HomeMy WebLinkAbout0 Willow Street - Cape Light Compact - Site Plan 8PUMP INSTALLATION 1. SEPTIC SYSTEM PUMPS SHALL BE MYERS SRM 4/10 HP PUMPS OR EQUAL PUMPS SHALL BE INSTALLED IN STRICT CONFORMANCE WITH THE MANUFACTURERS SPECIFICATIONS. PRIOR TO ORDERING PUMPING EQUIPMENT AND THE INSTALLER SHALL PROVIDE THE DESIGN SHOP DRAWINGS OF THE ALL PUMPING EQUIPMENT FOR APPROVAL. INSTALLER SHALL CONFIRM THAT THE REQUIRED POWER CONFIGURATION FOR FOR THE PUMP(S) IS AVAILABLE AT THE SITE. NOTE STAINLESS STEEL RAIL MOUNT REQ. 2. CONTROLS: PUMP CONTROLS SHALL BE LOCATED WITHIN THE OFFICE IN AN ACCESSIBLE AREA AND SHALL BE ENCLOSED AS REQUIRED TO MEET ALL STATE AND LOCAL CODES AND REGULATIONS. THE PUMPS SHALL OPERATE ALTERNATELY. PUMPS SHALL OPERATE FOLLOWING SEQUENCE: o. PUMPS OFF b. LEAD PUMP ON e. ALARM ON AND LAG PUMP ON (TWO PUMPS OPERATE OR ALTERNATE PUMP SUBSTITIUTES FOR FAILED PUMP) d. PUMPS MUST ALTERNATE 3. ALARM: PUMPS SHALL BE EQUIPPED WITH AN ALARM POWERED BY A CIRCUIT SEPARATE FROM THE PUMP POWER. THE ALARM SHALL CONSIST OF A RED WARNING LIGHT AND AUDIBLE SIGNAL WITH PRESS TO SILENCE SWITCH. THE ALARM SHALL SIGNAL A HIGH WATER LEVEL CAUSED BY PUMP FAILURE. 4. PROPER FUNCTION OF PUMPS, CONTROLS AND ALARMS SHALL BE DEMONSTRATED BY CLEAN WATER TESTING, ENGINEER TO WITNESS AND CERTIFY SEPTIC CALCULATIONS: OFFICE 26508 (.075) = 1988 GPD (NO STORAGE FLOW) NOTE: 278789SF (440 GPD/40000 SF)- 3066 GPD ALLOWED USE 1988 GPD DESIGN FLOW 2 COMPARTMENT TANK, 2X 1X REQ. USE 6000 GAL S/T (4000 AND 2000 GAL COMPARTMENTS USE 3000 GAL P/C USE 30' X 90' LEACHING FIELD (.74)=1998 GPD > 1988 O.K. 2.5' 5' 5' 5' 5'S, 2.5' 4"PERF, SCH40 PVC LINES _ 30' LEACHING BED SECTION SHOWING LATERAL SPACING SCALE: 1"=10' ALARM AND CONTROL PANEL TO BE INSTALLED INSIDE BUILDINGS. ALARM TO BE ON SEPARATE CIRCUIT FROM PUMP ELECTRIC PERMIT REQUIRED PROPOSED 800 SF STORAGE OFFICE SLAB EL. 38.63 24"I.D.MANHOLE SEE DETAIL TYP. ' 34.5 B 10" 14' .Tit'.. 34.2 8 TEE TEE Y'' 33.89 B 7' 1500 GAL H-20 GAS BAFFLE & 33.95 B -' 4" SCH-40 PVC AT 2% ( SEPTIC TANK ZABEL FILTER •.= '. 4 LIQ. LEVEL ACME OR EQUAL A100 FOUNDATION 6" GRAVEL &MECH. 4' SCH-40 PVC AT 2% COMPACTION (TYP.) 3' AT 0.02 SEPTIC TANK 1500 GAL H-20 DEPTH OF FLOW = 4' SEPTIC TANK 4' LIQ. LEVEL TEE SIZES: ACME OR EQUAL INLET DEPTH = 10" OUTLET DEPTH 14" TANIV(Z _ CZTOPAr-P' of PARKING LOT 0.5% MIN. PROPOSED SLAB FOUNDATION FIRST FLOOR EL. FOUNDATION STORAGE P/C 4 FxuS:o PROTECT. We" .r , SEE ABOVE PUMPS FO In K'n Z SECTION A -A SCALE: N.T.S. H-20 CAST IRON COVERS 2'-10" 26' TH1 TH2 TH3 TH4 SOIL EVALUATOR: DAN OJALA P.L.S. SOIL EVALUATOR: DAN OJALA P.L.S. SOIL EVALUATOR: DAN OJALA P.L.S., SE SOIL EVALUATOR: DAN OJALA P.L.S., SE DOWN CAPE ENGINEERING DOWN CAPE ENGINEERING DOWN CAPE ENGINEERING DOWN CAPE ENGINEERING WITNESS: KELDA WELCH (BOH) WITNESS: KELDA WELCH (BOH) EXCV. STEVE VAUGHN(BORTOLOTTI) EXCV. STEVE VAUGHN(BORTOLOTTI) EXCV. SCOTT (BORTOLOTTI) EXCV. SCOTT (BORTOLOTTI) DATE: 7-2-99 2 PM DATE: 7-2-99 2 PM DATE: MAY 22 1999 DATE: MAY 22 1999 0-2" 0 ORGANIC 10YR2/1 0-2" 0 ORGANIC 10YR2/1 0-2" 0 ORGANIC 10YR3/2 0-3" 0 ORGANIC 10YR3/2 2-4" A LOAMY SAND 10YR5/2 2-4" A LOAMY SAND 10YR3/2 2-5" A LOAMY SAND 10YR4 4 3-8" A LOAMY SAND 10YR4 4 4-36" B LOAMY SAND 2.5Y7/6 4-36" B LOAMY SAND 2.5Y7/6 5-38" B LOAMY SAND 1076/6 B-30" B LOAMY SAND 10YR5/8 36-60" Cl M/F SAND 2.5Y7/4 (LOWER 12" IOYR3/2) 36-66" Cl M/F SAND 2.51'7/4 38-66" Cl M/C SAND 2.5Y6/6 30-48" Cl M/C SAND 2.5Y6/6 10% GRAVEL 60'-84" C2 LOAMY SAND 2.5Y8/4 (REMOVE C2 FOR DRAINAGE, 66"-78" C2 SILT LOAM 2.5Y6/4 (UNSUITABLE, REMOVE) 66-78" C2 SANDY LOAM 7.SYR6/6 (FIRM, UNSUITABLE) 48-68' C2 MED SAND 2.SY7/3 84"-132" C3 M/C SAND 2.5Y7/6 OK FOR SAS) 78'-138" C3 M/C SAND 2.5Y7/6 - 78-144'C3 M/C SAND 1GYR5/6 68-168'C3 M/C SAND 2.5Y6/6 LENS OF SILT LOAM FROM 5'-10' NO GROUNDWATER FOUND NO GROUNDWATER FOUND /8• GROUNDWATER FOUND AT 10.8' GROUNDWATER FOUND AT 12.0' ON SOUTH SIDE OF HOLE UNSUITABLE; REMOVE EL. 37.7 0' EL 36.7 0" EL. 37.1 0' EL. 37.7 0' 0 2' 0 2" A2" A 3" A 4. A 4" ��`Q,yb'F#�YS7f;1=y,�� 5• 8" 6 B 9 ZONE E 8 ZONE E EL 34.7 36" EL 33.7 36" MANUF. LaBARON, BROCKTON, MA AIW247 4/99 23.9 -ZONE D-5.3 EL 35.25 30" AIW247 4/99 23.9 -ZONE D-5.3 MODEL, LT 105 EL. 33.97 38" AIW230 4/99 23.5 ZONE E-4.5 AIW230 4/99 23.5 ZONE E-4.5 Cl Cl WEIGHT: 430 LBS USE 5.3' ADJ. ClUSE 5.3' ADJ. EL. 32.7 60" TYPICAL ACCESS COVERL 33.75 46" EL. 29.7 66" ClCi C2 C2 C2 BOTTOM PERC AT 46' � 30 70 84" EL. 29.70 64' BOTTOM PERC SCALE: 3/4" - 1'-0" 244 GAL POUREDTIN14:30 EL 32.08 66" 24 GAL POURED EL 31.64 ADJ. WATER 6"AT 10:30 <2 MIN/IN C2 <2 MIN/IN EL 31.05 - ADJ. WATER EL 30.64 78' C3 C3 32" 5.3'C3 5.3'C3 24" 440 GAL RESERVE 3• w ALARM oN CHECK VALVE TYP. 440'± TO SEPTIC TANK PUMP ON NO WEEP HOLE MAINTAIN FROST z, PUMP OFF PROTECTION (4') LOW ALARM FLOAT SWITCH 4" WORKING RANGE 1 UP SETTINGS: SET AS SHOWN 6" GRAVEL & MECH. \ COMPACTION (NP.) DUAL MYERS SRM4 i(o HP PUMPS PUMP CHAMBER MOUNT ON MYERS CHAIN PULL STAINLESS STEEL RAIL MOUNT SYSTEM (NO SUBSTITUTIONS) 1000 GAL H-20 PUMP CHAMBER 4' LIQ. LEVEL ACME OR EQUAL (TYP,) i�■m�i w I era" r•1 4500 GAL 2400 CAL �� r * MORTAR ALL COMPONENTS CLEAN COMPACTED o SANDITT 440 GAL RESERVE 3• w ALARM oN CHECK VALVE TYP. 440'± TO SEPTIC TANK PUMP ON NO WEEP HOLE MAINTAIN FROST z, PUMP OFF PROTECTION (4') LOW ALARM FLOAT SWITCH 4" WORKING RANGE 1 UP SETTINGS: SET AS SHOWN 6" GRAVEL & MECH. \ COMPACTION (NP.) DUAL MYERS SRM4 i(o HP PUMPS PUMP CHAMBER MOUNT ON MYERS CHAIN PULL STAINLESS STEEL RAIL MOUNT SYSTEM (NO SUBSTITUTIONS) 1000 GAL H-20 PUMP CHAMBER 4' LIQ. LEVEL ACME OR EQUAL (TYP,) i�■m�i w I era" r•1 4500 GAL 2400 CAL �� r * MORTAR ALL COMPONENTS CLEAN COMPACTED o SANDITT ................... ..... 10'X17' ACME LOW PROFILE OR EQUAL DEPTH OF FLOW = 61 - TEE SIZES: INLET DEPTH >= 10" q OUTLET DEPTH - 29", 8" H-20 F&C (TYP,) i�■m�i w I era" r•1 4500 GAL 2400 CAL �� r * 10'X17' ACME LOW PROFILE OR EQUAL DEPTH OF FLOW = 61 - TEE SIZES: INLET DEPTH >= 10" q OUTLET DEPTH - 29", 8" H-20 F&C (TYP,) w I ADJUSTNG BLOCKS/1-1-20 RISER * MORTAR ALL COMPONENTS CLEAN COMPACTED o SANDITT ................... ..... oo000 oo°oau000 4" MIN. PEASTONE 6"OSCH-40 PVCI AT 2% MIN.onovo°000 ( Qoo°aooaa AND MIRAFI 140NS FROM ROOF DR(JNS a °oB", 5 -0 X 6 0 FABRIC OVER STONE oa°a a a 000.g...a H-20 " 000 oo°oo°o } L -. - - _ po°°oo°°o 000°o°000 800 GAL o°o°o°°Oa / 0 0°0°o a LEACHPIT 000°apo° aoaoaaa NOTE: IF INVERT OF DRYWELL IS ABOVE °°°° SHOREY OR EQUAL o aaaaaa°aa ELEVATION OF NATURAL Cl HORIZON ON oaoa SOIL LOGS, THE B LAYER MUST BE REMOVED 5' LATERALLY ALL AROUND aoao°aoaa aoa000°o° BASIN TO DEPTH OF Cl HORIZON AND e�soa°a°e° L°+°$000 REPLACED WITH CLEAN COARSE COMPACTED SAND. \\\ REMOVE ANY OTHER UNSUITABLE MATERIAL \ 3/4" - 1 1/2" ENCOUNTERED FOR 5' AROUND AND UNDER \ DOUBLE WASHED STONE LEACHING STRUCTURES. 4' MIN. AROUND PIT & 6" UNDER PIT ROOF DRAIN SECTION NOT TO SCALE 9L CONC. U BASE TO `---- MANUF. SPEC REMMANY/TOP&SUBSOIL (A & B HORIZONS) FROM ENEATH RETENTION BASIN BELOW CONTOUR 35 AND I REPLACE WITH CLEAN SAND. COVER WITH 4" LOAM AND HYDROSEED BASIN AREA FABRIC OVER OVERLAP 12" 4" PEASTONE OVE EL 26.34 _ OBSV. WATER AT 10.8 EL 25.75 _ OBSV. WATER AT 12.0 EL. 26.7 132" EL. 25.2 1 1138" EL 25.14 144' EL 23.75 168" TH5 TH7 TH8 24" SOIL EVALUATOR: DAN OJALA P.L.S., SE SOIL EVALUATOR: DAN OJALA P.LS., SE SOIL EVALUATOR: DAN OJALA P.L.S., SE DOWN CAPE ENGINEERING TH6 ((AUGER HOLE) DOWN CAPE ENGINEERING DOWN CAPE ENGINEERING EXCV. STEVE VAUGHN(BORTOLOTTI) SOIL PJALUATOR: DAN OJALA P.L.S. EXCV. STEVE VAUGHN(BORTOLOTTI) EXCV. STEVE VAUGHN(BORTOLOTTI) 7 DATE: 7-2-99 2 PM DOWN CAPE ENGINEERING DATE: 7-2-99 2 PM DATE: 7-2-99 2 PM 0-2" 0 ORGANIC 10YR2/1 DATE: 4-27-99 2 PM 0-3" 0/A LOAMY SAND 10YR3/2 0-2" 0/A LOAMY SAND IOYR4/2 m 2-4" A LOAMY SAND 10YR5/2 3-5" E LOAMY SAND 10YR7/2 2-4" E LOAMY SAND IOYR6/1 4-36" B LOAMY SAND 2.5Y7/6 0-1" 0 ORGANIC 10YR2/1 5-34" B LOAMY SAND 10Y7 8 4-36" B LOAMY SAND 10YR6/6 VARIGATED COLORS AT 84" 3" 36-66" Cl M/F SAND 2.5Y6/4 (TRACE SILT) 1-3" A LOAMY SAND 10YR3 2 34-132" Cl MED SAND 2.5Y7/4 36-132" Cl M/C SAND 2.5Y7/6 66'-72' C2 SILT LOAM 2.5Y7/4 (UNSUITABLE, REMOVE) 3-36' B LOAMY SAND 10YR6 8 10% GRAVEL GROUNDWATER AT 10.5' GROUNDWATER AT 10.6' 72"-138" C3 M/C SAND 2.5Y6/4 36-126" Cl M/C SAND 2.5Y7/6 10% GRAVEL NO GROUNDWATER FOUND EL 36.9 0 0' EL 38.0 0 0" A 1" EL 35.44 0/ A 0" EL 36.20 0 A 0" 2' 3" 3' / 2- A ZONE E E E FRAM E AN D G RATE B 4 EL. 33.9 B 36"W247 499 23.9 -ZONE D-5.3 AIW230 4/99 23.5 ZONE E-4.5 B ZONE E B 4 ZONE E EL. 35.0 36" USE 5.3' ADJ. EL 32.60 34" AIW247 6/99 24.3 -ZONE D-6.0 EL 33.20 36" AIW247 6/99 24.3 -ZONE D-6.0 SCALE: 3/4" - 1'-O" Cl AIW230 6/99 23.9 ZONE E-5.1 AIW230 6/99 23.9 ZONE E-5.1 MINIMUM WEIGHT: 388. LBS. Cl USE 6.0' ADJ. USE 6.0' ADJ. BUILDING. ALARM TO BE ON SEPARATE CIRCUIT FROM PUMP ELECTRIC PERMIT REQUIRED 3000 GAL PUMP CHAMBER 7'Y17' AC1AF mw PRnFII F nR 7011Al EL. 32.5 66' EL 32.0 C2 72" EL 31.8 _ ADJ. WATER Cl BOTTOM PERC AT 78" Cl 24 GAL IN 8:30 5.3' EL. 30.94 - ADJ. WATER <2 MIN/IN EL 31,60 _ ADJ. WATER C3 I i 6.0' 6.0' EL 26.5 _ OBSV. WATER AT 10.4' EL 26.4 126" EL. 24.94 - 126' EL. 25.60 EL 26.5 138"'. EL. 23.55 132' EL. 25.20 INSECT SCREEN SEE PAVEMENT CROSS SECTION L SOLID 12" OH -20 INVERTS CPP: SLOPE AS NOTED PER PLANm Y COMPACT BACKFILL G AROUND PIPE 1000 GALLON PRECAST H-20 MANHOLE '0X6'-8" S14OREY SOLO - BASIN H-20 OR EQUAL 127" 132" NOTE: ADDITIONAL TEST HOLES TO BE PERFORMED RESULTS WILL BE ADDED TO PLANS WITH ADDENDUM. 12" X 3" 1" CCBERM f MASS DPW TYPE 11 \ 12" PROCESSED GRAVEL MDPW M1.03.1 MD. ROLLER COMPACTED REMOVE TOP & SUBSOIL COMPACT SUBBASE SS SECTION T CRO NOT TO SCALE REMOVE TO THE BOTTOM OF THE B LAYER AND ANY UNSUITABLE SOIL AS SHOWN ON TEST HOLE LOGS. THE DEPTH OF FILL AND UNSUITABLE MATERIAL MAY VARY, ENGINEER TO INSPECT REMOVAL. i vn� in ni v l l vt-t. DETAIL SHEET ACCOMPANYING R CROSS SECTION SCALE: N.T.S. SITE PLAN DRAINAGE SYSTEM DETAIL OF LAND IN WEST YARMOUTH, MA SCALE: N.T.S. N 8" H-20 F&G EL'S LISTED CAPE LIGHT COMMONS DRILL (2) 1.0 OFFICE PARK AND STORAGE CENTER HOLES ADJ. BLOCKS AS REQ. PIPE 12"0 SLOTTED H-20 MORTAR ALL COMPONENTS TOP OF STRUCTURE CORRUGATED HDPE PIPE (TYP.) ADS N-12 OR EQUALSCALE AS NOTED DATE: 7-19-99 ;,�y --•= �-•=< -,- REVISED: 3-01-01 .75"-1.5" DOUBLE 2.0 (TVP.) REVISED: 4-27-01 1.5' 0 WASHED STONE o 0 0 0 0 0 3 C.B. TRAP ALL UNSUITABLE MATERIALS TO BE REMOVED a6 .1-0 0), �7 12"0 HDPE PIPE �V`H OF PREPARED Fi'QR.; q• FOR 5' HORIZONTALLY AND TO REQUIRED DEPTH .00.-- _�- ELBOW p'Z� BORNSTEIN COMPANIES AROUND ALL LEACHING TRENCH. ENGINEER TO INSPECT. SEH- �, off 508-362-4541 UNSUITABLE SUBSOIL AVERAGED 3' DEPTH. 0JAIJA 297 NORTH STREET fax 508 362-9880 ClIn TRENCH CROSS SECTION SLOTTED H-20 1000 GALLONSE PRECAST gam ti HYANNIS, MA 12'0 HDPE H-20 CATCH BASIN down cape engineering, Inc. NTS LEVEL BETWEEN BASINS ARN DATE INVERTS LISTED ON PUN '0X6'-8" SHOREY SOLID CI if BASIN H-20 OR EQUAL CIVIL ENGINEERS SECTIONAL PLATE DRAINAGE CROSS SECTIONLAND SURVEYORS NOT To SCALE SHEET 3 OF 3 939 main st, yarmouthport, ma 02675 r FRAM E AN D G RATE B 4 EL. 33.9 B 36"W247 499 23.9 -ZONE D-5.3 AIW230 4/99 23.5 ZONE E-4.5 B ZONE E B 4 ZONE E EL. 35.0 36" USE 5.3' ADJ. EL 32.60 34" AIW247 6/99 24.3 -ZONE D-6.0 EL 33.20 36" AIW247 6/99 24.3 -ZONE D-6.0 SCALE: 3/4" - 1'-O" Cl AIW230 6/99 23.9 ZONE E-5.1 AIW230 6/99 23.9 ZONE E-5.1 MINIMUM WEIGHT: 388. LBS. Cl USE 6.0' ADJ. USE 6.0' ADJ. BUILDING. ALARM TO BE ON SEPARATE CIRCUIT FROM PUMP ELECTRIC PERMIT REQUIRED 3000 GAL PUMP CHAMBER 7'Y17' AC1AF mw PRnFII F nR 7011Al EL. 32.5 66' EL 32.0 C2 72" EL 31.8 _ ADJ. WATER Cl BOTTOM PERC AT 78" Cl 24 GAL IN 8:30 5.3' EL. 30.94 - ADJ. WATER <2 MIN/IN EL 31,60 _ ADJ. WATER C3 I i 6.0' 6.0' EL 26.5 _ OBSV. WATER AT 10.4' EL 26.4 126" EL. 24.94 - 126' EL. 25.60 EL 26.5 138"'. EL. 23.55 132' EL. 25.20 INSECT SCREEN SEE PAVEMENT CROSS SECTION L SOLID 12" OH -20 INVERTS CPP: SLOPE AS NOTED PER PLANm Y COMPACT BACKFILL G AROUND PIPE 1000 GALLON PRECAST H-20 MANHOLE '0X6'-8" S14OREY SOLO - BASIN H-20 OR EQUAL 127" 132" NOTE: ADDITIONAL TEST HOLES TO BE PERFORMED RESULTS WILL BE ADDED TO PLANS WITH ADDENDUM. 12" X 3" 1" CCBERM f MASS DPW TYPE 11 \ 12" PROCESSED GRAVEL MDPW M1.03.1 MD. ROLLER COMPACTED REMOVE TOP & SUBSOIL COMPACT SUBBASE SS SECTION T CRO NOT TO SCALE REMOVE TO THE BOTTOM OF THE B LAYER AND ANY UNSUITABLE SOIL AS SHOWN ON TEST HOLE LOGS. THE DEPTH OF FILL AND UNSUITABLE MATERIAL MAY VARY, ENGINEER TO INSPECT REMOVAL. i vn� in ni v l l vt-t. DETAIL SHEET ACCOMPANYING R CROSS SECTION SCALE: N.T.S. SITE PLAN DRAINAGE SYSTEM DETAIL OF LAND IN WEST YARMOUTH, MA SCALE: N.T.S. N 8" H-20 F&G EL'S LISTED CAPE LIGHT COMMONS DRILL (2) 1.0 OFFICE PARK AND STORAGE CENTER HOLES ADJ. BLOCKS AS REQ. PIPE 12"0 SLOTTED H-20 MORTAR ALL COMPONENTS TOP OF STRUCTURE CORRUGATED HDPE PIPE (TYP.) ADS N-12 OR EQUALSCALE AS NOTED DATE: 7-19-99 ;,�y --•= �-•=< -,- REVISED: 3-01-01 .75"-1.5" DOUBLE 2.0 (TVP.) REVISED: 4-27-01 1.5' 0 WASHED STONE o 0 0 0 0 0 3 C.B. TRAP ALL UNSUITABLE MATERIALS TO BE REMOVED a6 .1-0 0), �7 12"0 HDPE PIPE �V`H OF PREPARED Fi'QR.; q• FOR 5' HORIZONTALLY AND TO REQUIRED DEPTH .00.-- _�- ELBOW p'Z� BORNSTEIN COMPANIES AROUND ALL LEACHING TRENCH. ENGINEER TO INSPECT. SEH- �, off 508-362-4541 UNSUITABLE SUBSOIL AVERAGED 3' DEPTH. 0JAIJA 297 NORTH STREET fax 508 362-9880 ClIn TRENCH CROSS SECTION SLOTTED H-20 1000 GALLONSE PRECAST gam ti HYANNIS, MA 12'0 HDPE H-20 CATCH BASIN down cape engineering, Inc. NTS LEVEL BETWEEN BASINS ARN DATE INVERTS LISTED ON PUN '0X6'-8" SHOREY SOLID CI if BASIN H-20 OR EQUAL CIVIL ENGINEERS SECTIONAL PLATE DRAINAGE CROSS SECTIONLAND SURVEYORS NOT To SCALE SHEET 3 OF 3 939 main st, yarmouthport, ma 02675 r r