Loading...
HomeMy WebLinkAbout210 Station Avenue Solar Array-13319,000 W DC 1100 SUNTECH STP290-24/VD MODULES 100 SOURCE CIRCUITS OF 11 MODULES 9 DC INPUT TERMINATIONS 250 KW ADVANCED ENERGY TX INVERTER NEMA -3R 295-595 VDC MPPT INPUT VOLTAGE RANGE 480 VAC 30 OUTPUT VOLTAGE 304 AAC MAXIMUM PER PHASE OUTPUT CURRENT HOST INTERNET CONNECTION INTEGRAL AC OUTPUT CIRCUIT BREAKER — INTEGRAL OUTPUT, 480 VAC 3(p UTILITY METER RELOCATED 322,190 W DC 1111 SUNTECH STP290-24/VD MODULES 101 SOURCE CIRCUITS OF 11 MODULES EXISTING MSB EXISTING 23kV TO 480V UTILITY TRANSFORMER GRAL FUSES ON TRANSFORMER PRIMARY OVERHEAD LINE EXISTING 23kV 12 CIRCUIT STRING COMBINER BOX WITH INTEGRAL DISC.SWITCH (TYP. OF 9) 200A 600V DC 3P DISC. SWITCH FUSED 150A ( TYP. OF 3) FACILITY GROUNDING SYSTEM INTEGRAL TRANSFORMER INTEGRAL AC OUTPUT CONTACTOR 400A 600V AC 3P DISC. SWITCH 3-400A CURRENT LIMITING FUSES 30A C. B. WITH AUX CONTACT MAX AVG. TEMP: MIN RECORD TEMP: PV ARRAY CONFIGURATION MODULE MFR AND MODEL: MODULE QTY: MODULES PER SOURCE CIRCUIT: TOTAL SOURCE CIRCUITS: PV MODULE OUTPUTw Voc: Voc (Temp Adjusted): ISo Vrop: Imp: PV SOURCE CIRCUIT OUTPUT Vor I sc: Vrop: Imp: 38C -24 C SUNTECH STP290-24/VD 2211 11 201 45. 00 Vdc 56. 25 Vdc 8. 42 Adc 35. 60 Vdc 8. 15 A 495.00 Vdc 8. 42 Adc 391.60 Vdc 8. 15 A WBASED ON MODULE PERFORMANCE AT STANDARD TEST CONDITIONS (STC) TABLE 1: PHOTOVOLTAIC SYSTEM EQUIPMENT LIST �3. 12%Z 480 - 480/277V )4 - e AWG & 1#6 AWG GND - 11/2'C (3) 3000VA 600 KCMIL, 1#3 GND, 1 1/0 INVERTER GND, 4-C GROUNDING (2) 3-600 KCMIL & 1 1/0 GND, 1 1/0 INV. GND, 4'C TRANSFORMERS 30A C. B. WITH AUX CONTACT MAX AVG. TEMP: MIN RECORD TEMP: PV ARRAY CONFIGURATION MODULE MFR AND MODEL: MODULE QTY: MODULES PER SOURCE CIRCUIT: TOTAL SOURCE CIRCUITS: PV MODULE OUTPUTw Voc: Voc (Temp Adjusted): ISo Vrop: Imp: PV SOURCE CIRCUIT OUTPUT Vor I sc: Vrop: Imp: 38C -24 C SUNTECH STP290-24/VD 2211 11 201 45. 00 Vdc 56. 25 Vdc 8. 42 Adc 35. 60 Vdc 8. 15 A 495.00 Vdc 8. 42 Adc 391.60 Vdc 8. 15 A WBASED ON MODULE PERFORMANCE AT STANDARD TEST CONDITIONS (STC) TABLE 1: PHOTOVOLTAIC SYSTEM EQUIPMENT LIST ID DESCRIPTION O1 2#10 - TYPICAL - SEE NOTE #1 O2#1/0 AWG & 1#6 AWG GND - 11/2'C O3- 600 KCMIL, 1#3 GND, 1 1/0 INVERTER GND, 4-C 4O (2) 3-600 KCMIL & 1 1/0 GND, 1 1/0 INV. GND, 4'C 11/27/12 ADJUST FINAL DESIGN TO MAINTAIN 1% VOLTAGE DROP lWig 1. ALL HOMERUN WIRES TO DC COMBINER BOXES ARE #10 AWG USE-2/RHW-2 DUAL RATED WIRES. ROUTED AS REQUIRED ON BACK SIDE OF MODULES AND RACKING SYSTEM 2. ALL CONDUCTORS ARE COPPER 90• -RATED 3. ALL EQUIPMENT TO BE LABELED PER NEC REQUIREMENTS 4, METER DATA IS CONNECTED TO DATA ACQUISITION SYSTEM THROUGH CAT -5 ETHERNET CONNECTION (NOT SHOWN) ie 641,190 Watts DC 500 kW AC Solar Array GENERAL NOTES: - ALL DESIGNS ARE SUBJECT TO FINAL STRUCTURAL ANALYSIS AND CONSTRUCTION LAYOUT - ALL MOUNTINGS, INVERTERS AND RACKING SYSTEMS ARE SUBJECT TO CHANGE TO AN "OR EQUAL" MANUFACTURER IN ORDER TO ACCOMMODATE THE SUGGESTED CONSTRUCTION SCHEDULE 6. GENERAL REVISION 02-27-13 5. CHANGED INVERTERS TO AE 12/18/12 4. GENERAL REVISION 11/27/12 3. GENERAL REVISIONS 10/23/12 2. ADDED WEATHER STATION 10/11/12 1. GENERAL REVISION 03/02/12 REVISIONS: BROADWAY ELECTRICAL CO. INC. 295 FREEPORT STREET BOSTON, MA 02122 617-288-7900 FAX: 617-288-4169 email: bwy@broadelec.com OWNER: PROJECT: DRAWING TITLE: DENNIS-YARMOUTH HIGH SCHOOL ONE -LINE DIAGRAM JOB NO: DATE: DRAWN BY: CHECK BY: SCALE: NO SCALE DRAWING NUMBER: PV -2