF SAS 9.5' REMAINDER OF CRAWLSPACE MINI IUM .75' of COV SLAB AT EL. 7.4' PRECAST H-10 ALL SYSTEM COMPONENTS SHALL BE MARKED WITH MAGNETIC TAPE OR COMPARABLE MEANS FOR FUTURE LOCATION. MARK CORNERS OF LEACH FIELD WITH 24" #5 REBAR WITH SAFETY CAP DRIVEN JUST BELOW GRADE EACH CORNER OF LEACH FIELD. L±4" DIA PERF. INSP. PORT TO SAND AT BOTTOM OF EACHING FIELD. 4" THREADED CAP TO WITHIN 3" OF FINISH GRADE 40 MIL LINER FROM ELEV. 8.8' TO ERETAINING WALL SCHEMATIC SHOWN, EXACT FASCADE AND CONSTRUCTION BY OTHERS. TOP OF WALL HT. AS NOTED OVER PRECAST TOP PIPE 8.6' FINISHED GRADE- 4" LOAM & SEED 2% MIN. SLOPE OVER SYSTEM T 80 ' 0.54 ACRES± / (12,745± UPLAND) R 8(5 del, NOTE: WETLAND RESOURCE AREAS FLAGGED BY LEC ENVIRONMENTAL CONSULTANTS, INC. `$\ -11.4 / A 5'r Qy del, alt, 0 LEC OHO �1�1, FLAG - 011, SM#1�//c� EXIST. / C./ BLOCK r BLOCK t! PAVED I PATP 5P `i1r, SM#2/ PROP. SITTING d11, WALL/AT EDGE J / OF +PATIO \`I` 101FI/o� oS�y SM#3 q10, 011, / .0. / PROP. VENT WITH CHARCOAL FILTER AND BUGSCREEN (FINAL PLACEMENT BY CONTRACTOR WITH HOMEOWNER CONSULTATION) WALK ►�1 PROP. 4 BR DWELLING -' FIRST FL. ELEV. 11.0' (CRAWLSPACE SLAB ELEV. MIN. 8.25') 5' UNSUITABLE SOIL REMOVAL LIMIT AROUND LEACHING FIELD .0, �' EXISTING 4 BR DWELLING (TO BE REMOVED AND REPLACED) EXISTING FIRST FL ELEV. = 9.4' Pis°`moo AH -1 8E MW _ (LEC) (DCE) / 10� \ v PROP. DRIVEWAY `I SpRONE,` / IVE AVED5`�`/ G VE 0 'b b PROPOSED 4 BR SEPTIC SYSTEM TO CONSIST OF A TITLE 5 COMPLIANT 1500 ROP. RET. )NALL GALLON SEPTIC TANK, DBOX, AND A ' TW = 9.0• 602 SF LEACH FIELD, BASE OF WHICH (DES;( , Y�THERS) IS 5' ABOVE HIGH GROUNDWATER. FINAL GRADE OVER SAS TO BE ELEV. / 10.0 -9.5' VARIES / BENCHMARK: C. BASIN AT ELEVATION 4.95' NGVD29 i SITE PLAN Scale: 1 "= 20' 0 NOTE: NO INCREASE IN TITLE 5 DESIGN FLOW, NOT "NEW CONSTRUCTION UNDER TITLE 5, 10 20 30 40 50 FEET VARIANCES REQUESTED UNDER MAXIMUM FEASIBLE COMPLIANCE 15.405: (la) LEACHING FIELD TO BE LOCATED 7.5' FROM LOT LINE (10' REQUIRED) VARIANCE OF 2.5' REQUESTED (1f) LEACHING FIELD TO BE LOCATED 25' FROM DRAIN WHICH MAY INTERCEPT HIGH GROUNDWATER- 50' REQ. 25' VARIANCE REQUESTED, WALL/LINER PROVIDED VARIANCE TO LOCAL BOARD OF HEALTH REGULATIONS REG. 3.7: LEACHING AREA TO BE 70.4' FROM COASTAL BANK, 100' REQUIRED, 29.6' VARIANCE REQUESTED DICE # 09-130 MUST BE PROVIDED FOR ZABEL FILTER. - 99-- EXISTING CONTOUR 4"SCH40 ^. RISERS (TYP.) PROP. TEE (98.4] PROPOSED SPOT EL. \ TEST HOLE FLOOD VENTS WITHIN 12" GRADE SLOPE OF GROUND �0-) UTILITY POLE NOTE: 500E GAL RESERVE FIRE HYDRANT 2'm 4"OSCH40 PVC ALARM AND CONTROL PANEL CLEAN FILL TO BE INSTALLED INSIDE / BUILDING. ALARM TO BE ON INV. IN (GROUND AT EL. 7.4) REQ. SEPARATE CIRCUIT FROM PUMP ' ' ZABEL FILTER FLOAT SNITCH ALARM ON (A100) 14'TEE SLOPE TO DRAIN BACK 10� 2500 GAL4"PERFORATED WEEP HOLE PIPES LEVEL 1ST 2'.,.;.., THIS SIDE OF BAFFLE CHECK VALVE CAP ENDS PUMP OFF 12 SUBMERSIBLE 4/10 HP PUMP SYSTEM (OR EQUAL) (ON BLOCK) 4 DOSES PER DAY, AT 110 GAL. PER VENTS ON 2 SIDES REQ. DOSE (5" WORKING RANGE) B' RAFFLE SEPTIC TANK/PC CHAMBER COMBINATION (NOT TO SCALE) Pvc. S=0005-- o . TEST HOLE LOGS ENGINEER: DANIEL A. OJALA PE, PLS SE1805 DATE: JULY 1, 2009 PERC, RATE _ < 2 MIN/INCH CLASS I SOILS 7 2' 4 p" 7.0' O" 7.0' FILL FILL 3" LOAM 3" LOAM THEN SAND THEN SAND 24" 24" FLOOD VENT/FOUNDATION DESIGN A LS A LS 27" 10YR 3/2 COMBINATION B LS ° ° 42„ 3/4'-1-1/2' DOUBLE WASHED STONE LEACHING FIELD o :::j PERC Cl Cl BOTT. AT 52', 24 BY OTHERS. GAL IN 9:30 < 2 MIN/INCH SHOREY OR EQUAL M/C S GROUNDWATER DEPTH 56.4" 8 °o°°°Oa °o°°°°°o° °e ° °°°°°oa°off°o°°o°°o °0 8.25' O SEE BELOW 6"DEPTH 8 MIN BELOW INV. / <.' a PROPOSED ROCK WALL VENEER 8.52' 8.35 LEVEL BOTTOM o pp' 7.5' (SEE DETAIL) f A 4 55' BLOCK UP OOOOOOO D -BOX ACME -EVER TIP. D OR 5' MIN.UNSUITABLE DEPTH OF F 00 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 C O^OnOnOnO�O^O�O�O�O�O�O� Q. 750' SOIL REMOVAL '• 10 - SEPTIC SYSTEM PROFILE DEPTH WH�RPERSPECIFIED LOGS . INLET DEPTH = L 6" CRUSHED STONE OR MECHANICAL 5.0' y. OUTLET DEPTH = 14" COMPACTION. (15.221 [21) o°o°o°oo°°o°000 TIDALLY INFLUENCED GROUNDWATER _ 2.5' LEACHING: USE A 602 SF LEACHING FIELD 602 SF X .74 = 445 GPD O.K. (2-% SLOPE) (-L- r SLOPE) (-Lx x SLOPE) FOUNDATION 15' - SEPTIC TANK 2' D' BOX 12' LEACHING FACILITY ACCESS FOR ROUTINE MAINTENANCE T 80 ' 0.54 ACRES± / (12,745± UPLAND) R 8(5 del, NOTE: WETLAND RESOURCE AREAS FLAGGED BY LEC ENVIRONMENTAL CONSULTANTS, INC. `$\ -11.4 / A 5'r Qy del, alt, 0 LEC OHO �1�1, FLAG - 011, SM#1�//c� EXIST. / C./ BLOCK r BLOCK t! PAVED I PATP 5P `i1r, SM#2/ PROP. SITTING d11, WALL/AT EDGE J / OF +PATIO \`I` 101FI/o� oS�y SM#3 q10, 011, / .0. / PROP. VENT WITH CHARCOAL FILTER AND BUGSCREEN (FINAL PLACEMENT BY CONTRACTOR WITH HOMEOWNER CONSULTATION) WALK ►�1 PROP. 4 BR DWELLING -' FIRST FL. ELEV. 11.0' (CRAWLSPACE SLAB ELEV. MIN. 8.25') 5' UNSUITABLE SOIL REMOVAL LIMIT AROUND LEACHING FIELD .0, �' EXISTING 4 BR DWELLING (TO BE REMOVED AND REPLACED) EXISTING FIRST FL ELEV. = 9.4' Pis°`moo AH -1 8E MW _ (LEC) (DCE) / 10� \ v PROP. DRIVEWAY `I SpRONE,` / IVE AVED5`�`/ G VE 0 'b b PROPOSED 4 BR SEPTIC SYSTEM TO CONSIST OF A TITLE 5 COMPLIANT 1500 ROP. RET. )NALL GALLON SEPTIC TANK, DBOX, AND A ' TW = 9.0• 602 SF LEACH FIELD, BASE OF WHICH (DES;( , Y�THERS) IS 5' ABOVE HIGH GROUNDWATER. FINAL GRADE OVER SAS TO BE ELEV. / 10.0 -9.5' VARIES / BENCHMARK: C. BASIN AT ELEVATION 4.95' NGVD29 i SITE PLAN Scale: 1 "= 20' 0 NOTE: NO INCREASE IN TITLE 5 DESIGN FLOW, NOT "NEW CONSTRUCTION UNDER TITLE 5, 10 20 30 40 50 FEET VARIANCES REQUESTED UNDER MAXIMUM FEASIBLE COMPLIANCE 15.405: (la) LEACHING FIELD TO BE LOCATED 7.5' FROM LOT LINE (10' REQUIRED) VARIANCE OF 2.5' REQUESTED (1f) LEACHING FIELD TO BE LOCATED 25' FROM DRAIN WHICH MAY INTERCEPT HIGH GROUNDWATER- 50' REQ. 25' VARIANCE REQUESTED, WALL/LINER PROVIDED VARIANCE TO LOCAL BOARD OF HEALTH REGULATIONS REG. 3.7: LEACHING AREA TO BE 70.4' FROM COASTAL BANK, 100' REQUIRED, 29.6' VARIANCE REQUESTED DICE # 09-130 MUST BE PROVIDED FOR ZABEL FILTER. - 99-- EXISTING CONTOUR INSTALLER MUST FOLLOW ALL EXIST. SPOT ELEV. 99 MANUFACTURER'S SPECIFICATIONS FOR (98.4] PROPOSED SPOT EL. PROPER FILTER INSTALLATION TEST HOLE 22, SLOPE OF GROUND �0-) UTILITY POLE NOTE: 500E GAL RESERVE FIRE HYDRANT -W- PROVIDED W PC ALARM AND CONTROL PANEL FENCE LINE TO BE INSTALLED INSIDE BUILDING. ALARM TO BE ON INV. IN 7.2' SEPARATE CIRCUIT FROM PUMP 2" PRESSURE UNE _ ' ZABEL FILTER FLOAT SNITCH ALARM ON (A100) 14'TEE SLOPE TO DRAIN BACK OUTLET TEE W/EXTENSION SETTINGS: PUMP ON 1500 GAL MI . WEEP HOLE 5" WORKING RANGE 6" THIS SIDE OF BAFFLE CHECK VALVE MYERS SRM 4 PUMP OFF 12 SUBMERSIBLE 4/10 HP PUMP SYSTEM (OR EQUAL) (ON BLOCK) 4 DOSES PER DAY, AT 110 GAL. PER DOSE (5" WORKING RANGE) B' RAFFLE 2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION (NOT TO SCALE) TEST HOLE LOGS ENGINEER: DANIEL A. OJALA PE, PLS SE1805 WITNESS: AMY VON HONE RS, CHO DATE: JULY 1, 2009 PERC, RATE _ < 2 MIN/INCH CLASS I SOILS ELEV. 4 p" 7.0' O" 7.0' FILL FILL 3" LOAM 3" LOAM THEN SAND THEN SAND 24" 24" A LS A LS 27" 10YR 3/2 27" 10YR 3/2 B LS B LS 42„ 10YR 5/6 3.5' 42„ 10YR 5/6 3.5' PERC Cl Cl BOTT. AT 52', 24 GAL IN 9:30 < 2 MIN/INCH M/C S M/C S GROUNDWATER DEPTH 56.4" 2.5 Y 7/3EL. 2.3' 2.5 Y 7/3 el. 2.3' BUT TIDALLY INFLUENCED SEE BELOW 120" �_ J -3.0 120" 1 -3.0 NOTE: MONITORING WELL OVER LUNAR CYCLE EL. 2.5 TIDALLY INFLUENCED- USE 2.5 NGVD29 AS ADJUSTED HIGH GROUNDWATER ELEVATION (AUTOMATED MONITORING WELL SET, AND READINGS TAKEN OVER NEW MOON CYCLE DURING HIGHEST TIDES OF JUNE) 4" DIA PERF. INSP. PORT TO SAND AT BOTTOM OF LEACHING FIELD. 4" THREADED CAP, SCH40 PVC THREADED CAP TO WITHIN 3" OF FINISH GRADE 2% MIN. FINISH GRADE MAX . r MIN. 10" MIN. i LOAM AND SEED MIRAFI 140N FABRIC OR 2" PEASTONE ? 5' MIN. 3/4" TO 1 1/2" DOUBLE ADJ. _ WASHED STONE (NO FINES) GROUNDWATER 5' MIN.UNSUITABLE CROSS SECTION VIEW SOIL REMOVAL WHERE SPECIFIED DEPTH PER SOIL LOGS LEACHING FIELD TYPICAL DETAIL NOT TO SCALE ° DANIEL.. e<' DANIEL OJALA 'N� T CIVIL= OJALA q "S 2 ' No. 409 v DATE DANIEL A. OJALA, P.E., P.L.S. off 508-362-4541 fax 508-362-9880 downcope.com Q7 -I cope engineering, inc. civil engineers land surveyors 939 Moin Street ( Rte 6A) YARMOUTHPORT MA 02675 e Lewis Bay h X'odio RDod 51Dnd tl cyy'?P Oleo Nantucket Sound LOCUS MAP SCALE 1"=2000'± ASSESSORS MAP 14 PARCEL 3 DATUM: NGVD LOCUS IS WITHIN FEMA FLOOD ZONE B & Al2 ELEV. 10 AS SHOWN ON COMMUNITY PANEL #250015 0005 D DATED JULY 2, 1992 (NOTE: ELEVATIONS, BASED ON NGVD, INDICATE ENTIRE SITE IS WITHIN THE 100 YEAR FLOOD ELEVATION) WETLAND RESOURCE AREAS FLAGGED BY LEC ENVIRONMENTAL CONSULTANTS, INC. ZONING SUMMARY ZONING DISTRICT: R-25 MIN. LOT SIZE 25,000 S.F. MIN. FRONT SETBACK 30' MIN. SIDE SETBACK 15' MIN. REAR SETBACK 20' MAX. LOT COVERAGE: 25% UPLAND AREA (TO C. BANK) - 1277 SF PROP. LOT COVERAGE: 23.8%7 / SITE IS LOCATED WITHIN AP DISTRICT REFERENCES CTF 139728 LCP 14426H, LOT 80 LEGEND. - 99-- EXISTING CONTOUR X 99'1 EXIST. SPOT ELEV. 99 PROPOSED CONTOUR (98.4] PROPOSED SPOT EL. TH1 TEST HOLE 22, SLOPE OF GROUND �0-) UTILITY POLE FIRE HYDRANT -W- WATER LINE -X- FENCE LINE LOT LINE POST LIGHT IF' NOT ALL SYMBOLS MAY APPEAR IN DRAWINi SITE PLAN SHOWING PROPOSED DWELLING AT 355 GREAT ISLAND ROAD WEST YARMOUTH PREPARED FOR B. RODOALPH & M. MICOZZI JUNE 12, 2009 REV. JULY 1, 2009 (TH LOGS ETC.) REV. JULY 14, 2009 (FLOODZONES, ETC.) REV AUG. 10, 2009 (CRAWLSP. ELEV.) REV AUG. 18, 2009 (HEALTH DEPT. NOTES) REV AUG. 24, 2009 (FRONT STEPS) REV. SEPT. 15, 2009 (LOT COV.) REV. SEPT. 22, 2009 (T.W. EL) Scale: 1 "= 20' 0 10 20 30 40 50 FEET FILL- WV