HomeMy WebLinkAbout140 South Street - Sewage Disposal SystemSOIL TEST PIT DATA: JUNE 22, 2005
TEST PIT --#]-- TEST PIT #2
GRD. EL. 5.76 GRD. EL. 5.57
EST.
FINE SAND
2.5Y 7/2
EL = (-4.24) 1
EST. HIGH GW. 2.5
LOA Y SAND
10YR 4 1 7„ HIGH GROUNDWATER COMPUTATION
B BASED ON BASS RIVER HIGH TIDE)
LOAMYS ND
1OYR 5 8 HIGH TIDE ELEVATION 2.5 NGVD
,4„ EL = 3.57 24"
9" 37"
8" = 42"
FINE SAND
2.5Y 7/2
20" EL = (-4.43) 120"
INDICATES
Z ESTIMATED
SEASONAL HIGH
DATE: DATE: GROUND WATER
6/22/05 6/22/05 INDICATES
TEST BY: TEST BY: _v OBSERVED
TOM McCLELAN TOM McCLELAN _ GROUND WATER
WITNESSED BY: WITNESSED BY: 0M INDICATES
LYNN MULKEEN LYNN MULKEEN PERC.
SEPTIC TANK DETAIL: 1,500 GALLON
NOT TO SCALE
NOTES: 1. SEPTIC TANK SHALL BE STEEL 5. INLET AND OUTLET TEES TO BE CAST IRON,
REINFORCED CONCRETE. 11 SCHED. 40 PVC OR CAST -IN-PLACE CONCRETE.
2. SEPTIC TANK TO WITHSTAND H-10 LOADING TEES TO BE CENTERED UNDER MANHOLE COVER.
UNLESS UNDER PAVEMENT, DRIVES OR
TRAVELED WAYS, WHEREIN H-20 LOADING
SHALL APPLY.
3. ALL PIPE CONNECTIONS AND CONCRETE 2_24. DIA CONCRETE MANHOLES
CONSTRUCTION SHALL BE WATERTIGHT. W/ METAL HANDLES BROUGHT
4. FILL ALL UNUSED KNOCKOUTS WITH T6 6. OF FINISH GRADE
MORTAR. TEE TO BE UNDER 12• MIN.
M.H. OPENING COVER
RAISE
10'-6" SEWER BRICK �. •: .
10'-0" & MORTAR
I I NORMAL WATER LEVEL. 12"
o L 3• %%
0
PRECAST SEPTIC TANK 1(10" 14"
DISTRIBUTION
BOX DETAIL:
NOT TO SCALE
36" MAX .COVER
9.20
B
FINISHED GRADE
8.80
NO. OF OUTLETS 9
FINISHED GRADE
4' P��F S Fi 40 gYC SqS=Q 005'('
�°•° ��° 'b4° 1f'►�4 b$a b�°0���°'��(iP^b�° 1f�4 'b `III
D
EMO'ABLE
c• N:PTH
3" WALLS
NOTES:
OVER I
F
LEVEL BOTTOM
INVERTS AT LEACHING FACILITY:
�Q: a..+.�: a..+.q: V.... ::v.:•"
5"
1. DIST. BOX TO WITHSTAND H-20 LOADING
CLEAN GRANULAR SAND, FREE FROM ORGANIC
1 T PW BARRIER
2. PROVIDE INLET TEE OR BAFFLE WHERE
SLOPE OF PIPE EXCEEDS 0.08 FT./FT OR
8.22
36" MAX. - 12" MIN. COVER
4" INVERT AT END
IN PUMPED SYSTEM.
J_T
4�
8.10
LOAM & SEED DISTURBED AREAS
OF FILL SAMPLE PASSING THE #4 SIEVE, SUCH
f.
8
MATERIAL MEETS EACH OF THE FOLLOWING
3. FIRST TWO FEET OF PIPE OUT OF DIST.
6" •• 9,5" OUTLETS
:.
J
BOX TO BE LAID LEVEL
a oe o ova ova 1
4. RECOMMENDED MANUFACTURER-ROTONDO
4'°
�° °a�° L_ 4"
OR APPROVED EQUAL
BOTTOM ON LEVEL
STABLE BASE
6" MIN. 3//4" TO
5. ALL PIPE CONNECTIONS AND CONCRETE
3/4" TO 1-1/2" DOU BLEZ�/�
1 1, C1IUSHED
CONSTRUCTION SHALL BE WATERTIGHT.
CROSS-SECTION
STONE BASE
6. FIT BREAKOUT BARRIER SNUG AROUND
w INLET TEE I 5'-1
O 5'-2" 4'-6" d 4'-0" MIN. °°nii°EE" J
K LIQUID DEPTH FTL �NTRa) .,•
5'-8' s :e
C4 c
s.
a BOTTOM ON LEVEL STABLE BASE u 3'
PLAN VIEW 6" MIN. 3/4" TO �C��`����`�`�
1 1/2" STONE CROSS-SECTION VIEW
I'-' 30" -
PRECAST DI;
BOX / 18"
DIAMETER
PLAN VIEW
D -BOX AND USE EPDXY RESIN FOR WATER
TIGHT SEAL.
7. FILL ALL UNUSED KNOCKOUTS WITH MORTAR.
FILE COPY
LEACHING FIELD DETAIL: NOT TO SCALE
11.77
A
36" MAX .COVER
9.20
B
FINISHED GRADE
8.80
ENDS \
4" PVC-'
4" INVERT AT SEPTIC TANK (OUT)
4' P��F S Fi 40 gYC SqS=Q 005'('
�°•° ��° 'b4° 1f'►�4 b$a b�°0���°'��(iP^b�° 1f�4 'b `III
D
4" INVERT AT DIST. BOX (IN)
c• N:PTH
E
ae Q o�r e a e�a l+ a a�•1 �o a o a e G�i"�C�a o 1
8.27
F
LEVEL BOTTOM
INVERTS AT LEACHING FACILITY:
ALL TOPSOIL, SUBSOIL AND OTHER
40'
4" INVERT AT BEGINNING
CLEAN GRANULAR SAND, FREE FROM ORGANIC
PROFILE
OF LEACHING FIELD
8.22
36" MAX. - 12" MIN. COVER
4" INVERT AT END
SIEVE, SHALL BE PERFORMED ON A
2" MIN. FINISH GRADE 4" MIN. LOAM & SEED
OF LEACHING FIELD
8.10
LOAM & SEED DISTURBED AREAS
OF FILL SAMPLE PASSING THE #4 SIEVE, SUCH
3.1 MAXIMUM
MATERIAL MEETS EACH OF THE FOLLOWING
SPECIFICATIONS:
OF LEACHING FIELD
7.60
J
(0.30 mm EFFECTIVE PARTICLE SIZE)
a9�°'o�P�
aM� e a (-2" MIN. OF 1/6" TO
(0.15 mm EFFECTIVE PARTICLE SIZE)
6'
f e° e �pa
spy �a� a �b ,'`ee e 1/2" WASHED STONE
1•.i 6 .i`d ° e a off+• o as o • ��
2.50
K
OBSERVED
SIBLE FOR PROPERLY LOCATING AND
3/4" TO 1-1/2" DOU BLEZ�/�
GROUNDWATER
2.07
WASHED STONE (NO FINES)PROP
LINER
DIG -SAFE SHALL BE NOTIFIED PER
THE STATE OF MASSACHUSETTS
(np TOP 9.0
AT TEL. 1-888-344-7233. THE
ENGINEER DOES NOT GUARANTEE
CROSS-SECTION BOT 5.0
UTIUTIES AND SUBSURFACE STRUCTURES
OFA48
ELEVATIONS OF UNDERGROUND UTILITIES
TAKEN FROM RECORD PLANS. THE
CONTRACTOR SHALL VERIFY SIZE,
o� MARK D. �G
AND STRUCTURES AS REQUIRED PRIOR
DESIGN CRITERIA:
8. THIS SYSTEM IS NOT DESIGNED FOR
PERC. RATE: PERC. RATE: TEST �� ����z, a DIBB DESIGN FLOW:
2 MIN./INCH 2 MIN./INCH �A `M 4: CIVIL
INDICATES 7.9 YI ADJACENT �eoae N0 X937 4 BEDROOMS AT 110 G.P.B./D 440 G.P.D.
SOIL EVALUATOR SOIL EVALUATOR ®
TOM McCLELAN TOM McCLELAN MATERIAE E BUILDINGAll
PROPOSED Ell
SOIL CLASS: SOIL CLASS: 40mil POLY LINER
I s � �� � REQUIRED SEPTIC TANK:
1 1 J 7g'1735" TOP 9.0 v h 440 X 200% = 880 GAL.
f` BOTTOM 5.0 PROPOSED ( 2- O G O
L.T.A.R. L. T. A.R. /o// SEPTIC TANK PROVIDED: = 1500 GAL.
0.74 G.P.D./SQ.FT. 0.74 G.P.D./SQ.FT. 1 ' • PROPOSED LIMITS 15'x40
OF EXCAVATION LEACHING PROPOSED
J• SEE NOTES 5 & 6 1 FIELD PROPOSED 1500 GALLON N/F
_ SIZE OF LEACHING FACILITY REQUIRED:
DATUM: I ' 79.25 "D° BOX OTAMAR DANNER
J 1� �� ASSESSORS MAP 34 DESIGN PERC, RATE: <2 MIN./ INCH
VERTICAL DATUM: NGVDPROPERTY L
~ INE BY PLAN 1151 PARCEL 293 LONG TERM APPL. RATE 0.74 G.P.D/S. F.
r ^ I
BENCH MARK USED: TOP OF CONCRETE BOUND ON SOUTH STREET v/ s ��
AT SOU22.9'' 440 GPD + 0,74 GPD/SF 596 S.F.
ThWEST CORNER OF PROPERTY S 85•os'2g" E S -
1 J � �' 78 67' 6g 56'
ELEVATION 5.93 NGVD � - 4
� f
I �' 30' - -- i- -4j SIZE OF LEACHING FACILITY PROVIDED:
PROFILE•
NOT TO SCALE Q
EL.= A FIPST PIPE L _
TOP FOUNDATION CONCRETE COVERS TO WITHIN TO BE SET _. I ' , T -_.f _T_ 5 7 440 GPD _ 0,74 SF/GPD 595 S.F.
EL.= 11.1 6" OF FINISHED GRADE. -7 FOR MIN. 2' 1 /
/ � / 1 • 1 �' � � ' � LEACHING � USE LEA
1 ING FIELD
I
5 OUTLET
DIST. BOX
SEPTIC TANK
INVERT ELEVATIONS:
TOP OF FOUNDATION
11.77
A
4" INVERT AT BUILDING
9.20
B
4" INVERT AT SEPTIC TANK (IN)
8.80
C
4" INVERT AT SEPTIC TANK (OUT)
8.55
D
4" INVERT AT DIST. BOX (IN)
8.44
E
4" INVERT AT DIST. BOX (OUT)
8.27
F
150' OF ANY KNOWN LEACHING FACILITY.
INVERTS AT LEACHING FACILITY:
ALL TOPSOIL, SUBSOIL AND OTHER
IMPERVIOUS MATERIAL.
4" INVERT AT BEGINNING
CLEAN GRANULAR SAND, FREE FROM ORGANIC
MATERIAL AND DELETERIOUS SUBSTANCES.
OF LEACHING FIELD
8.22
G
4" INVERT AT END
SIEVE, SHALL BE PERFORMED ON A
REPRESENTATIVE SAMPLE OF FILL UP TO 45%
OF LEACHING FIELD
8.10
H
OF FILL SAMPLE PASSING THE #4 SIEVE, SUCH
ELEVATION AT BOTTOM
MATERIAL MEETS EACH OF THE FOLLOWING
SPECIFICATIONS:
OF LEACHING FIELD
7.60
J
(0.30 mm EFFECTIVE PARTICLE SIZE)
ADJUSTED HIGH
(0.15 mm EFFECTIVE PARTICLE SIZE)
0%-5% MUST PASS #200 SIEVE
GROUNDWATER
2.50
K
OBSERVED
SIBLE FOR PROPERLY LOCATING AND
COORDINATING THE PROPOSED CON-
GROUNDWATER
2.07
COMPANY AND MAINTAINING THE
VARIANCES REQUESTED:
NONE
FLOOR PLANS:
SEE ATTACHED ARCHITECTURAL PLANS
F4I=S1H GRADE
4' PVC scH ao 0.5-9.a J I ',PROPOSEDDRIVEWAY -
1 I I 1 1 I• 7.0 BOTTOM 15' x 40' = 600 S.F
� 1 1 I •
LEACHI,Nr - I • : '.� I I 1 I .. ' , e I .
11 1 a I 7.3 1�_ 2p, 600 S.F X 0,74 SF/GPD = 444 GPD
� �( I / � •. I I I I 9.0 f �
I I Q I1 1 I 1
5.1' SEPARATION il J If I I I 1 IJ I,
W ; ► rL-= L6 _ L f- 11.0
EST. HIGH GROUNDWATER j-3jJ I '1'
KCd
LOCUS INFORMATION
/
7.a I I I I I 1; '
CURRENT OWNER: KEVIN & ROBERT PALMER
I II w o : ' 1 ; ; ; MIN I �� 3 TITLE REFERENCE: DEED BOOK 21242, PAGE 56
PLAN REFERENCE: NO RECORD PLAN
40_0 to w ABUTTERS (115-1, 7615C)
I J "> L 1 I I'' PROPOSED l' 0 /
I I C) / • • .. •�'�-t !J • 4 BEDROOM DWELLING i� ASSESSORS MAP: 34
I I z 1 1• '' ; : ; FIRST FLOOR 12.8 PARCEL: 294
I /
TOP -OF-f--ND,1.1 $ DISTRICT: RS -40
ZONING
CRAWL SPACE 7.8�
53.0' 29.3' SETBACKS: FRONT 30'
�..�-�
I / SIDE 6' TO BE CONFIRMED
J I PROPOSED - \ s / REAR BY ZONING OFFICER
I �, •' DRIVEWAYo \ 49.0'
o MINIMUM LOT SIZE: 40,000 S.F. G1v�
1 EXISTING LOT AREA: 17,255± S.F.
3REAKOUT 8.8 � t � � \� ,l
TP#2TP#1 / OVERLAY DISTRICT: NONE
0 1 J�� / NITROGEN SENSITIVE Boa
l-�
..• • • PR(POSED 4'� l ZONE: NOT A ZONE II �o
� ev
FEMA FLOOD
PROPpSED
G GAS SERVICE LAB ELEV 11 ZONE DISTRICT: A-11, ELEV 11, 7/2/1992
I PANEL #250015 0006 D
PROPOSED G �� _
WA ER - G �� N /F
SERVICE - - - - G HENRY FAMILY
- - _ 10.0 G f ASSOCIATES LOCUS PLAN: NO SCALE
_ 7,6 ASSESSORS MAP 34
-
/ 18.2' 9.0 l ( PARCEL 292.1 28
PROPERTY LINE BY L.C. PLAN 7216-C 15404'
OHw .
\ 6.0
BENCHMARK OHw N 8 38'40" W
TOP OF CONCRETE \ OHW
BOUND WITH DISK
ELEV 5.93 NGVD -5-''-
OHw U. POLE
N/F
HENRY FAMILY ASSOCIATES oHW EASEMENT
ASSESSORS MAP 34
PARCEL 292.2
PLAN VIEW
SCALE: 1' = 10 FEET
0 5 10 20 FT,
If
OyW
\'OHW \
w
LU
>
OLD MAIN ST, w
L7
M 0 I WILLOW STREET <
o I i N a¢n
:
CONCRETE • to to
BOUND FOUND
OFF 0.7' I I YzrmoutK.l e21th Department
AP •�, 'D L CUS
I
F'L CO ) I
I SO��N S�oR
NANTUCKET SOUND
REVISIONS
NO. DATE DESCRIPTION
/ /o / L oc %LEL. RESERJE
GENERAL NOTES:
1. THIS PLAN IS FOR DESIGN AND
CONSTRUCTION OF THE SEWAGE
DISPOSAL FACILITY ONLY.
2. ALL CONSTRUCTION METHODS AND
MATERIALS SHALL CONFORM TO MASS.
D.E.P TITLE 5 AND LOCAL BOARD
OF HEALTH REGULATIONS.
3. ALL PIPES LOCATED UNDER PAVEMENT
OR TRAVELED WAY SHALL BE SCHEDULE
40 OR EQUAL
4. THERE ARE NO KNOWN PRIVATE WELLS
LOCATED WITHIN 150 FT. OF THE
PROPOSED LEACHING FACIUTY NOR
ANY KNOWN WELLS PROPOSED WITHIN
150' OF ANY KNOWN LEACHING FACILITY.
5. WITHIN LIMIT OF EXCAVATION REMOVE
ALL TOPSOIL, SUBSOIL AND OTHER
IMPERVIOUS MATERIAL.
6. REPLACE ALL EXCAVATED MATERIAL WITH
CLEAN GRANULAR SAND, FREE FROM ORGANIC
MATERIAL AND DELETERIOUS SUBSTANCES.
MIXTURES AND LAYERS OF DIFFERENT CLASSES
OF SOIL SHALL NOT BE USED. THE FILL SHALL
NOT CONTAIN ANY MATERIAL LARGER THAN
TWO INCHES. A SIEVE ANALYSIS, USING A #4
SIEVE, SHALL BE PERFORMED ON A
REPRESENTATIVE SAMPLE OF FILL UP TO 45%
BY WEIGHT OF THE FILL SAMPLE MAY BE
RETAINED ON THE #4 SIEVE. SIEVE ANALYSES
ALSO SHALL BE PERFORMED ON THE FRACTION
OF FILL SAMPLE PASSING THE #4 SIEVE, SUCH
ANALYSES MUST DEMONSTRATE THAT THE
MATERIAL MEETS EACH OF THE FOLLOWING
SPECIFICATIONS:
100% MUST PASS #4 SIEVE
(4.75 mm EFFECTIVE PARTICLE SIZE)
10%-100% MUST PASS #50 SIEVE
(0.30 mm EFFECTIVE PARTICLE SIZE)
0%-20% MUST PASS #100 SIEVE
(0.15 mm EFFECTIVE PARTICLE SIZE)
0%-5% MUST PASS #200 SIEVE
(0.075 mm EFFECTIVE PARTICLE SIZE)
7. EXISTING UTILITIES WHERE SHOWN
IN THE DRAWINGS ARE APPROXIMATE.
THE CONTRACTOR SHALL BE RESPON-
SIBLE FOR PROPERLY LOCATING AND
COORDINATING THE PROPOSED CON-
STRUCTION ACTIVITY WITH DIG -SAFE
AND THE APPUCABLE UTIUTY
COMPANY AND MAINTAINING THE
EXISTING UTILITY SYSTEM IN SERVICE.
DIG -SAFE SHALL BE NOTIFIED PER
THE STATE OF MASSACHUSETTS
STATUTE CHAPTER 82, SECTION 409
AT TEL. 1-888-344-7233. THE
ENGINEER DOES NOT GUARANTEE
THEIR ACCURACY OR THAT ALL
UTIUTIES AND SUBSURFACE STRUCTURES
ARE SHOWN. LOCATIONS AND
ELEVATIONS OF UNDERGROUND UTILITIES
TAKEN FROM RECORD PLANS. THE
CONTRACTOR SHALL VERIFY SIZE,
LOCATION AND INVERTS OF UTIUTIES
AND STRUCTURES AS REQUIRED PRIOR
TO THE START OF CONSTRUCTION.
8. THIS SYSTEM IS NOT DESIGNED FOR
THE USE OF A GARBAGE GRINDER.
A GARBAGE GRINDER IS NOT
RECOMMENDED DUE TO RECOGNIZED
ADVERSE IMPACTS TO THE LEACHING'
FACILITY.
9. PROP. INVERTS ARE TO BE CHECKED BY
THE CONTRACTOR PRIOR TO CONSTRUCTION.
CONFIRM LOCATION & NUMBER OF INVERTS.
0. THE ENGINEER IS TO BE NOTIFIED OF
ANY FIELD CHANGES THAT MAY BE
REQUIRED.
mc GRDUP
349 Main Street, (RT. 28) Unit D
W. Yarmouth Massachusetts
02673
508 778 8919
PROJECT TITLE:
DESIGN FOR
-SEWAGE DISPOSAL
SYSTEM
6 #140
UTH STREET
A.K.A.
#185
RIVER STREET
SOUTH YARMOUTH
MASSACHUSETTS
PREPARED FOR:
MR ROBERT PALMER
7 MARION AVENUE
WOBURN
MA 01801
(781) 953-9966
DATE: SEPTEMBER 20, 2006
COMP. DESIGN: K. HEALY
CHECK: M. DIBB
DRAWN: K. HEALY
FIELD: D. GAZZOLO / J. MCCARTIN
FILE NO. 9164-SEP.DWG
DWG NO. 5762-01
SHEET 1 OF 1
JOB NO. 4-9164.001