HomeMy WebLinkAbout10 Whale Road - Site PlanSYSTEM DESIGN: GARBAGE DISPOSER IS NOT ALLOWED DESIGN FLOW: 5 BEDROOMS ® 110 GPD = 550 GPD USE A 550 GPD DESIGN FLOW SEPTIC TANK: 550 GPD (2) = 1100 USE AN H-10 2500 ST/PC COMBINATION (SEE DETAIL) LEACHING: BOTTOM AREA ONLY: 748 SF X (.74) = 553.5 GPD USE A 748 SF LEACHING FIELD AS SHOWN APPROVED NOTES DATE ... FILE Copy ALL SYSTEM COMPONENTS SHALL BE MARKED *THE INSTALLER SHALL VERIFY THE SEPTIC SYSTEM PROFILE FOR FUTURE LOCATION.. WITH MAGNETIC TAPE COMPARABLE MEANS MARK CORNERS OF LOCATIONS OF ALL UTILITIES AND ALL LEACH FIELD WITH 24" #5 REBAR WITH SAFETY BUILDING SEWER OUTLETS AND (NTS) CAP DRIVEN JUST BELOW GRADE EACH CORNER ELEVATIONS PRIOR TO INSTALLING ANY of LEACH FIELD. PORTION OF SEPTIC SYSTEM PROVIDE MIN. 20" DIAM. WATERTIGHT 4" DIA PERF. INSP. PORT TO SAND AT BOTTOM OF FIRST FLOOR BLDG EL120' CONCRETE ACCESS COVERS TO WITHIN 6" OF FIN. GRADE LEACHING FIELD. 4" THREADED CAP TO WITHIN 3" OF FINISH GRADE 40 MIL LINER FROM ELEV. 8.8' TO ELEV. 4.8' MIN. EV. RETAINING WALL SCHEMATIC SHOWN, EXACT FASCADE CRAWLSPACE SLAB 8.6' TOP FOUNDATION 11.0' AND CONSTRUCTION BY OTHERS. TOP OF WALL HT. AS NOTED (WITHIN 20' OF SAS) 9.3' MIN.TOP PIPE 8.6' REMAINDER OF CRAWLSPACE .75' OF COVER OVER PRECAST 10.0 FINISHED GRADE- 4" LOAM & SEED 2% MIN. SLOPE OVER SYSTEM SLAB AT EL. 7.4' 1PRECAST H-1 PROP TEE y / i FLOOD VENTS WITHIN 12" GRADE a"scHao (GROUND AT EL. 7.4) REQ. VENTS ON 2 SIDES REQ. ",.1 7,2' FLOOD VENT/FOUNDATION DESIGN BY OTHERS. ?] z1 7.5'* RISERS��1•� 2'f •) 4"4SCH40 PVC 8,75' CLEAN FILL > TOP RET. WALL ELEV. 8.8' °. PIPES LEVEL IST 2' :-: - - � � � � � CAP ENDS 4- PERFORATED PVC S=0.005 0 a.. 0 3/4'-1-1/2" DOUBLE WASHED STONE LEACHING FIELD 0 °e °e°oe°opeeveea°oo°e °ea , 0 6'•DEPTH T MIN BELOW INV io ° PROPOSED ROCK WALL VENEER „o„o„o_o_o„e o. 8.25 LEVEL BOTTOM 0 B.OD' 8.52' 8.35 f ° 55' 5' MIN UNSUITABLE COVER TYP. ' ° O O O O O O O O O O BLOCK UP FOR 24 O O O O O O D -BOX ACME DB -9 OR EQ. SOIL REMOVAL O O 0 O O O O O O O O O C WHERE SPECIFIED PSOILL������������ DEPTH PER OGS 6" CRUSHED STONE OR MECHANICAL 5.0 y .000 WATER TEST D'BOK FOR LEVELNESS o°o°o°O°°o°°off 00 COMPACTION. (15.221 (21) USE TIDALLY INFLUENCED ADJ GROUNDWATER ELEV 2 5' ' MA - - --. _ _ _- - -_-.-- _ -- -- LEACHING: =USE A 748 SF LEACHING FIELD 748 -SF X .74 - 553 GPD O.K. - LOCUS MAP BOARD OF HEALTH ( �+ S SLOPE) SCALE 1"=2000't FOUNDATION - ST PC LEACHING *ACCESS FOR ROUTINE MAINTENANCE ASSESSORS MAP 14 PARCEL 128 10 / 40 D BOX MUST BE PROVIDED FOR ZABEL FILTER. PROVIDE (3) MIN. 20" DAM. WATERTIGHT FACILITY INSTALLER MUST FOLLOW ALLCONCRET AA � i CCESS COVERS TO WRHIN 6" OF FIN. GRADE .- MANUFACTURER'S SPECIFICATIONS FOR LOCUS IS WITHIN FEMA FLOOD ZONE Al2 PROPER FILTER INSTALLATION NOTE: 5503 GAL RESERVE PROVIDED IN PC (EL 10) ,SND B AS SHOWN ON COMMUNITY BUOYANCY CALCS: 2500 H-10 TANK WGT: 22560 LBS RUN 2' U # NE UP INTO RISER AS SHOWN PANEL 250015 0005D DATED 7/2/1992 FOR EASE OF FUTURE PUMP REMOVAL DATUM: NGVD 2. MUNICIPAL WATER IS EXISTING 3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT. 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS TO BE AASHO H-jQ 5. PIPE JOINTS TO BE MADE WATERTIGHT. 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH 310 CMR 15.000 (TITLE 5.) 7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO BE USED FOR LOT LINE STAKING OR ANY OTHER PURPOSE. 8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC. 9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED WITHOUT INSPECTION BY BOARD OF HEALTH AND PERMISSION OBTAINED FROM BOARD OF HEALTH. 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING DIGSAFE (1-888-344-7233) AND VERIFYING THE LOCATIONOF ALL UNDERGROUND & OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK. 11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE REMOVED 5' BENEATH AND AROUND THE PROPOSED 'TEACHING FACILITY. 12. EXISTING SEPTIC SYSTEM .SHALL BE PUMPED AND REMOVED. 13. ALL RUN-OFF TO BE CONTAINED ON-SITE DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS. 14. DRYWELLS (OR DRIP TRENCHES) SHALL BE INSTALLED TO CONTAIN ROOF RUN-OFF. 15. CONTRACTOR TO COORDINATE ALL UTILITY DISCONNECTS AND NEW SERVICES WITH APPROPRIATE VENDORS. 16. SHOULD PRIMARY LEACHING FACILITY FAIL, IT SHALL BE REMOVED IN ITS ENTIRETY, ALL CONTAMINATED SOILS REMOVED AND SYSTEM TO BE REPLACED IN KIND. TEST HOLE LOGS ENGINEER: ARNE H. OJALA PE, PLS SE1804 WITNESS: PHIL RENAUD DATE: 2/10/2010 PERC. RATE _ < 2 MIN/INCH CLASS I SOILS ELEV. ELEV. p" 6.8'7.3' 0, - FILL 282_' 4.5' A LS 32" 10YR 2/1 4.1' E FS 36" 1 OYR 6/1 3 8, FILL 36" 4.3' A LS 38" 1OYR 2/1 4.1' E FS 40" 1OYR 6/1 4.0' B LS B LS 50" 1OYR 5/6 2.6' 66" 1OYR 5/6 C1 C1 PERC MCS MCS BOTT. AT 1 OYR 6/6 1 OYR 6/6 60' 60"M V EL. 1.8' 114" DCE #10-006 -2.2' 0.6' x 11.8' X 6.3 x 62.4 = 2753 ALARM AND CONTROL PANEL TO BE INSTALLED INSIDE UP (OK) BUILDING. ALARM TO BE ON INV. IN 7.2' SEPARATE CIRCUIT FROM PUMP 2" PRESSURE LINE ZA FILTER (A1oo) 24' TEE SLOPE TO DRAIN BACK FLOAT SNITCH ALARM ON (nl OUTLET TEE W/E%TENSION WEEP HOLES SETTINGS: PUMP ON_ 1300 GAL CHECK VALVE 5' WORKING RANGE 6 OF avnjIS E QUICK DISCONNECT 5• MYERS SRM 4 e'eSUBMERSIBLE 4/10 HP PUMP PUMP OFF 12 SYSTEM (OR EQUAL) - 4 DOSES PER DAY, AT 110 GAL. PER 000000 0000 00 0000 (ON BLOCK) DOSE (5" WORKING RANGE) \ e• 9APFIE s �\ 2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION (NOT TO SCALE) 0 EL. 1.8' -7- FLOOI� / (TYP.) i USE C. BASIN \ \\ 5' REMOVAL OF UNSUITABLE SOIL REAL AROUND PERIMETER OF LEACHING FACII DOWN TO SUITABLE SOIL LAYER. REPLA VI ATH CLEAN MED. SAND, TO MEET SPECIFICATIONS OF 310 CMR 15.255(3) PROP. RETAINING WALL T.O.W. - EL 8.8' (SEE DETAIL, DESIGN BY OTHERS) .0 0 N' / �O• SAS DETAIL `T' 1" - 20' 7 I O o D-6'Q O \\ D-2 l g / D-5 D-3NpWPRp/4 pUNE- 8 ' D-4 ZONEj a �i;APJIEL cyc� F/ LIcLr.-`otic / EL 12) A. OJA A TT, / Al2 ( 4I OJALA v CIVIL / "'o. 40980 < `b t„502 .c o m Fc o STEL Gia / DATE DANIEL A. OJALA, P.L.S.,7C• ZONING SUMMARY ZONING DISTRICT: R25 RESIDENTIAL TEE 2500 GAL H-10 MIN. LOT SIZE 25,000 S.F. 15,600 S.F. MIN. LOT FRONTAGE SEPTIC TANK/PC 130' MIN. FRONT SETBACK COMBINATION 31.3' MIN. SIDE SETBACK SHOREY OR EQUAL 15.9'f MIN. REAR SETBACK (SEE DETAIL) 29.7' ✓ MAX. LOT COVERAGE RISERS��1•� 2'f •) 4"4SCH40 PVC 8,75' CLEAN FILL > TOP RET. WALL ELEV. 8.8' °. PIPES LEVEL IST 2' :-: - - � � � � � CAP ENDS 4- PERFORATED PVC S=0.005 0 a.. 0 3/4'-1-1/2" DOUBLE WASHED STONE LEACHING FIELD 0 °e °e°oe°opeeveea°oo°e °ea , 0 6'•DEPTH T MIN BELOW INV io ° PROPOSED ROCK WALL VENEER „o„o„o_o_o„e o. 8.25 LEVEL BOTTOM 0 B.OD' 8.52' 8.35 f ° 55' 5' MIN UNSUITABLE COVER TYP. ' ° O O O O O O O O O O BLOCK UP FOR 24 O O O O O O D -BOX ACME DB -9 OR EQ. SOIL REMOVAL O O 0 O O O O O O O O O C WHERE SPECIFIED PSOILL������������ DEPTH PER OGS 6" CRUSHED STONE OR MECHANICAL 5.0 y .000 WATER TEST D'BOK FOR LEVELNESS o°o°o°O°°o°°off 00 COMPACTION. (15.221 (21) USE TIDALLY INFLUENCED ADJ GROUNDWATER ELEV 2 5' ' MA - - --. _ _ _- - -_-.-- _ -- -- LEACHING: =USE A 748 SF LEACHING FIELD 748 -SF X .74 - 553 GPD O.K. - LOCUS MAP BOARD OF HEALTH ( �+ S SLOPE) SCALE 1"=2000't FOUNDATION - ST PC LEACHING *ACCESS FOR ROUTINE MAINTENANCE ASSESSORS MAP 14 PARCEL 128 10 / 40 D BOX MUST BE PROVIDED FOR ZABEL FILTER. PROVIDE (3) MIN. 20" DAM. WATERTIGHT FACILITY INSTALLER MUST FOLLOW ALLCONCRET AA � i CCESS COVERS TO WRHIN 6" OF FIN. GRADE .- MANUFACTURER'S SPECIFICATIONS FOR LOCUS IS WITHIN FEMA FLOOD ZONE Al2 PROPER FILTER INSTALLATION NOTE: 5503 GAL RESERVE PROVIDED IN PC (EL 10) ,SND B AS SHOWN ON COMMUNITY BUOYANCY CALCS: 2500 H-10 TANK WGT: 22560 LBS RUN 2' U # NE UP INTO RISER AS SHOWN PANEL 250015 0005D DATED 7/2/1992 FOR EASE OF FUTURE PUMP REMOVAL DATUM: NGVD 2. MUNICIPAL WATER IS EXISTING 3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT. 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS TO BE AASHO H-jQ 5. PIPE JOINTS TO BE MADE WATERTIGHT. 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH 310 CMR 15.000 (TITLE 5.) 7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO BE USED FOR LOT LINE STAKING OR ANY OTHER PURPOSE. 8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC. 9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED WITHOUT INSPECTION BY BOARD OF HEALTH AND PERMISSION OBTAINED FROM BOARD OF HEALTH. 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING DIGSAFE (1-888-344-7233) AND VERIFYING THE LOCATIONOF ALL UNDERGROUND & OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK. 11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE REMOVED 5' BENEATH AND AROUND THE PROPOSED 'TEACHING FACILITY. 12. EXISTING SEPTIC SYSTEM .SHALL BE PUMPED AND REMOVED. 13. ALL RUN-OFF TO BE CONTAINED ON-SITE DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS. 14. DRYWELLS (OR DRIP TRENCHES) SHALL BE INSTALLED TO CONTAIN ROOF RUN-OFF. 15. CONTRACTOR TO COORDINATE ALL UTILITY DISCONNECTS AND NEW SERVICES WITH APPROPRIATE VENDORS. 16. SHOULD PRIMARY LEACHING FACILITY FAIL, IT SHALL BE REMOVED IN ITS ENTIRETY, ALL CONTAMINATED SOILS REMOVED AND SYSTEM TO BE REPLACED IN KIND. TEST HOLE LOGS ENGINEER: ARNE H. OJALA PE, PLS SE1804 WITNESS: PHIL RENAUD DATE: 2/10/2010 PERC. RATE _ < 2 MIN/INCH CLASS I SOILS ELEV. ELEV. p" 6.8'7.3' 0, - FILL 282_' 4.5' A LS 32" 10YR 2/1 4.1' E FS 36" 1 OYR 6/1 3 8, FILL 36" 4.3' A LS 38" 1OYR 2/1 4.1' E FS 40" 1OYR 6/1 4.0' B LS B LS 50" 1OYR 5/6 2.6' 66" 1OYR 5/6 C1 C1 PERC MCS MCS BOTT. AT 1 OYR 6/6 1 OYR 6/6 60' 60"M V EL. 1.8' 114" DCE #10-006 -2.2' 0.6' x 11.8' X 6.3 x 62.4 = 2753 ALARM AND CONTROL PANEL TO BE INSTALLED INSIDE UP (OK) BUILDING. ALARM TO BE ON INV. IN 7.2' SEPARATE CIRCUIT FROM PUMP 2" PRESSURE LINE ZA FILTER (A1oo) 24' TEE SLOPE TO DRAIN BACK FLOAT SNITCH ALARM ON (nl OUTLET TEE W/E%TENSION WEEP HOLES SETTINGS: PUMP ON_ 1300 GAL CHECK VALVE 5' WORKING RANGE 6 OF avnjIS E QUICK DISCONNECT 5• MYERS SRM 4 e'eSUBMERSIBLE 4/10 HP PUMP PUMP OFF 12 SYSTEM (OR EQUAL) - 4 DOSES PER DAY, AT 110 GAL. PER 000000 0000 00 0000 (ON BLOCK) DOSE (5" WORKING RANGE) \ e• 9APFIE s �\ 2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION (NOT TO SCALE) 0 EL. 1.8' -7- FLOOI� / (TYP.) i USE C. BASIN \ \\ 5' REMOVAL OF UNSUITABLE SOIL REAL AROUND PERIMETER OF LEACHING FACII DOWN TO SUITABLE SOIL LAYER. REPLA VI ATH CLEAN MED. SAND, TO MEET SPECIFICATIONS OF 310 CMR 15.255(3) PROP. RETAINING WALL T.O.W. - EL 8.8' (SEE DETAIL, DESIGN BY OTHERS) .0 0 N' / �O• SAS DETAIL `T' 1" - 20' 7 I O o D-6'Q O \\ D-2 l g / D-5 D-3NpWPRp/4 pUNE- 8 ' D-4 ZONEj a �i;APJIEL cyc� F/ LIcLr.-`otic / EL 12) A. OJA A TT, / Al2 ( 4I OJALA v CIVIL / "'o. 40980 < `b t„502 .c o m Fc o STEL Gia / DATE DANIEL A. OJALA, P.L.S.,7C• ZONING SUMMARY ZONING DISTRICT: R25 RESIDENTIAL DISTRICT MIN. LOT SIZE 25,000 S.F. 15,600 S.F. MIN. LOT FRONTAGE 150' 130' MIN. FRONT SETBACK 30' 31.3' MIN. SIDE SETBACK 15' 15.9'f MIN. REAR SETBACK 20' 29.7' ✓ MAX. LOT COVERAGE 25% 22.0% SITE IS LOCATED NOT WITHIN MASS DEP ZONE II. OWNER OF RECORD THEODORE WOJNAR 104 CALM COURT BELLAIRE, TX 77401 REFERENCES LAND COURT DOC: 1,045,034 LAND COURT CTF; 181185 LAND COURT PLAN 14426-H (SHEET 2) REQUIRED INSPECTIONS AND CERTIFICATIONS 1. ENGINEER SHALL INSPECT WHEN REQUIRED EXCAVATION IS COMPLETE. 3. ENGINEER SHALL STAKE FOOTING PRIOR TO POURING 3. ENGINEER SHALL INSPECT FOOTING AND REBAR PRIOR TO POURING OF WALL 4. ENGINEER SHALL INSPECT WHEN CLEAN FILL HAS BEEN PROPERLY DEPOSITED 5. ENGINEER SHALL INSPECT AND CERTIFY SEPTIC COMPONENTS AND PUMP MECHANISMS AFTER INSTALLATION ENGINEER SHALL CERTIFY TO YARMOUTH HEALTH DEPARTMENT THAT THE RETAINING WALL, SEPTIC SYSTEM AND PUMP MECHANISMS HAVE BEEN INSTALLED IN SUBSTANTIAL COMPLIANCE NTH THE APPROVED PLAN. TITLE 5 SITE KLAN OF 10 WHALE ROAD WEST YARMOUTH PREPARED FOR THEODORE WOJNAR DATE: MARCH 15, 2010 REV 4/20/10 (MOVE/ROTATE HSE) REV 5/25/10 (ROOF & PATIO) REV 8/19/10 ( PER BOH: SLAB, P/C NOTES) Scale: l "= 20' 0 10 20 30 40 50 FEET I off 508-362-4541 fax 508-362-9880 CUth Health Department downcOpe.com p APPROVED down cape engineering, inr. � v 7 Civil engineers /and surveyors 939 Main Street ( Rte 6A) YARMOUTHPORT MA 02675 10-006 WOJNAR.DWG