HomeMy WebLinkAbout31 Moss Road Site & Sewage Disposal SystemGENERAL NOTES:
A.) NEITHER DRIVEWAYS NOR PARKING AREAS ARE ALLOWED OVER SEPTIC SYSTEM
UNLE55 H-20 COMPONENTS ARE USED.
B.) THE DESIGNER WILL NOT BE PESPON51BLF FOR THE SYSTEM AS DESIGNED UN -
j LE55 CONSTRUCTED AS SHOWN. ANY CHANGES SHALL BE APPROVED IN WRITING.
C.) CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION OF ALL
UNDERGROUND AND OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK.
CONSTRUCTION NOTES:
1.) ALL CONSTRUCTION SHALL CONFORM TO THE STATE ENVIRONMENTAL CODE,
TITLE 5, AND THE REQUIREMENTS OF THE LOCAL BOARD OF HEALTH.
2.) SEPTIC TANK(5), GREASE TRAP(5), DOSING CHAMBER(5) AND DISTRIBUTION
BOX(E5) SHALL BE SET ON A LEVEL STABLE BASE WHICH HAS BEEN MECHANICALLY
COMPACTED, OR ON A G INCH CRUSHED STONE BA5E.
3.) SEPTIC TANKS) SHALL MEET A5TM STANDARD C 1 127-93 AND SHALL HAVE
AT LEAST THREE 20" DIAMETER MANHOLES. THE MINIMUM DEPTH FROM THE BOT-
TOM OF THE SEPTIC TANK TO THE FLOW LINE SHALL BE 48".
4.) SCHEDULE 40 PVC INLET AND OUTLET TEF5 SHALL EXTEND A MINIMUM OF 6"
ABOVE THE FLOW LINE OF THE 5EFTIC TANK AND SHALL BE INSTALLED ON THE
CENTERLINE OF THE TANK DIRECTLY UNDER THE CLEANOUT MANHOLE.
5.) PAI5E COVERS OF THE SEPTIC TANK AND DISTRIBUTION BOX WITH PRECAST
CONCRETE WATER TIGHT RISERS OVER INLET AND OUTLET TEES TO WITHIN G" OF
FIN 15H GRADE, OR AS APPROVED BY THE LOCAL BOARD OF HEALTH AGENT.
6.) PIPING SHALL CON515T OF 4" SCHEDULE 40 PVC OR EQUIVALENT. PIPE SHALL
BE LAID ON A MINIMUM CONTINUOUS GRADE OF NOT LESS THAN I %.
7.) DISTRIBUTION LINES FOR 501L AB50PPTION SYSTEM (AS REQUIRED) SHALL BE
4" DIAMETER SCHEDULE 40 FVC LAID AT 0.005 FTJFT. LINE SHALL BE CAPPED
AT END OR AS NOTED.
8.) OUTLET PIPES FROM DISTRIBUTION BOX SHALL REMAIN LEVEL FOR AT LEAST
2' BEFORE PITCHING TO 501L ABSORPTION SYSTEM. WATER TEST DISTRIBUTION
BOX TO ASSURE EVEN DISTRIBUTION.
9.) DISTRIBUTION BOX SHALL HAVE A MINIMUM SUMP OF G" MEASURED BELOW
THE OUTLET INVERT.
10.) BASE AGGREGATE FOR THE LEACHING FACILITY SHALL CON515T OF 314" TO
1- 112" DOUBLE WASHED STONE FREE OF (RON, FINES AND DUST AND SHALL BE
INSTALLED BELOW THE CROWN OF THE DISTRIBUTION LINE TO THE BOTTOM OF THE
SOIL ABSORPTION SYSTEM. BASE AGGREGATE SHALL BE COVERED WITH A 2"
LAYER OF I /8" TO 1/2" DOUBLE WASHED STONE FREE OF IRON, FINES AND DUST.
1 1.) VENT SOIL ABSORPTION SYSTEM WHEN DISTRIBUTION LINES EXCEED 50 FEET;
WHEN LOCATED EITHER IN WHOLE OR IN PART UNDER DRIVEWAYS, PARKING AREAS,
TURNING AREAS OR OTHER IMPERVIOUS MATERIAL; OR WHEN PRESSURE DOSED.
12.) SOIL ABSORPTION SYSTEM SHALL BE COVERED WITH A MINIMUM OF 9' OF
CLEAN MEDIUM SAND (EXCLUDING TOP501U.
13.) FINISH GRADE SHALL BE A MAXIMUM OF 36" OVER THE TOP OF ALL SYSTEM
COMPONENTS, INCLUDING THE SEPTIC TANK, DISTRIBUTION BOX, DOSING CHAMBER
AND 501L ABSORPTION SYSTEM. SEPTIC TANK5 SHALL HAVE A MINIMUM COVER
OF 9".
14.) FROM THE DATE OF INSTALLATION OF THE SOIL ABSORPTION SYSTEM UNTIL
RECEIPT OF A CERTIFICATE OF COMPLIANCE, THE PERIMETER OF THE SOIL ABSORP-
TION SYSTEM SHALL BE STAKED AND FLAGGED TO PREVENT THE USE OF SUCH
AREA FOR ALL ACTIVITIES THAT MIGHT DAMAGE THE SYSTEM.
15.) THE BOARD OF HEALTH SHALL REQUIRE INSPECTION OF ALL CONSTRUCTION
BY AN AGENT OF THE BOARD OF HEALTH (OR THE DESIGNER IF TH15 SYSTEM RE-
QUIRES A VARIANCE) AND MAY REQUIRE SUCH PERSON TO CERTIFY IN WRITING
THAT ALL WORK HAS BEEN COMPLETED IN ACCORDANCE WITH THE TERMS OF THE
PERMIT AND APPROVED PLANS. 48 HOURS ADVANCE NOTICE 15 REQUESTED.
I G.) ALL TOPSOIL 4 SUBSOIL (A 4 B) ENCOUNTERED WITHIN 5' AROUND THE 5.A.5.
SHALL BE REMOVED DOWN TO THE CLEAN SAND AND REPLACED WITH CLEAN SAND,
COMPACTED TO MINIMIZE SETTLEMENT.
17.) ALL FILL USED ON PROJECT SHALL BE CLEAN AND FREE OF DEBRIS. FILL SHALL
BE PLACED IN G-8" UrT5 AND BE COMPACTED TO 95% OF MAXIMUM DRY DENSITY
AS PER AA5HO T 180, METHOD D. FILL TO BE USED SHALL CONFORM TO
31 O CMR 15.255 (3).
CONSERVATION NOTES:
1.) LIMIT OF WORK SHALL BE AS SHOWN ON PLAN VIEW. THE LIMIT OF WORK
SHALL CONSIST OF DOUBLE STAKED HAYBALE5 OR SILT BARRIER AS CONDITIONED
BY CON5tRVATION COMMISSION AND SHALL BE CON5TRUCTED PRIOR TO ANY
WORK ON THE PROJECT.
2.) ROOF RUN-OFF SHALL BE CONTROLLED THROUGH GUTTER, DOWNSPOUTS,
4 DRY -WELLS OR BY STONE TRENCHES (2'x I') LOCATED UNDER ALL DRIP LINES.
3.) ALL DISTURBED AREAS SHALL BE REVEGETATED UPON THE COMPLETION
OF THE PROJECT.
4.) ALL FILL REQUIRED FOR THE PROJECT SHALL BE CLEAN SAND, FREE OF DEBRIS
AND GARBAGE. UN -USED MATERIAL SHALL BE REMOVED FROM PROPERTY.
FINISH WITH BLACK
BARK MULCH , °
< O
e
prGek4i . O 13EARBEPPY 2 GAL. MIN
SHORE JUNIPER 2 GAL MIN
n1 (� 3} •
PLANTING DETAIL:
SCALE I "=20'
FLOW PROFI LE:
NOT TO SCALE
24" DIAMETER CONCRETE COVERS
RAISED TO WITHIN G" OF FINISH
FINISH FLOOR GRADE (OR A5 NOTED)
EL= I G.O± (SEE NOTE #5)
Prono5ed EL= 1 1.5± 7
I O"
iii 410"
14"
T
GAS BAFFLE -
1 500 GALLON
SEPTIC TANK
SOIL TEST LOGS:
TEST PIT 1: EL=5.3±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUN5EW
SOIL
MOTTLING
OTHER
0-10
A
Loamy Fine Sand
I OYR 313
NONE
NONE
10-24
B
Loamy Fine Sand
I OYR 8
NONE
Fine Sand
24-84
CI
Loamy Sand
I OYR 7/5
NONE
Perc 24'
Groundwater R EL=49"
C2
Fine Sand
I OYP 612
NONE
Groundwater 0 EL=40"
TEST PIT 2: EL=6.2±
DEPTH FROM SOIL
SURFACE HORIZON
(INCHES)
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUN5EW
SOIL OTHER
MOTTLING
O-
Loam Fine Sand
I OYR 3/3
NONE
7-26 B
Loam Fine Sand
I OYR 5/8
NONE
2G-81 I
Fine San
I OYR 6/4
NONE Perc 58"
CI
Fine Sand
I OYR G14
Groundwater EL=58"
TFST PIT 3: EI_=58±
DEPTH FROM
SURFACE
(INCHES)
501L
HORIZON
50L
T URE
(U DA)
501L
COLOR
(MUN5EW
SOIL OTHER
MOTTLING
0-9
A
LoAmy Fine Sand
I OYR 313
NONE
9-2G
B
Loamy Fine Sand
I OYR 5/8
NONE
2G-82
CI
Fine Sand
I OYR G14
NONE
Medium Loamy Sand
I OYR GIG
NONE
Loose Weepmq H2O R 42"
Groundwater R EL=49"
TEST PIT 4: EL=5.3±
DEPTH FROM
SURFACE
(INCHES)
501L
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MON- EW
SOIL OTHER
MOTTIJNG
0-8
A
Loam Fine Sand
I OYR 313
NONE
8-2
B
Loam Fine Sand
I OYK 5/8
NONE
25-83
C I
Loamy Sand
I OYR 7/8
NONE
Medium Loamy Sand
I OYR GIG
NONE
Loose Weepmq H2O R 42"
Groundwater P EL -44"
DATE OF TESTING: 04122/10
PERCOLATION RATE: LE55 THAN 2 MINANCH IN "C" LAYERS.
WITNESSED BY: KEITH E. FERNANDES, FIT, J.M. OREILLY C ASSOCIATES, INC.
AMY VON HONE, AGENT, YARMOUTH HEALTH DEPARTMENT
STANDING GROUNDWATER ENCOUNTERED AS NOTED
USE A LOADING RATE OF 0.74 GPD/5F FOR SIZING OF SOIL ABSORPTION SYSTEM.
I
1
DRIP LINE
1
1
1 2" OF I/8"-1/2" STONE
1
T
2'
3/4"- 1 112" STONE WRAPPED
�I IN FILTER FABRIC
NOTE:
STONE TRENCH SHALL BE CENTERED UNDER ALL
DRIP EDGE5 AND ALONG THE EDGE OF THE STONE
POOL DECK.
TYPICAL STONE DRIP LINE TRENCH DETAIL:
NOT TO SCALE
SOIL TEST LOGS:
HAND BORING I: EL -5.1±
DEPTH FROM
SURFACE
(INCHES)
501L
HORIZON
SOIL
TEXTURE
(USDA)
501L
COLOR
(MUN5EW
SOIL
MOTTLING
OTHER
0-11
A
Fine Sand
I OYP 1
NONE
Loose
11-17
B
Fine Loamy Sand
I OYR 414
NONE
Friable
17-83
CI
Medium Loamy Sand
I OYR GIG
NONE
Loose Weepmq H2O R 42"
83-108
C2
Fine Sand
I OYP 612
NONE
Verj Friable
N
ui
J
w
J
w
HAND BORING 2: EL=4.9±
DEPTH FROM
SURFACE
(INCHES)
501L
HORIZON
501L
TEXTURE
(USDA)
501L
COLOR
(MUN5EW
SOIL
MOTTLING
OTHER
0-7
A
Fine Sand
I OYR 5/1
NONE
Loose
7-19
B
Fine Loamy Sand
I OYR 4J4
NONE
Friable
19-52
CI
Medmm Loamy Sand
IOYR 6J6
NONE
Loose Wee m H20ED 0"
52-109
C2
Fine Sand
I OYR G)2
NONE
Very Friable
N
ui
J
w
J
w
DATE OF TESTING: 09/04/96
PERCOLATION RATE: LE55 THAN 2 MIN/INCH IN "C' LAYERS.
WITNESSED BY: MATTHEW T. FARREL, EIT, J.M. O'REILLY 4 ASSOCIATES, INC.
AMY VON HONE, AGENT, YARMOUTH HEALTH DEPARTMENT
NO WATER ENCOUNTERED
USE A LOADING RATE OF 0.74 GPD/5F FOR SIZING OF 501L ABSORPTION SYSTEM.
BUILDING COVERAGE:
DWELLING 1,577.2 SF
WOOD DECK 607.7 SF
POOL 738.8 5F
POOL DECK 607.4 51'
POOL TROUGH 81.8 5F
ENTRY 193.2 5F
SHOWER 40.0 5F
WALI5 70.0 5F
TOTAL 4, 189. 1 5F
r ----Utility Pole #4
4, 189.1 X86
18.731 x100=22.4%
PETER F. 5ARTHOU 4
- EL=5.55 MIMI I. 5ARTHOU
CALCU .ATI ONrJ : LAND COURT DOCUMENT #1 15351
PARCEL IIG
INFILTRATION RATE: 0.9 GAL/5F/MIN (SAND)
BACKWASH BED: 32'x 12'x 18"
22' SURFACE AREA: [2(I 2 x 1.5) + 2(32 x 1.5) + (32 x 1.5))=516 5F \
INFILTRATION CAPACITY: 516 5F x (0.9 GAL/SF/MIN)
(I 8" Effedve %�
Depth) =464 GAUMIN
BACKWASH FILTER TO BE LIMITED TO 100 GAUMIN
VOLUME: 32 x 12 x 1 .5=576 CF
-EL=3.75 57G x 45%=259 CF - 1930 GAL.
EL=2.75 (GROUND WATER)
NOTE:
CONSTRUCT BY PLACING THREE (3) - 8' x 4' FLOW DIFFUSERS NSE FD
4'x 8'- D FLOW DIFFUSER UNITS BY 5HOREY PRECAST, INC.) WITH 4'
OF STONE AROUND AND G" OF STONE BELOW
BACKWASH BED DETAIL:
NOT TO SCALE
INSPECTION NOTE: -
PRIOR TO FINAL INSPECTION BY THE ENGINEER, SYSTEM
NEEDS TO BE COMPLETE INCLUDING BUILDUP FOR COVERS.
Proposed EL= I I .O± ProO5ed EL=9.8± Min.
INSPECTION PORT
9" Cover Min.
1: 10.0
DB -3
D -BOX
H-20
Longest Run = 8'±
LEACHING FIELD
45.0'x 15.0'x G.O"
O
PROP05ED GAS LINE
(APPROXI'MATE)
PROPOSED f\AI ING
WALL T.O.W. EL= 9. ±
VARIES TO EL=6.0± \
PROPOSED SWALE
BOTTOM OF SWALE EL=4.)5±
SYSTEM DESIGN CALCULATIONS:
SEWAGE DESIGN FLOW:
4 BEDROOM DWELLING @ I 10 GPD = 440 GPD
LEACHING CAPACITY REQUIRED:
4 BEDRO M5 (MAX.) @ 1 IQ GPD = 440 GPD REQUIRED
SEPTIC TANK CAPACITY REQUIRED:
DAILY FLOW = 440 GPD @ 200% = 880 GAL. REQUIRED
SEPTIC TANK CAPACITY PROVIDED:
1 500 GALLON SEPTIC TANK (MIN. ALLOWED)
LEACHING CAPACITY PROVIDED:
ONE (1) 45.0'X 15.0'X G" LEACH FIELD CAN LEACH:
Vt = (45.0 X 15.0) X 0.74 GPD/5F=499.5 GPD
499 GPD>440 GPD REQUIRED
NOTE: A GARBAGE DISPOSAL 15 NOT PERMITTED WITH THI5 DESIGN.
INSTALL:
NE (1) - 1500 GALLON SEPTIC TANK
ONE (1) - 3 OUTLET DISTRIBUTION BOX (H-20 Rated)
ONE (1) - 45.0'x 15.0'x 6" LEACH FIELD
MOSS ROAD
5LATERAL SOIL REMOVAL
(SEE NOTE # I G) _-
INSPECTION PORT
c--� s I+ e -c 6 -0 -a -4,Q g2.22,
L a e c-
48.24' -+..... _ -�
Sx '.
40MILHDPEUNER
LOG
I I -05-9G EL=2.61
TOP @ EL=4. I +
I I- I I_96 EL=2.49
BOTTO>.; @ L',=3.0±
a' I
n B
✓;
PROPOSED LANL6CAPE WALL
x 7.5
'
I 1-25-9G EL=2.25
TOP Of WALL VAR5 5
04-10-10 EL=2.40
5x9
i
EL=2."5 HISTORIC HIGH GROUNDWATER
O
i.,
OO
G b IS
N
ui
J
w
J
w
3
3
w
N
j
40MILHDPEUNER
LOG
I I -05-9G EL=2.61
TOP @ EL=4. I +
I I- I I_96 EL=2.49
BOTTO>.; @ L',=3.0±
I I -14-9G EL=2.25
PROPOSED LANL6CAPE WALL
x 7.5
'
I 1-25-9G EL=2.25
TOP Of WALL VAR5 5
04-10-10 EL=2.40
5x9
EL=2."5 HISTORIC HIGH GROUNDWATER
O
o
O
N
ui
J
w
J
w
3
3
w
N
j
Q,�,e1\in9
PJd9eCI,_h X22'} ,
Bvddm0�e�9
I�PROFOSED 4
DeEJ
1 6.9 I
x 7.0
POOL
(EL= 13.0±)
10
PROPO
GRADE
5
Existing
Grade
O
0
A
3/
MONITOR WELL
LOG
I I -05-9G EL=2.61
I I- I I_96 EL=2.49
I I -14-9G EL=2.25
I 1-25-9G EL=2.25
04-10-10 EL=2.40
EL=2."5 HISTORIC HIGH GROUNDWATER
o
O
N
ui
J
w
J
w
3
3
w
N
N
U_
0
O
O
M
w
w
w
d
N
<F
G. 1'
_
iED�. � I
L
EL=4.5± U
6' DEEP 5TONEN BED @ BOTTOM
OF SWALE - 3/4"- 1 112" STONE;
�-
BOTTOM OF BED EL=4.0±
10 20
30
40
IN
CROSS SECTION
A -W:
hORIZONTAL SCALE I "= 10'
VERTICAL SCALE I "= 10'
LENCHMARK:
Tor of Water Gate
E'.-5.6± (MSL 1929 NGVD Datum)
100 YR FLOOD PLAIN
ZONE: Al2
ELEVATION= 10
FROM FEMA MAPS
COMMUNITY PANEL
#250015 0005D
JULY 2, 1992
__TFTAT5N6 A
PROPOSED SWALE BOTTOM EL=4.8± VELOCITY ZONE
S
-
ALL AREAS OF THE FRONT PORTION OF THE DWELLING
THAT ARE LOCATED WITHIN 20' OF PRIMARY* RESERVE
5.;.5. SHALL BE CONSTRUCTED U51 NG SLAB ON GRADE
WITH A MINIMUM 5LA6 EL= 10.0
- PROPOSED 6" STONE BED @ BOTTOM OFSWALE
314" - I 1/2' STONE
- PROPOSED 2' WIDE DRIP LINE TRENCH ON 3:1 SLOPE -
COlI5TRUCT 3 CHECK DAMS TO SLOW RUN-OFF
T -A PROPOSED WATERLINE
1(APPROXIMATE)
4.6 �lFer
PAULETTE J. FINNERTY REVOCABLE TRUST
PAULETTE J. FINNERTY, TRUSTEE
CERTIFICATE OF TITLE # 177554
PARCEL 114
z !2 PROPOSED 2' WIDE DRIP LINE
k
•'"� ) TRENCH (f W.)
ir
4 i
PROPOSED OUTDOOR SHOWER TO 51T ON
P CEEP 3/4" TO 1 1/2" GRAVEL n'=0 FOR
DKAINAGE
x ,9 �
\ \ f
O O ED ! 50 BuFfer
Zone
5 K 6.3 '
r
b" Bikar
Zone
PPOP05FD SWALE
BOTTOM OF SWALE EL -4.5±
PROPOSED LIMIT OF WORK
(SEE CONSERVATION NOTE # 1)
\ \ x 7.3 I to O O
\ o
i \ Over x 71 PR 5ED +
9S, PROPOSED POOL
BACKWASH B -_D (SEE DU xx
ET _ % r� S �-
\` / rt -r O /
3.4/x\
SOP \I / /f.✓ SOP#2
\30��
DEP OBSERVATION
9 / s
Vill 9.4 I _ _ �J 1 - /t/` / ', DEP OB5ERVATION PLOT #2
PROPOSED 5':✓ALE`- ' . •-•• / //}' 3.1 /
BOTTOM EL='3.Om 7 ~� / / 4yy'aC� 1 1
x5.4 8 tills I
� x62/ �i
O WPROPORK LIAIT er ' / 3.4 '` l
/ 4 �. 3.6
�h Td", \ / /
X4.4
x 5.5
/ 5
/
4.0 t
L� 4 � /
LJ �� Revised 05/13110: Re'
„ „ - „ JOSEPH N. PETROWSKI 4 � i Vegetated
- 2 LAYER OF 1 /8 1 /2 STONE DEBRA T. PETROW5KI 3,9 wetland PLAN
CAP LAND COURT DOCUMENT #543091 4111
3/4" - 1-1 /2" STONE PARCEL 121 ®-_ SCALE 1"=29 do Gregg L15ciot
THIS AREA IS SERVED E SEV�
8.35 6 / BY TOWN WATER. SIT
A:-. \ � 3.4
31 1
T
J.M
i,� Prol
�- EL=2.75 HIGH GROUNDWATER LI
- O 20 40 60
111
SCALE 1"=29 (508)898-8801
ib DATE:
G:WA)obs\LI5eXoM Developmen!AMo 5Road127GAWwg\l 27GA.SD5.rev5-13-IO.dwg 04/21/10
FILE COPY
. ii/F-�i�x 7.4
Ewsti
Ridg
e 2)ng
Bwldrng zt
N92e1ght_2 f.9'*
VARIANCE REQUEST:
SECTION 3.7 DISTANCE LOCATION OF
DISPOSAL FACILITIES
• SPECIFICALLY: THE REQUIREMENT OF "NO
FILL SHALL BE DEPOSITED WHEN THE
WATER TABLE 15 WITHIN FOUR (4) FEET OF
THE ORIGINAL GRADE"
• PROJECT 15 PROPOSING TO MOUND THE
SEWAGE SYSTEM 50 AS TO MAINTAIN
THE FIVE (5) FEET OF SEPARATION ABOVE
GROUNDWATER TO THE BOTTOM OF THE
5.A.S.