HomeMy WebLinkAbout134 Old Main Street - First Floor Plan SouthNOTES:
1. INSTALL WIRE GUARDS ON ALL SPEAKERS AND HANDSETS
IN GYMNASIUM AND EXTERIOR TO BUILDING.
2. FOR GENERAL NOTES AND LEGEND SEE DRAWING T-0.1
3. FOR COMMUNICATIONS SYSTEM RISER DIAGRAM AND
INSTALLATION DETAILS SEE DRAWING T-5.1.
4. CONTRACTOR SHALL PROVIDE AND INSTALL NEW 20A -1P
BRANCH CIRCUIT BREAKER WITHIN EMERGENCY POWER PANEL
"EPP1" TO PROVIDE POWER TO NEW INTERCOM/PA SYSTEM.
NEW CIRCUIT BRANCH CIRCUIT BREAKER SHALL MATCH
EXISTING IN FRAME SIZE AND AIC RATING. SEE DRAWING T-2.1
FOR LOCATION OF EMERGENCY POWER PANEL "EPP1".
5. CONTRACTOR SHALL VERIFY TYPE AND PROVIDE
RECEPTACLE AT INTERCOM/PA CABINET TO PRO4fIDE POWER TO
INTERCOM/PA SYSTEM.
6. POWER BRANCH CIRCUITRY SHALL BE INSTALLED IN
CONDUIT FROM THE PANEL TO THE FIRST DEVICE. POWER
BRANCH CIRCUITRY MAY BE TYPE MC CABLE WHERE
CONCEALED ABOVE SUSPENDED CEILINGS AND IN METAL STUD
WALLS.
I D.3::>rriftllc� �«4i1�4nsR912 413gbdr«eA6Hav� llbshnrtnhaetl3, iAg50=14tB56pa�D;P."fflk21224\Elet\21224T23.dq 111-14-01 1 10:09 1 Dmicciche
UP
Nq ENGINEERS
Andover, MA
Boston, MA
Richard D. Kimball Company, Inc
200 Brickstone Square
Andover. MA 01810-1488
P 978-475-0298
F 978-475-5768
W
This CADD Document is an instrument of
professional service, and shall not be used, in
whole or in part, for any project other than for
which it was created Without the expressed,
written consent of the Richard D. Kimball
Company, Inc. Any unauthorized use, reuse,
modification or alteration, including automated
conversion of this document shall be at the user's
sole risk without liability or legal exposure to the
Richard D. Kimball Company, Inc.
ISEVISIONS1,71
A DATE CHK DESCRIPTION
00EAL [111 110 '"
IRROJECT
NUMBER
21224
March 19, 2003
Dennis Yarmouth
Regional School District
John Simpkins
Elementary School
Communications System
Replacement
[MRAWING
DRAWN BY
D. Micciche
CHECKED BY
A. Robinson
SCALE
118" = 1'-0"
Demolition and New Work
Communications System
First Floor Part Plan
South
1
81