Loading...
HomeMy WebLinkAbout43 Vernon Street - Design for Sewage Disposal System Upgrade002A: JULY 17, 2007 SEPTIC TANK DETAIL: 1,500 GALLON NOT TO SCALE NOTES: 1. SEPTIC TANK SHALL BE STEEL 5. INLET AND OUTLET TEES TO - CAST IRON, REINFORCED CONCRETE. TEES T 40 PVC OR CAST -IN-PLACE CONCRETE. TEES TO BE CENTERED UNDER MANHOLE COVER. 2. SEPTIC TANK TO WITHSTAND H-10 LOADING HIGH GROUNDWATER COMPUTATION UNLESS UNDER PAVEMENT, DRIVES OR BASED ON TP#1) TRAVELED WAYS, WHEREIN H-20 LOADING SHALL APPLY. DEPTH TO WATER 8.3 3. ALL PIPE CONNECTIONS AND CONCRETE 2-24" PIA CONCRETE MANHOLES CONSTRUCTION SHALL BE WATERTIGHT. W/ METAL HANDLES BROUGHT Ip INC. INDEX WELL MIW-29 4, FILL ALL UNUSED KNOCKOUTS WITH TO 6" OF FINISH GRADE WATER LEVEL RANGE ZONE A - MORTAR. TEE TO BE UNDER 12" MIN. CURRENT DEPTHQINDEX WELL 7/07 B.2 M.H. OPENING R _ WATER LEVEL ADJUSTMENT 1.7 F� DEPTH TO ADJUSTED HIGH WATER 6.6 .H RAISE M.H W/- Io' -6" SEWER BRICK a- R r 10'-0" &MORTAR NORMA 10" L W. INDICATES �` 3" ESTIMATED PRECAST SEPTIC TANK INDICATES �_- SEASONAL HIGH INLET TEE PERC. GROUND WATER- TEST - O 5'-2• 4 -6" 4'-0" MIN. INDICATES _ LIQUID DEPTH FT. W-8" - ®INDICATES �_- OBSERVED UNSUITABLE GROUND WATER MATERIAL e BOTTOM ON LEVEL STABLE BASE PLAN VIEW 6" MIN. 3V4" TO �c�'�/'� CROSS-SECTION VIEW 1 1/2 STONE L DISTRIBUTION BOX DETAIL: NOT TO SCALE LEACHING DETAIL: NOT TO SCALE NO. OF OUTLETS: 5 - 22'5 FINISHED GRADE EMOVABLE f 2' WALLS NOTES: OVER I �,�'•i.!,a:'i. •.. ,.'q••• 2" 1. DIST. BOX TO WITHSTAND H-10 LOADING UNLESS UNDER PAVEMENT, DRIVES OR 4" PVC 1TRAVELED WAYS WHEREIN H-20 LOADING PIPE •I •V -F15" SYSTEM UPGRADE 01 �;00 3 UNITS • •:. HIGH DENSITY PORT POLYETHYLENE INFILTRATOR 3050 00 OT 04 6" •. 001 00 I 2. PROVIDE INLET TEE OR BAFFLE WHERE FT./FT OR 0 00 MATERIAL FOR5. MATERIALS SHALL CONFORM TO MASS. BOARD REVISIONS NO. DATE DESCRIPTION Tl 50" 11' GENERAL NOTES: 1 Il 1. THIS PLAN IS FOR DESIGN AND CONSTRUCTION OF THE SEWAGE DISPOSAL FACILITY ONLY. 1� 30" -F15" SYSTEM UPGRADE SHALL APPLY. - 28.0' WEST YARMOUTH 2. ALL CONSTRUCTION METHODS AND 6" •. 5,5" OUTLETS i 8" I 2. PROVIDE INLET TEE OR BAFFLE WHERE FT./FT OR VIEW - LEACHING CHAMBERS MATERIAL FOR5. MATERIALS SHALL CONFORM TO MASS. BOARD WITHIN LIMIT OF EXCAVATION REMOVE DATE' AUGUST 22, 2007 19 1 SLOPE OF PIPE EXCEEDS 0.08 PLAN O O D.E.P TITLE 5 AND LOCAL SHEET 1 OF 1 ;� •'•e DElH IN PUMPED SYSTEM. BY WEIGHT OF THE FILL SAMPLE MAY BE OF HEALTH REGULATIONS. •• a�f• "e� •e• 11111 g'°'�• 1- 2" 3. FIRST TWO FEET OF PIPE OUT OF DIST. LO.*;. & SEED DISTURBED AREAS jCHAMBER 3. ALL PIPES LOCATED UNDER PAVEMENT p� A, 1111 'Ill 6. REPLACE ALL EXCAVATED MATERIAL WITH OR TRAVELED WAY SHALL BE SCHEDULE BOTTOM ON LEVEL 6" MIN. 3/4w TO BOX TO BE LAID LEVEL. CLEAN GRANULAR SAND, FREE FROM ORGANIC 40 OR EQUAL. -1/ STABLE BASE 41" 1 1/2" CRUSHED 4• ALL PIPE CONNECTIONS AND CONCRETE 3' MAX. COMPACTED FILL_ 36" MAXIMUM 12"MINIMUM 4. THERE ARE NO KNOWN PRIVATE WELLS 50" CROSS-SECTION STONE BASE CONSTRUCTION SHALL BE WATERTIGHT. MIXTURES AND LAYERS OF DIFFERENT CLASSES uoo 0 o°o°oot�` °0 0000000 3" LAYER LOCATED WITHIN 150 FT. OF THE PROPOSED LEACHING FACILITY NOR - 11' 5 FILL ALL UNUSED KNOCKOUTS WITH MORTAR. OF SOIL SHALL NOT BE USED. THE FILL SHALL PEASTONE KNOWN WELLS PROPOSED WITHIN N/F TOWN OF YARMOUTH IDATION ELEV. =19.0 \ 15 ASSESSORS MAP 28 Z^ PARCEL 137 SSE SOBS137 28 PROPOSED LIMITS OF \ \�- �} GIF PROPOSED 11.0' x 28A' EXCAVATION. SEE NOTES 5, \ LEACHING SYSTEM FIRST PIPE LENGTH 5 AND 6.�.- TO WITHIN TO BE SET LEVEL FOR MIN. 2' \ y GRADE. FINISH GRADE �``-� � �� _ '`'-• \ EL.=15.3-16.8 \ I - ECK 30" SEWAGE DISPOSAL SYSTEM UPGRADE O O Qp 0 O REMOVE UNSUITABLEEFFEC. WEST YARMOUTH 150' OF ANY KNOWN LEACHING FACILITY. 1/Z" /2 24"POLYETHYLENE -ILTRATOR 3050 O p O MATERIAL FOR5. SIEVE, SHALL BE PERFORMED ON A WITHIN LIMIT OF EXCAVATION REMOVE DATE' AUGUST 22, 2007 19 CHECK: M. D188 LEACHING O O O 5' ALL AROUND SHEET 1 OF 1 ALL TOPSOIL, SUBSOIL AND OTHER DElH BY WEIGHT OF THE FILL SAMPLE MAY BE IF APPLICABLE IMPERV OUS MATERIAL. jCHAMBER 4`o8coDENSITY p� A, 1111 'Ill 6. REPLACE ALL EXCAVATED MATERIAL WITH ALSO SHALL BE PERFORMED ON THE FRACTION CLEAN GRANULAR SAND, FREE FROM ORGANIC OF #THATITHE SUCH 41" 3/4" -1 1/2"MATERIAL AND DELETERIOUS SUBSTANCES. CRITERIA: YSSAMPLE MUST DEMONSTRATE 50" WASHED STONE MIXTURES AND LAYERS OF DIFFERENT CLASSES DESIGN MATERIAL MEETS EACH OF THE FOLLOWING - 11' KITCHEN OF SOIL SHALL NOT BE USED. THE FILL SHALL BEDROOMSPECIFICATIONS: [CESIGN FLOW- 100% MUST PASS #4 SIEVE LEGEND NOT CONTAIN ANY MATERIAL LARGER THAN I - ECK DESIGN FOR SEWAGE DISPOSAL SYSTEM UPGRADE #43 -- 21' WEST YARMOUTH TWO INCHES. A SIEVE ANALYSIS, USING A #4 1/Z" /2 I moi. PREPgRED-FOR: CROSS --SECTION OF CHAMBER 74 BOSTON POST ROAD SIEVE, SHALL BE PERFORMED ON A (603) 860 4273 DATE' AUGUST 22, 2007 COMP. DESIGN: K. HEALY CHECK: M. D188 DRAWN: P. HAGIST FIELD: D. GAZZOLO / J. McCARTIN REPRESENTATIVE SAMPLE OF FILL. UP TO 45% RAN VIEW SHEET 1 OF 1 JOB NO. 4-9252.00 BY WEIGHT OF THE FILL SAMPLE MAY BE RETAINED ON THE #4 SIEVE. SIEVE ANALYSES A, 1111 'Ill ALSO SHALL BE PERFORMED ON THE FRACTION OF #THATITHE SUCH CRITERIA: YSSAMPLE MUST DEMONSTRATE DESIGN MATERIAL MEETS EACH OF THE FOLLOWING KITCHEN BATH BEDROOMSPECIFICATIONS: [CESIGN FLOW- 100% MUST PASS #4 SIEVE LEGEND L 3 BEDROOMS AT110G.P.B./D 330 G.P.D. (4.75 mm EFFECTIVE PARTICLE SIZE) 1a-1o0a MUST PASS #50 SIEVE _ _ _ (0.30 mm EFFECTIVE PARTICLE SIZE) 07-20% MUST PASS #100 SIEVE SMH WG SEWER MANHOLE WATER GATE (0.15 mm EFFECTIVE PARTICLE SIZE) TOF FF TOP OF FOUNDATION FINISHED FIRST FLOOR � REQUIRED SEPTIC TANK: � 09-57 MUST PASS #200 SIEVE (0.075 mm EFFECTIVE PARTICLE SIZE) INV WF SEPTIC PIPE INVERT WETFLAG NUMBER LIVING ROOM 1 BEDROOM - 33O X 2OO'/. - 660 GAL. 7. EXISTING UTILITIES WHERE SHOWN N/F NOW OR FORMERLY SEPTIC TANK PROVIDED: = 1500 GAL. IN THE DRAWINGS ARE APPROXIMATE. THE CONTRACTOR SHALL BE RESPON- TP TEST PIT I SIBLE FOR PROPERLY LOCATING AND COORDINATING THE PROPOSED CON - NOTE, SIZE OF LEACHING FACILITY REQUIRED: STRUCTION ACTIVITY WITH DIG -SAFE TO BE AND THE APPLICABLE UTILITY 4" PVC SCH 40� 24' OAK EXISTING DWELLING AND D PROPOSED 7 HIGH 40MIL �___ _ `` REMOVED, NEW DWELLING TO BE SET INTERIOR SKETCH DESIGN PERC. RATE: <2 MIN./ INCH COMPANY AND MAINTAINING THE j PROPOSED 'D' BOX ON NEW FOUNDATION TOE COMPASS THE NOT TO SCALE EXISTING UTILITY SYSTEM IN SERVICE. LEACHING CHAMBER POLY LINER. ^T:S `\ OLD DWELLING. ADDITION rA WILL BE LONG TERM APPL. RATE 0,74 G.P.D S.F. DIG -SAFE SHALL BE NOTIFIED PER 7�UT� \ SET ON SONO TUBES AND Y,AD TOWAgpS /S31'58'00"W 1\ �THE REAR OF THE PROPERTY, ADDITION CBI:� THE STATE OF MASSACHUSETTS I -G �-55.25' 1' 24' OA\r WILL EXTEND TOWARD THE SOUTHERLY 33O G T - F9 PROPERTY LINE AND WILL FALL ENTIRELY FLOOR PLANS PD ' 0 74 GPD/SF 446 S F ATATEL 1TUTE -888-344APTER 27233. TTHE40iH o ................. . `,.. - H HE X N CK REAN:WIT INT E ISTI G DE A FNGINEFR DOES NOT CIIARANTF I -F _ _ �' A C AL NS THEIR ACCURACY OR THATALL .... t lHE EXISTING GRADING IS T'O BE MAINTAINED DIST. BOX 5.3' SEPARATION PROVIDED I - - I- - _- AT THE FRONT AND THE WALL ON THE SOUTH SEE RCHI TUR PLA SIZE OF LEACHING FACILITY PROVIDED: UTILMES AND SUBSURFACE L (5' SEPARATION REQ.) "- __ 1 to' f I `11.2 "\ ? SIDE OF THE DRIVEWAY WILL EITHER BE ARE SHOWN. LOCATIONS AND ( I PROPOSE) 1500 GALLON STRUCTURALLY ENHANCED OR REPLACED ( EST. HIGH GROUNDWATER EXISTING II.... SEPTIC ANK IF NEE➢ED. USE HIGH DENSITY POLYETHYLENE ELEVATIONS OF UNDERGROUND UTILITIES J HOUSE #39 ' p I TAKEN FROM RECORD PLANS. THE 1 l LEACHING CHAMBERS(3 UNITS) 11'X2'X28' CONTRACTOR SHALL VERIFY SIZE, LOCATION AND INVERTS OF UTILITIES FULL FND, \ ;- `�- I I - AND STRUCTURES AS REQUIRED PRIOR #1 ; N/F NIDEWALL - 2(111428') X 2 = 156 . . .. - j HOSPITAL TOM = 11 X -CH o TO THE START OF CONSTRUCTION. _. ... . �; _ ASSESSORS MAP 28 ��'• - ... SE` -BA �t UNE - PARCEL 58.1 Fitt NE FOR { � g� T 308 I 464S F 8. THIS SYSTEM IS NOT DESIG D '�- 1 A I • % H �t'i THE USE OF A GARBAGE GRINDER. o0 21-0' ��� 4(34 S,F x.0,74 GPD/SF = 343GPD A GARBAGE GRINDER IS NOT 19.0 A 3N o 1 o O i o' 1 • / o MARK D. �� �L I RECOMMENDED DUE TO RECOGNIZED 14.50 B ❑aln 'o GAS A I I I oxo 12.3' METER IN) 14.00 C �°�ANN In _j N/F JUT) 13.75 D Z�N0 WILLIAM !/ I o m do X05 Q0< � & SUSAN 1 I � , ; E 13.67 E >ya o o TOWNER PROPOSED I / z I (it as �yAG PW o o ASSESSORS MAL"t ADADITIBNS z w I /1 m m$ ?' �) 13.50 F � O0 PARCEL 146 Z 1 z • p o` 00� z 4,420±S.F, 15 STORY (j�+ h, n WF#5 1 6.0' WOOD FRAME m 1 `I 'tI _ FY: 6'S HOUSE #43 11i w J j o ° \ TOF=19,0 'n 1 / • a / ✓ B FF=20,2 z vii 0 EX. INV=17.0 I PROP. INV=15.0 9 ! a I z 24. OAK 13.1' 6.0' GARAGE r 0- ' 13.30 G BREAKOUT 13.8 m W t 1 SLAB CL • a T� CH I- 28.3'- �I EL=11.5 a .. 11.30 H REM D� r 79 30' OAK • 1 r g 6.0 J r� / �I F, `s STDDP J I I 0 i LOCUS INFORMATION CURRENT OWNER: WILLIAM N. TOWNER TITLE REFERENCE: BOOK 11662, PAGE 164 PLAN REFERENCE: BOOK 26, PAGE 105 ASSESSORS MAP: 28 PARCEL: 146 �� 4.3 i i s5 f,<gjaz(a2 y % 1 I 0" ;' aI ZONING DISTRICT: R-25 5 G - - - - --- SETBACKS: FRONT 30' _- F- 0OFF � SIDE 15' REAR 20 _ PROPOSED N RESERVE AREA�, I l j jf f ,-� 15 I i /2 • / f ,w WF#4 .D" ------ -r= -- DRIVEWAY _OW LEACHING SYSTEM TO BE 5' OFF REAR N31.58*00"E - - • -I= - 77 11'� RTY LINE IN LIEU OF 10'._ '16' MAPLE 55.25 _ -7i CB -OW THE LEACHING SYSTEM TO BE 10' OFF "` -�- - w W EDGE OF PAVEMENT JG & PROPOSED FOUNDATION WALL. _OW THE SEPTIC TANK TO BE 5.0' OFF ll \4 WF#3 DE)PROPERTY LINE. VER�`0N STREST(PUBLIC 40' W _OW THE RESERVE AREA TO BE 11' OFF 'f ISED FOUNDATION WALL IN LIEU OF 20'. I tCB i '_OW THE RESERVE AREA TO BE 5' FROM � i' •_ _ , AND SIDE PROPERTY LINES IN LIEU OF 10' - - - - - - - - - f- - / ° �I WF#2 LOW THE WATER LINE TO REMAIN WHERE JNTIL SUCH TIME AS THE RESERVE IS NEEDED = " , CB/DISK <. w .OW THE LEACHING SYSTEM TO BE 86' FROM NDS IN LIEU OF 100' _J LOW THE RESERVE AREA TO BE 77' FROM NDS IN LIEU OF 100' IC SEWER SERVICE THIS PROPERTY WOULD wF#1 IATELY "TIE IN" AND ABANDON PRIVATE SEPTIC ` 901 (4P% Permit valid for REPAIR OF SEPTIC SYSTEM ONLY, due to State and Local septic variances. 6aard of Health review and approval is required for anY future additions/renovations/alterations to sews^e favi"ties and/or structures/dweDl ng. Yarmouth Health Department APPROVED 5_,* -,44 r�&Ikv 7 67 N me Date PLAN VIEW SCALE: 1' = 10 FEET jiln 1111 0 5 10 20 FT, OVERLAY DISTRICT: NOT IN A ZONE II FEMA FLOOD C & A9, DATED 7/2/92 ZONE DISTRICT: PANEL #250015 0005 D MINIMUM LOT SIZE: 25,000 S.F. EXISTING LOT SIZE: 4,420±S.F. f 'iSTING LOT COVERAGE: 918/4,420=20.87 LOCUS PLAN: NO SCALE LEWIS BAY ADVERSE IMPACTS TO THE LEACHING FACILITY. 9. EXITING INVERTS ARE TO BE CHECKED 13Y THE CONTRACTOR PRIOR TO CONSTRUCTION. CONFIRM LOCATION & NUMBER OF INVERTS. 10. THE ENGINEER IS TO BE NOTIFIED OF ANY FIELD CHANGES THAT MAY BE REQUIRED. 349 Main Street, (RT. 28) Unit D W. Yarmouth Massachusetts 02673 508 778 8919 PROJECT TITLE: DESIGN FOR SEWAGE DISPOSAL SYSTEM UPGRADE #43 VERNON STREET WEST YARMOUTH MASSACHUSETTS �• t I moi. PREPgRED-FOR: WILLIAM N. TOWNER 74 BOSTON POST ROAD AMHERST, NH 03031 (603) 860 4273 DATE' AUGUST 22, 2007 COMP. DESIGN: K. HEALY CHECK: M. D188 DRAWN: P. HAGIST FIELD: D. GAZZOLO / J. McCARTIN FILE NO. 9252-EXC.DWG DWG NO. 5822-02 SHEET 1 OF 1 JOB NO. 4-9252.00 r