HomeMy WebLinkAbout2 Morning Drive Proposed Septic Design.-
BPEO�
F FOUNDATION
A�T�ON
ELEV. = 102.50 .--,
(ASSUME
2' ABOVE HIGHT POIN'
;x'
;*r
A
I
3'
10 FT. MINIMUM
4' CAST IRON PIPE
(OR EQUAL) MINIMUM
PITCH 1/4' PER FT.
ELEV. - 99_5 _
ELEV. = 98.75
A
FT. MINIMUM FROM CELLAR
CONCRETE
COVERS 4" SCHEDULE 40 PVC PIPE
MIN. PITCH 1/8" PER FT.
FLOW
2,D"
ELEV. = 9a50_ LEVEL
GAS ELEV. 6' SUMP ELEV. 910_
BAFFLE DISTRIBUTION
ELEV.
(TO BE PLACED ON FIRM BASE)BOX-8L83--/
TO BE WATER TESTED
1500 GALLON IF MORE THAN ONE OUTLET
SEPTIC TANK (TO BE PLACED ON FIRM BASE)
3/4" TO 1 1/2" CLEAN J
DOUBLE WASHED STONE
FREE OF FINES do SILT
SEWAGE DISPOSAL SYSTEM PROFILE
NOT TO SCALE
CLEAN SAND
AND SEED
2" LAYER OF
1/8- TO 1/2-
.33
MAX. WASHED STONE VENT
100.5 MIN. NOT REQUIRED
99.33 °'
o .
fla
-=10" • EL V. _ _ 97.0 -
4 HIGH CAPACITY INFILTRATORS WITH
STONE IN AN
Y
SOIL TEST
DATE OF SOIL TEST $./JJPZ
SOIL TEST DONE BY CRAIG F..
WITNESSED BY -6miYQN HONE - "✓�
OBSERVATION HOLE 1 ELEV.=—Mo-5D OBSERVATION HOLE 2 ELEV.= 100.00 �o ,
PERCOLATION RATE <2_ MIN./INCH AT X52=64 INCHES PERCOLATION RATE < 2— MIN./INCH ATI C( S
DEPTH
HORIZ
TEXTURE
t
C
HIGH ..
3
POINT
-L
3
NO
t
WATER ENCOUNTERED AT _12'_ ELEV. _ _ AR -5
BE^+Cwd>P
(�rAft
_
nr✓
SOIL ABSORPTION
"
1I
A
t �
10184/2
u Par p
1
33"
0
LOAMY SAND
t0YR6/8
A
FT. MINIMUM FROM CELLAR
CONCRETE
COVERS 4" SCHEDULE 40 PVC PIPE
MIN. PITCH 1/8" PER FT.
FLOW
2,D"
ELEV. = 9a50_ LEVEL
GAS ELEV. 6' SUMP ELEV. 910_
BAFFLE DISTRIBUTION
ELEV.
(TO BE PLACED ON FIRM BASE)BOX-8L83--/
TO BE WATER TESTED
1500 GALLON IF MORE THAN ONE OUTLET
SEPTIC TANK (TO BE PLACED ON FIRM BASE)
3/4" TO 1 1/2" CLEAN J
DOUBLE WASHED STONE
FREE OF FINES do SILT
SEWAGE DISPOSAL SYSTEM PROFILE
NOT TO SCALE
CLEAN SAND
AND SEED
2" LAYER OF
1/8- TO 1/2-
.33
MAX. WASHED STONE VENT
100.5 MIN. NOT REQUIRED
99.33 °'
o .
fla
-=10" • EL V. _ _ 97.0 -
4 HIGH CAPACITY INFILTRATORS WITH
STONE IN AN
Y
SOIL TEST
DATE OF SOIL TEST $./JJPZ
SOIL TEST DONE BY CRAIG F..
WITNESSED BY -6miYQN HONE - "✓�
OBSERVATION HOLE 1 ELEV.=—Mo-5D OBSERVATION HOLE 2 ELEV.= 100.00 �o ,
PERCOLATION RATE <2_ MIN./INCH AT X52=64 INCHES PERCOLATION RATE < 2— MIN./INCH ATI C( S
DEPTH
HORIZ
TEXTURE
COLOR
MOTT.
OTHER
3
0
LOAMY SAND
3
NO
uNsuir.
WATER ENCOUNTERED AT _12'_ ELEV. _ _ AR -5
WATER ENCOUNTERED AT 11'_
ELEV. 89 0_
11. MINIMUM SETBACK 307 OF (84.40+625)/2-23'
SOIL ABSORPTION
"
9'
A
LOAMY SAND
10184/2
NO
APPROVED: BOARD HEALTH
33"
B
LOAMY SAND
t0YR6/8
NO
EL 97.25
33'
8
LOAMY SAND
10YR6/8
NO
EL•97.75
150'
C
FINE SAND
2.5Y7/6
NO
NUMBER OF BEDROOMS
DEPTH
HORIZ
TEXTURE
COLOR
MOTT.
OTHER L
3"
0
LOAMY SAND
3
NO
vwS�+7T,
WATER ENCOUNTERED AT _12'_ ELEV. _ _ AR -5
WATER ENCOUNTERED AT 11'_
ELEV. 89 0_
11. MINIMUM SETBACK 307 OF (84.40+625)/2-23'
SOIL ABSORPTION
"
8"
A
LOAMY SAND
10YR4/2
NO
APPROVED: BOARD HEALTH
33"
B
LOAMY SAND
t0YR6/8
NO
EL 97.25
140"
C
FINE SAND
2.5Y7/6
NO
DESIGN CALCULATIONS
jSrREET
LOT 6 AND LOT COMB/NED AREA
16,0511 SF. MAP 42
PARCEL 64LC PL.25JOJ9662
5 Lor s
fi. GARAGE
rt cl
DECK
C.
100 3
TOWN WATER —W—W—
SOIL CLASSIFICATION _j—_
FOR A MINIMUM OF 5 FEET FROM AROUND THE SOIL ABSORPTION SYSTEM
CATCH BASIN �8\
DESIGN PERCOLATION RATE <5_ MIN./IN.
AND BE REPLACED WITH SAND AS SPECIFIED IN 310 CMR 15.255: (3)
11' X 3T X 10" TRENCH FORMATION
3
S g
(I.E. TITLE 5) IF ENCOUNTERED BELOW S.A.S. PIPE INVERT.
WATER ENCOUNTERED AT _12'_ ELEV. _ _ AR -5
WATER ENCOUNTERED AT 11'_
ELEV. 89 0_
11. MINIMUM SETBACK 307 OF (84.40+625)/2-23'
SOIL ABSORPTION
"
ZOLL
Mlw 29
S
LEACHING CAPACITY (AREA X RATE) _3SQ_ GAL/DAY
APPROVED: BOARD HEALTH
ZONE
02
No. 27483,,x,
RESERVE LEACHING CAPACITY :360_ GAL./DAY
SYSTEM (SAS)
o usT
'w>. NhC/5h'g�'a,
LEGEND:
DESIGN CALCULATIONS
NOTES:
2.14
EXISTING SPOT ELEVATION 00„0
NUMBER OF BEDROOMS
3
PROPOSED SEPTIC DESIGN
TITLE 5 AND THE TOWN RULES AND REGULATIONS FOR THE .SUBSURFACE
EXISTING CONTOUR ----00----
GARBAGE DISPOSAL UNIT
N0
DISPOSAL OF SEWAGE.
USGS PROBABLE WATER TABL_ ELEV.'-
ye
FINAL SPOT ELEVATION ®
TOTAL ESTIMATED FLOW
OBSERVED WATER TABLE ( 5 / 01 / 02) ELEV. _
_M&L._
FINAL CONTOUR--- Q�Q}—
( 110 GAL/BR./DAY X �3 BR.)
_334_ GAL/DAY
j.
BOTTOM OF TEST HOLE ELEV. _
_$$ 5 _
SOIL TEST LOCATION
REQUIRED SEPTIC TANK CAPACITY
-15M_ GAL
y "
USED UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS.
UTILITY POLE -4-
ACTUAL SIZE OF SEPTIC TANK
1500 GAL.
4. ANY MASONRY UNITS USED TO BRING COVERS TO GRADE SHALL
jSrREET
LOT 6 AND LOT COMB/NED AREA
16,0511 SF. MAP 42
PARCEL 64LC PL.25JOJ9662
5 Lor s
fi. GARAGE
rt cl
DECK
C.
100 3
PROPOSED
DWELLING
�. 5 A•S O �/ GARAGE
SEPTIC
TANK
e.
t � l
� X11 � Y � �, s � j��,ore.•
1, )� •
DRIVEW uc 96.00'
K
,11X ( s
190.00 �.
E NOTE 10 ]
100 2 RNIN� %—
VE
MoiC
J—
TOWN WATER —W—W—
SOIL CLASSIFICATION _j—_
FOR A MINIMUM OF 5 FEET FROM AROUND THE SOIL ABSORPTION SYSTEM
CATCH BASIN �8\
DESIGN PERCOLATION RATE <5_ MIN./IN.
AND BE REPLACED WITH SAND AS SPECIFIED IN 310 CMR 15.255: (3)
GAS UNE
EFFLUENT LOADING RATE 9,7. GAL./DAY/S.F.
(I.E. TITLE 5) IF ENCOUNTERED BELOW S.A.S. PIPE INVERT.
CLEAN OUT C
LEACHING AREA 487 SQ. FT.
11. MINIMUM SETBACK 307 OF (84.40+625)/2-23'
CESSPOOL C.P.0
(Yi'X37")+(96'X10/127
-
OF
S
LEACHING CAPACITY (AREA X RATE) _3SQ_ GAL/DAY
APPROVED: BOARD HEALTH
CIVIL
487, X 0.74
No. 27483,,x,
RESERVE LEACHING CAPACITY :360_ GAL./DAY
'w>. NhC/5h'g�'a,
DATE .AGENT .:
NOTES:
1. ALL WORKMANSHIP AND MATERIALS' SHALL CONFORM TO D.E.P.
PROPOSED SEPTIC DESIGN
TITLE 5 AND THE TOWN RULES AND REGULATIONS FOR THE .SUBSURFACE
0
DISPOSAL OF SEWAGE.
ye
2. ALL COVERS TO SANITARY UNITS SHALL BE BROUGHT TO
LINDA SETHARES
WITHIN 6' OF FINISHED GRADE.
3. ALL COMPONENTS OF THE SANITARY SYSTEM SHALL BE CAPABLE OF
P, rs
j.
WITHSTANDING H-10 LOADING UNLESS THEY ARE UNDER OR WITHIN
i
10 FT. OF DRIVES OR PARKING AREAS -H-20 LOADING SHALL BE
y "
USED UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS.
4. ANY MASONRY UNITS USED TO BRING COVERS TO GRADE SHALL
j
BE MORTARED IN PLACE.
S. NO OLTERMiNATIGN HAS BEEN MADE -AS TO LGi.SrUANCC »I,R
DEEDED OR ZONING REGULATIONS. OWNER / APPLICANT IS TO
235 GREAT WESTERN ROAD
508— P. 0. BOX 1044
OBTAIN SUCH DETERMINATION FROM APPROPRIATE AUTHORITY.
398-8311. SOUTH DENNIS, MASS. 02660+
6• UTILITIES SHOWN ARE APPROXIMATE ONLY, EXCAVATION CONTRACTOR
alt
IS TO CALL "DIG -SAFE" AT 1-888-344-7233 AT LEAST 72 HOURS
DATE MAY 13, 2002
PRIOR TO COMMENCING WORK ON SITE.
SCALE 1 11_ 20'
7. CONTRACTOR IS TO VERIFY GRADES AND ELEVATIONS AS WELL A§
,
�.
SITE CONDITIONS PRIOR TO COMMENCING WORK ON SITE. ANY VARIATION
IS TO BE BROUGHT TO THE ATTENTION OF THE DESIGN ENGINEER '
IMMEDIATELY.
8. PARCEL 15 IN FLOOD ZONE _C &A—.
REwS£D --
SHEET 1 OF 1 .
9. LOT IS SHOWN ON ASSESSORS MAP _ 42 AS PARCEL_.
10, ALL UNSUITABLE MATERIAL SHALL BE REMOVED FROM UNDER, AND
PROPOSED
DWELLING
�. 5 A•S O �/ GARAGE
SEPTIC
TANK
e.
t � l
� X11 � Y � �, s � j��,ore.•
1, )� •
DRIVEW uc 96.00'
K
,11X ( s
190.00 �.
E NOTE 10 ]
100 2 RNIN� %—
VE
MoiC
J—
,
0 2002 CRAIG R. SHORT, P.E.
FOR A MINIMUM OF 5 FEET FROM AROUND THE SOIL ABSORPTION SYSTEM
AND BE REPLACED WITH SAND AS SPECIFIED IN 310 CMR 15.255: (3)
(I.E. TITLE 5) IF ENCOUNTERED BELOW S.A.S. PIPE INVERT.
5
11. MINIMUM SETBACK 307 OF (84.40+625)/2-23'
Of 41 ' '
"i4� Aro
°y\
:df ` �1YI LY•'.S� n
alai �fiik ,n..
�'. 1
-
OF
S
F,
APPROVED: BOARD HEALTH
CIVIL
No. 27483,,x,
f,
'w>. NhC/5h'g�'a,
DATE .AGENT .:
PROPOSED SEPTIC DESIGN
0
FOR
LINDA SETHARES
P, rs
LOC. PAR. 649 MORNING DRIVE
SOUTH YARMOUTH, MASS -
LoCvS
CRAIG R SHORT, P.L.'
235 GREAT WESTERN ROAD
508— P. 0. BOX 1044
398-8311. SOUTH DENNIS, MASS. 02660+
DATE MAY 13, 2002
�y}
SCALE 1 11_ 20'
4
�f �7
JOB N0. `12-94/
RSED
EVI
- LOCATION MAP
REwS£D --
SHEET 1 OF 1 .
,
0 2002 CRAIG R. SHORT, P.E.
0 2002 CRAIG R. SHORT, P.E.