Loading...
HomeMy WebLinkAbout10 Old Hyannis Road - 09 - Electrical Details & NotesSCALE: 1=1 W:\SPRINT\7472\CAPECOD\73\RBA663E2.DWG 8/4/99 DR NOTES AMP 0 1. ELECTRICAL NOTES CABLE TO GROUND BAR ANTENNA 2. WATER 1. INSPECTIONS COAX GND KIT ANTENNA ANTENNA ANTENNA DETAILS, SEE LAYOUT DRAWINGS. A. GENERAL: DURING AND UPON COMPLETION OF THE WORK, ARRANGE AND PAY ALL ASSOCIATED CABLE TRAY. B. SHORT CIRCUIT RATINGS: PROVIDE EQUIPMENT WITH HIGHER FAULT CURRENT RATINGS AS NOTE 1 INSPECTIONS OF ALL ELECTRICAL WORK INSTALLED UNDER THIS CONTRACT, IN ACCORDANCE TO CONCRETE. NEEDED TO MATCH UTILITY COMPANY AVAILABLE FAULT CURRENT. ANTENNA COAX ANTENNA COAX ANTENNA COAX WITH THE CONDITIONS OF THE CONTRACT. DETAIL 569-5 ON DRAWING E4. 3 GND KIT , CABLE i �— SEE DWG. E1 B. INSPECTIONS REQUIRED: AS PER THE LAWS AND REGULATIONS OF THE LOCAL AND/OR STATE 8. TELEPHONE SERVICE i AGENCIES HAVING JURISDICTION AT THE PROJECT SITE. CABLE CABLE m a DO m ; A. GENERAL: INSTALLATION SHALL BE IN ACCORDANCE WITH TELEPHONE UTILITY COMPANY'S C. INSPECTION AGENCY: APPROVED BY THE LOCAL AND/OR STATE AGENCIES HAVING JURISDIC- - RULES AND REGULATIONS. G Q TION AT THE PROJECT SITE. GND BAR • a a D. CERTIFICATES: SUBMIT ALL REQUIRED INSPECTION CERTIFICATES. 9. GROUNDING SYSTEM w NOTE 1.3 4 4 - O A. INSTALLATION: INSTALL AS INDICATED ON THE DRAWINGS AND AS REQUIRED: L O ¢ 2. HANGERS AND SUPPORTS p) w 1. BOND ALL CABLE TRAY SECTIONS. 04 w ,z, A. MATERIALS: ALL HANGERS, SUPPORTS, FASTENERS AND HARDWARE SHALL BE ZINC COATED OR ; 1 1 OF EQUIVALENT CORROSION RESISTANCE BY TREATMENT OR INHERENT PROPERTY, AND SHALL BE J z MANUFACTURED PRODUCTS DESIGNED FOR THE APPLICATION. PRODUCTS FOR OUTDOOR USE 10. CHECKOUT, TESTING, AND ADJUSTING SHALL BE HOT DIP GALVANIZED. A. CORRECTION/REPLACEMENT: AFTER TESTING BY CONTRACTOR, OWNER OR ENGINEER, CORRECT ANY DEFICIENCIES, AND REPLACE MATERIALS AND EQUIPMENT SHOWN TO BE DEFECTIVE OR TOP OF I B. TYPES: HANGERS, STRAPS, RISER SUPPORTS, CLAMPS, U -CHANNEL, THREADED RODS, ETC. AS UNABLE TO PERFORM AT DESIGN OR RATED CAPACITY. TOWER: z z _ INDICATED OR REQUIRED. B. POWER CONDUCTORS: CONTRACTOR SHALL CONDUCT A CONTINUITY & INSULATION TEST ON 2 BCW CONDUCTORS BETWEEN SERVICE DISCONNECT SWITCH & POWER CABINET. C. INSTALLATION: RIGIDLY SUPPORT AND SECURE ALL MATERIALS, RACEWAY AND EQUIPMENT TO BUILDING STRUCTURE USING HANGERS, SUPPORTS AND FASTENERS, SUITABLE FOR THE USE, C. WHEN SITE POWER IS DERIVED FROM 3 PHASE SOURCE LOAD READINGS WILL BE TAKEN AND MATERIALS AND LOADS ENCOUNTERED. PROVIDE ALL NECESSARY HARDWARE. PROVIDE CONDUIT RECORDED TO MAINTAIN A BALANCED LOAD AT THE PRIMARY SOURCE. RECORDS SHALL BE 2 AWG AING CIGBE INSULATED CIGBE SUPPORTS AT MAXIMUM 5 FT. O.C. TURNED TO THE OWNER'S REPRESENTATIVE. I POWER PROTECTION GREEN Z2 0. OVERHEAD MOUNTING: ATTACH OVERHEAD MOUNTED EQUIPMENT TO STRUCTURAL FRAMEWORK OR 11. QUALITY ASSURANCE I CABINET SUPPORTING METAL FRAMEWORK. MIGB NOTES 2 & 3 I TELCO POWER (PPC -MINI)) I 8Y OTHER BOTTOM 3 A. INSTALLERS QUALIFICATIONS: FIRM WITH NOT LESS THAN FIVE YEARS EXPERIENCE IN THE I PANEL PANEL NOTE 2 OF TOWER a W INSTALLATION OF ELECTRICAL SYSTEMS AND EQUIPMENT SIMILAR IN SCOPE AND COMPLEXITY E. WALL MOUNTING: SUPPORT WALL MOUNTED EQUIPMENT BY MASONRY, CONCRETE BLOCK, METAL N I I TO THOSE REQUIRED FOR THIS PROJECT, AND HAVING SUCCESSFULLY COMPLETED AT LEAST U U FRAMING SUB -FRAMING. Lm TEN COMPARABLE SCALE PROJECTS. Q M F. EXTERIOR WALLS: MOUNT ALL EQUIPMENT LOCATED ON THE INTERIOR OF EXTERIOR BUILDING B. INCIDENTAL WORK: PAINTING, PATCHING, WELDING, CARPENTRY, MECHANICAL WORK AND THE I WALLS, AT LEAST ONE INCH AWAY FROM WALL SURFACE, USING SUITABLE SPACERS. LIKE RELATED TO OR REQUIRED FOR ELECTRICAL WORK SHALL BE PERFORMED BY CRAFTSMAN a GROUND z SKILLED IN THE APPROPRIATE TRADE, BUT SHALL BE PROVIDED FOR UNDER THIS CONTRACT. RODS) G. STRUCTURAL MEMBERS: DO NOT CUT, DRILL OR WELD ANY STRUCTURAL MEMBER EXCEPT AS 12. CIRCUIT BREAKERS SPECIFICALLY APPROVED BY THE ENGINEER. A. GENERAL: MOLDED CASES WITH THERMAL AND MAGNETIC TRIPS UNLESS INDICATED OTHER - CABLE WISE. H. INDEPENDENT SUPPORT: DO NOT SUPPORT MATERIALS OR EQUIPMENT FROM OTHER EQUIPMENT, CONDUITS PIPING, DUCTWORK OR SUPPORTS FOR SAME. B. INDIVIDUALLY MOUNTED: ENCLOSURES AS SPECIFIED ABOVE, UNLESS INDICATED OTHERWISE. I. RACEWAY SUPPORTS: RIGIDLY SUPPORT ALL RACEWAY WITH MAXIMUM SPACINGS PER NEC, AND PPC MINI SO AS TO PREVENT DISTORTION OF ALIGNMENT DURING PULLING OPERATION. USE APPROVED 13. SAFETY SWITCHES HANGERS, CLAMPS AND STRAPS FOR INDIVIDUAL RUNS. DO NOT USE PERFORATED STRAPS OR A. GENERAL: HEAVY DUTY, HORSEPOWER RAZED, FULLY ENCLOSED, FUSIBLE (WITH REJECTION L ----------------------------------- ---- -------- --------------------J PE WIRES. WHERE MULTIPLE PARALLEL RACEWAYS ARE TO RUN TOGETHER, USE TRAPEZE TYPE FUSE CLIPS) OR NON-FUSED AS INDICATED, QUICK -MAKE, QUICK BREAK SIMTCHING MECHA- SEE SEE DWG. E1 HANGER ARRANGEMENT MADE FROM U -CHANNEL AND ACCESSORIES, SUSPENDED BY THREADED NISM INTERLOCKED WITH COVER, & NEMA -1 ENCLOSURE FOR DRY LOCATIONS, AND NEMA -3R RODS, AND ALLOW AT LEAST 257 SPARE CAPACITY FOR FUTURE INSTALLATION OF ADDITIONAL ANTENNA CABLE ENCLOSURE FOR OUTDOOR LOCATIONS UNLESS INDICATED OTHERWISE. SWITCHES TO BE RACEWAYS. RIGIDLY ANCHOR VERTICAL CONDUITS SERVING FLOOR MOUNTED OR "ISLAND" TYPE SEE DWG. E1 LABELED AS "SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT," WHERE REQUIRED. BCW EQUIPMENT MOUNTED AWAY FROM WALLS WITH METAL BRACKET OR RIGID STEEL CONDUIT EXTEM- A $2 SION SECURED TO FLOOR. , B. RATINGS: VOLTAGE, PHASES, AMPERAGES AND FUSING AS INDICATED. J. MISCELLANEOUS SUPPORTS: PROVIDE ANY ADDITIONAL STRUCTURAL SUPPORT STEEL BRACKETS C. IN THE FUSED CONFIGURATION, SNITCHES SHALL HAVE AN INTERRUPTING CAPACITY OF AT ANGLES, FASTENERS AND HARDWARE AS REQUIRED TO ADEQUATELY SUPPORT ALL ELECTRICAL LEAST 100,000 AMPS SYMMETRICAL AT SIX HUNDRED (600) VOLTS WHEN USED WITH CLASS MATERIALS AND EQUIPMENT. RK -5 TIME DELAY CURRENT LIMITING FUSES. K. ONE HOLE STRAPS SHALL NOT BE USED FOR CONDUITS LARGER THAN 3/4 INCH. D. GUARDS: LINE SHIELD GUARDS TO PREVENT CONTACT WITH LIVE PARTS. , E. CONTACTS: SILVER ALLOY, SNATCH BLADES SHALL BE DE -ENERGIZED IN THE OPEN POSITION. 3. ENCLOSURES F. LUGS: SOLDERLESS TYPE. A. DRY LOCATION, INDOOR - NEMA 1 G. REJECTION FUSE CUPS: PROVIDE FOR FUSIBLE SNATCHES (30-600A) TO PREVENT THE INSTA- LLATION OF CLASS H AND CLASS K NON -CURRENT -LIMITING FUSES. B. WET LOCATION OR OUTDOOR -NEMA 3R H. ACCEPTABLE MANUFACTURERS: GENERAL ELECTRIC, SQUARE D, SIEMENS. 4. HOLES, SLEEVES AND OPENINGS A. GENERAL: PROVIDE ALL HOLES, SLEEVES, AND OPENINGS REQUIRED FOR THE COMPLETION OF WORK AND RESTORE ALL SURFACES DAMAGED, TO MATCH SURROUNDING SURFACES. MAINTAIN INTEGRITY OF ALL FIRE AND SMOKE RATED BARRIERS USING APPROVED FIRESTOPPING SYSTEMS. WHEN CUTTING HOLES OR OPENINGS, OR INSTALLING SLEEVES, DO NOT CUT, DAMAGE OR DIS- GATE FRAME TURB STRUCTURAL ELEMENTS OR REINFORCING STEEL, UNLESS APPROVED, IN WRITING, BY THE PROJECT STRUCTURAL ENGINEER. GATE POST B. CONDUIT PENETRATIONS: SIZE CORE DRILLED HOLES SO THAT AN ANNULAR SPACE OF NOT #4/0 FLEXIBLE LESS THAN 1/4" AND NOT MORE THAN 1" IS LEFT AROUND THE CONDUIT, PIPE ETC. WHEN OPE- NINGS ARE CUT IN LIEU OF CORE DRILLED, PROVIDE SLEEVE IN ROUGH OPENING. SIZE SLEEVES TO PROVIDE AND ANNULAR SPACE OF NOT LESS THAN 1/4" AND NOT MORE THAN 1" AROUND THE CONDUIT, PIPE ETC. PATCH AROUND SLEEVE TO MATCH SURROUNDING SURFACES. Gf X .1 5. CUTTING AND PATCHING A. GENERAL: PROVIDE ALL CUTTING, DRILLING, CHASING, FITTING AND PATCHING NECESSARY FOR . ACCOMPLISHING THE WORK, THIS INCLUDES ANY AND ALL WORK NECESSARY TO: UNCOVER WORK TO PROVIDE FOR THE INSTALLATION OF ILL TIMED WORK: REMOVE AND REPLACE DEFEC- TIVE WORK AND WORK NOT CONFORMING TO THE REQUIREMENTS OF THE CONTRACT DOCUMENTS INSTALL EQUIPMENT AND MATERIALS IN EXISTING STRUCTURES; IN ADDITION TO THAT REQUIRED X DURING THE NORMAL COURSE OF CONSTRUCTION. C( GRADE B. BUILDING STRUCTURE: DO NOT ENDANGER THE INTEGRITY OF THE BUILDING STRUCTURE BY \\ \ \ CUTTING, DRILLING OR OTHERWISE MODIFYING ANY STRUCTURAL MEMBER, WITHOUT SPECIFIC \�/�\� \�>i\\i./�\/' ✓!�\// .�/�\ " �KR APPROVAL. DO NOT PROCEED WITH ANY STRUCTURAL MODIFICATIONS WITHOUT WRITTEN PEP.IAI- $SION OF THE PROJECT STRUCTURAL ENGINEER. r TYPE ) CONNECTOR UND ;TOR C. REPAIRS: REPAIR ANY AND ALL DAMAGE TO WORK OF OTHER TRADES CAUSED BY CUTTING TO GROUND SYSTEM AND PATCHING OPERATIONS, USING SKILLED MECHANICS OF THE TRADES INVOLVED. NOTE: FENCE GROUND CONNECTIONS SHALL BE AT EACH CORNER. GATE JUMPER SHALL BE: 6. RACEWAY SYSTEMS #4/0 FLEXIBLE COPPER BRAD WITH SLEEVES ON EACH DESIGNED FOR EXOTHERMIC WELDING AND INSTALLED SO THAT JUMPER WILL NOT BE SUBJECTED TO DAMAGING A. CONDUIT SEALS: INSTALL CONDUIT SEAL FOR EACH CONDUIT PENETRATING AN EXTERIOR, BUIL- STRAIN WHEN GATE IS FULLY OPENED IN EITHER DIRECTION. DING WALL BELOW GRADE (UNLESS PENETRATION IS BELOW LOWEST BUILDING FLOOR SLAB), AND ELSEWHERE AS INDICATED, AND SO AS TO ACHIEVE A SEALED WATERTIGHT INSTALLATION. B. COORDINATE ALL CONDUIT STUB UP LOCATIONS WITH EQUIPMENT LAYOUT.10 TYPICAL GATE - GROUNDING E1 NO SCALE 7. .ELECTRIC SERVICE A. GENERAL: COMPLY WITH AND COORDINATE ALL REQUIREMENTS OF THE UTILITY COMPANY. C CLOUGH, HARBOUR YARMOUTH, PROSPECT HILL WATER TANK L & ASSOCIATES LLP A DRAWING COPYRIGHT EINIG NEERS, SURVEYORS, PLANNERS YARMOUTH WATER DEPT. © 1999 S. LANOSCAPE ARCHITECTS 171 PARK AVENUE – WEST SPRINGFIELD, MA – 01090 OLD HYROAD/ PROSPECT HILL YARMOUTH, P.O. Box 626 413-746-0796 YARMOUTH, MA. 02664 CHA Project No. 7472-73 6 -1- __._ _ _ S ._ 4 a NOTES AMP 0 1. EXISTING UTILITY POLE CABLE TO GROUND BAR ANTENNA 2. WATER GROUND RING. COAX GND KIT ANTENNA ANTENNA FENCE DETAILS, SEE LAYOUT DRAWINGS. TANK CABLE TRAY. #2 (SOLID TINNED BCW) GROUND NOTE 1 NOTE 1 TO CONCRETE. 1 ANTENNA COAX ANTENNA COAX FOR EQUIPMENT GROUNDING SEE DETAIL 569-5 ON DRAWING E4. 3 i �— SEE DWG. E1 GND KIT GND KIT 33 CABLE CABLE m DO m ; a - /TELCO BACKBOARD NIREWAY G Q I a a v NOTE 1.3 4 4 GND BAR GND BAR p) 2 BCW LADDER w ,z, ; 1 1 w w 3 3 � J I 1 a r , ( I r—SEE DWG. E1 LEASE AREA < a a _ - - -•--.— J J N I NOTE 5 I i SEE DWG. Et --� z z _ 2 BCW r-----'----------------------------� NOTE4 I 2 AWG AING CIGBE INSULATED CIGBE I POWER PROTECTION GREEN Z2 BCW I CABINET w, 2 BCW o MIGB NOTES 2 & 3 I TELCO POWER (PPC -MINI)) I 8Y OTHER BOTTOM 3 I PANEL PANEL NOTE 2 OF TOWER a W I I N U U Lm I Q M m Lm LM I a GROUND z RODS) 6 AWG GND KIT GND BAR CABLE CONDUITS GPS ANTENNA PPC MINI I L ----------------------------------- ---- -------- --------------------J SEE SEE DWG. E1 GATE ANTENNA CABLE SEE DWG. E1 COVER ASSEMBLY C GND BAR BCW A $2 a NOTES AMP 0 1. BOND ANTENNA GROUNDING KIT CABLE TO GROUND BAR ANTENNA 2. 12 (SOLID TINNED) BCW BURIED GROUND RING. COAX GND KIT 3, FOR GROUNDING CONNECTION & DETAILS, SEE LAYOUT DRAWINGS. CABLE 4. #2 (SOLID TINNED BCW) GROUND RING FOR EQUIPMENT, ATTACHED TO CONCRETE. 5. FOR EQUIPMENT GROUNDING SEE DETAIL 569-5 ON DRAWING E4. SCHEMATIC DIAGRAM — GROUNDING SYSTEMS NO SCALE -�- Sprint Spectrum, LP v CROSSROADS CORPORATE CENTER 1 INTERNATIONAL BOULEVARD, SUITE 800 MAHWAH, NEW JERSEY 07495 BOSTON MTA SITE NO.: BS23XC663B2 3 N0. I DATE SCALE AS NOTED ISSUED FOR CONSTRUCTION ISSUED FOR REVIEW REVISIONS )ESIGNED: ' 00 ANTENNA CABLE COVER ASSEMBLY POWER CABINET PRIMARY RADIO CABINET LOAD DATA GRADE LEVEL CONNECTED LOAD 175.9 AMP MAX. 1 0 240/120VAC, 10 3 RUNNING LOAD 145.9 AMP MAX. 1 0 240/120VAC, 10 3W NOTES 1. UTILIZE EXISTING SPARE METER SOCKET. METER BY UTILITY COMPANY. 2. FOR COMPLETE INTERNAL WIRING AND ARRANGEMENT REFER TO VENDOR PRINTS PROVIDED BY PPC MANUFACTURER. 3. ELECTRICAL SERVICE SHALL BE RATED 200A, 2t31120V, 10 3W. 4. PROVIDE 200 AMP, 2 POLE, 250 VOLT CIRCUIT BREAKER. POWER & TELEPHONE DIAGRAM NO SCALE ) ALL METAL OBJECTS TO POLE GROUNDING SYSTEM. RDINATE ALL INSTALLATIONS TO UTILITY POLE WITH UTILITY COMPANY: .ODED NOTES INDUCTORS FROM UTILITY POLE TO METER INSTALLED BY CONTRACTOR, iNTRACTOR TO PROVIDE SUFFICIENT CABLE TO REACH A MINIMUM OF 24" OVE TERMINATION LOCATIONS, AND ROUTE TO SERVICE DISCONNECT WITH - T A SPLICE OVIDE INSULATING BUSHING. USE DUCT SEAL TO MAKE WATERTIGHT. 'E STRAPS, INSTALL AT NOT MORE THAN 2'-0" INTERVALS. EPHONE SERVICE CONDUIT WITH PULL CORD. SEE SITE PLAN FOR CONDUIT 'E & ROUTING. EEPS MUST BE MADE USING RIGID GALVANIZED STEEL CONDUITS. TO EQUIPMENT SEE ELECTRICAL PLAN FOR CONTINUATION (zFR\/Irr' f](11 F – DO IAX'D 4, NO SCALE RIGS Cum LISV DR CMM SUN BY CHK APP'D DRAWN: DR 9 PHONE Sprint Spectrum, LP ELECTRICAL DETAIL AND NOTES JOB NO. DRAWING NUMBER 7472.04.73 RBA663E2 22 X 34 J C B A Ev 1