HomeMy WebLinkAbout83-1859 - Site Plan002SYSTEM DESIGN: GARBAGE DISPOSER IS NOT ALLOWED DESIGN FLOW: 4 BEDROOMS @ 110 GPD = 440 GPD USE A 440 GPD DESIGN FLOW SEPTIC TANK: 440 GPD (2) = 880 USE A 1500 MIN. GAL. SEPTIC TANK BOTTOM AREA ONLY: 13.5' (+/-) X 50.3'= 602 SF X (.74) = 446 GPD USE A 602 SF LEACHING FIELD AS SHOWN MA APPROVED DATE BOARD OF HEALTH NOTES I. VMIVIVI I - 2. MUNICIPAL WATER IS AVAILABLE 3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT. 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS TO BE AASHO H-10 5. PIPE JOINTS TO BE MADE WATERTIGHT. 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH 310 CMR 15.000 (TITLE V.) 7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO BE USED FOR LOT LINE STAKING OR ANY OTHER PURPOSE. 8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC. 9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED WITHOUT INSPECTION BY BOARD OF HEALTH AND PERMISSION OBTAINED FROM BOARD OF HEALTH. 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING DIGSAFE (1-888-344-7233) AND VERIFYING THE LOCATION OF ALL UNDERGROUND & OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK. . 11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE REMOVED 5' BENEATH AND AROUND THE PROPOSED LEACHING FACILITY. 12. EXISTING LEACHING FACILITY SHALL BE PUMPED AND REMOVED OR PUMPED AND FILLED WITH CLEAN SAND. 13. NO"BASEMENT" ALLOWED. FLOODZONE RESISTANT DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS AS SHOWN. 14. ALL RUN-OFF TO BE CONTAINED ON-SITE DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS. 15. DRYWELLS (OR DRIP TRENCHES) SHALL BE INSTALLED TO CONTAIN ROOF RUN-OFF. 16. CONTRACTOR TO COORDINATE ALL UTILITY DISCONNECTS AND NEW SERVICES WITH APPROPRIATE VENDORS. 17. CONTRACTOR TO NOTE ORDER OF CONDITIONS COVERING ANY WORK ON SITE TO BE ISSUED BY THE TOWN OF YARMOUTH CONSERVATION COMMISSION. COPY OF ORDER TO BE ONSITE AND ALL CONDITIONS AND SPECIAL CONDITIONS SHALL BE ADHERED TO. REQUIRED INSPECTIONS AND CERTIFICATIONS 1. ENGINEER SHALL INSPECT WHEN REQUIRED EXCAVATION IS COMPLETE. 2. ENGINEER SHALL STAKE FOOTING PRIOR TO POURING 3. ENGINEER SHALL INSPECT FOOTING AND REBAR PRIOR TO POURING OF WALL 4. ENGINEER SHALL INSPECT WHEN CLEAN FILL HAS BEEN PROPERLY DEPOSITED 5. ENGINEER SHALL INSPECT AND CERTIFY SEPTIC COMPONENTS AND PUMP MECHANISMS AFTER INSTALLATION ENGINEER SHALL CERTIFY TO YARMOUTH HEALTH DEPARTMENT THAT THE RETAINING WALL, SEPTIC SYSTEM AND PUMP MECHANISMS HAVE BEEN INSTALLED IN SUBSTANTIAL COMPLIANCE WITH THE APPROVED PLAN. pAr *THE INSTALLER SHALL VERIFY THE LOCATIONS OF ALL UTILITIES AND ALL BUILDING SEWER OUTLETS AND ELEVATIONS PRIOR TO INSTALLING ANY PORTION OF SEPTIC SYSTEM FIRST FLOOR BLDG ELEV. 11.0' CONCRETE ACCESS COVERS TO WITHIN 6" OF FIN. GRADE RAWLSPACE SLAB .6' roP FOUNDATION 10.03 WITHIN 20' OF SAS g 5' REMAINDER OF CRAWLSPACEMINIMUM .75' of c0v ALL SYSTEM COMPONENTS SHALL BE MA KED WITH MAGNETIC TAPE OR COMPARABLE MEANS FOR FUTURE LOCATION. MARK CORNERS DF LEACH FIELD WITH 24" #5 REBAR WITH AFETY CAP DRIVEN JUST BELOW GRADE EACH CORNER OF LEACH FIELD. 4" DIA PERF. INSP. PORT TO SAND AT BOTTOM OF LE CHING FIELD. 4" THREADED CAP TO WITHIN 3" OF FINISH GRADE 40 MIL LINER FROM ELEV. 8.8' TO ELEV. 4.8' MIN. \ RETAINING WALL SCHEMATIC SHOWN, EXACT FASCADE \\\ AND CONSTRUCTION BY OTHERS. TOP OF WALL HT. AS NOTED ' OVER PRECAST /F--. TOP PIPE 8.65± FINISHED GRADE- 4" LOAM &SEED 2% MIN. SLOPE OVER SYSTEM SLAB AT EL. 7.4' PRECAST H-10 PROP. TEE / \ ` T P T -p (C C 4"SCH40 .... RISERS OY'P.) i r \ . . FLOOD VENTS WITHIN 12" GRADE 2m 4"OSCH40 PVC CLEAN FILL / PIPES LEVEL 1ST 2' - 10' �'-- . ��'.. .-:�-;; . �.-:::.: _,:.-, �. , ..,.:_:;: :.:,:.:,,. CAP ENDS a (GROUND AT EL. 7.4) REQ. TEE 2500 GAL r ° ^ r 4" PERFORATED PVC. 5=0.005 0 VENTS ON 2 SIDES REQ. s,: SEPTIC TANK/PC o FLOOD VENT/FOUNDATION DESIGN 7.2 COMBINATION ° 3/4"-1-1/2 DOUBLE WASHED STONE LEACHING FIELD o ° °o°o°p°p°o°ege' 0 6"DEPTH MIN BELOW INV. BY OTHERS. SHOREY OR EQUAL ° '° °°° 8.25' 8.00' °"°,•°"°^O^O °• EVEL BOTTOM o / 7.5'* (SEE DETAIL) 8.52' 8.35 s:^:' '::: '. •.; ... - 55 5' MIN. UNSUITABLE _° BLOCK UP FOR 24" COVER NP. DEPTH OF FLOW 4' 0 O^ 0 O^ 0 O^ 0 O^ 0 O^ 0 O^ 0 0 O^ 0 O^_ 0 O^ 0 O^ 0 Cr - 0 -BOX ACME DB -5 OR EQ. 7.50 rDEPTH OIL REMOVAL °O °O °O °O °O °O °O °O °O °O °O °C HERE SPECIFIED INLET DEPTH = 10" SEPTIC SYSTEM PROFILE .0 PER SOIL LOGS 6CRUSHED STONE OR MECHANICAL 5 ~ ,.,'. °°°°°°°o°'°°°°°°°! OUTLET DEPTH = 14" COMPACTION. (15.221 [2]) TIDALLY INFLUENCED GROUNDWATER _ 2.5' LEACHING: USE A 602 SF LEACHING FIELD 602 SF X .74 = 445 GPD O.K. (2-% SLOPE) (--Z-% SLOPE) (-1-7 SLOPE) FOUNDATION -SEPTIC TANK LEACHING - 15 2' D' BOX 12 C-A^II ,T,y 11 LOT 80 0.54 ACRES± (12,745± UPLAND) all, alr, _ NOTE: WETLAND RESOURCE AREAS FLAGGED BY LEC ENVIRONMENTAL CONSULTANTS, INC. Qom/ atP QQQ' / OP�QG� F-� Qy 'Ill,LEG ally V0� i y �o 1011 �Pe FLAG - 0111 y�P all, SM #17 �6 EXISTCONC . � I ally �5`I' all, / BLOCK PAVEO PAT/10 5Qy SM#2/� PROP. SITTING I �j dll, i1 i' WALL/AT EDGE, OF 1PAT10 &,C �' \ 0111 011, Ir- I?, I? / O PROP. VENT WITH CHARCOAL FILTER \ AND BUGSCREEN (FINAL PLACEMENT BY CONTRACTOR WITH HOMEOWNER CONSULTATION) A.--•, 0 LEC FLAG ` ��9 w m 4� N o 6 N o '•s. c� PROP. 4 BR DWELLING -I o. 6' FIRST FL ELEV. 11.0' (CRAWLSPACE SLAB ELEV. MIN. 8.25') 5' UNSUITABLE SOIL REMOVAL LIMIT AROUND LEACHING FIELD Y/ EXISTING 4 BR DWELLING (TO BE REMOVED AND REPLACED) EXISTING FIRST Fl. ELEV. = 9.4' ��9eO AIi8E MW \ T (LEC) (DCE) / \ �,WO� PROP. OP ' \ / \ DRIVEWAY 0 QSTON�- 6� LFAVED / \ IVE �-+ i A �d� 1 ,[ \C3 ky Dc � BOG ob / v / A\/ / PROPOSED 4 BR SEPTIC SYSTEM TO O\ /1I / CONSIST OF A TITLE 5 COMPLIANT 1500 'FSTO ROP. RET. )N LL GALLON SEPTIC TANK, DBOX, AND A c3P TW- 9 0' 602 SF LEACH FIELD, BASE OF WHICH (DESiI , YY7TTHERS) IS 5' ABOVE HIGH GROUNDWATER. FINAL GRADE (VER SAS TO BE ELEV. 10.0 -9.5' VCIES /-/ BENCHMARK: C. BASIN AT / SITE PLAN Scale: 1 "= 20' 0 10 20 30 40 so FEET NOTE: NO INCREASE IN TITLE 5 DESIGN FLOW, NOT "NEW CONSTRUCTION" UNDER TITLE 5. VARIANCES REQUESTED UNDER MAXIMUM FEASIBLE COMPLIANCE 15.405: (1a) LEACHING FIELD TO BE LOCATED 7.5' FROM LOT LINE (10' REQUIRED) VARIANCE OF 2.5' REQUESTED (1f) LEACHING FIELD TO BE LOCATED 25' FROM DRAIN WHICH MAY INTERCEPT HIGH GROUNDWATER- 50' REQ. 25' VARIANCE REQUESTED, WALL/LINER PROVIDED VARIANCE TO LOCAL BOARD OF HEALTH REGULATIONS REG. 3.7: LEACHING AREA TO BE 70.4' FROM COASTAL BANK, 100' REQUIRED, 29.6' VARIANCE REQUESTED DCE # 09-130 ELEVATION 4.95' NGVD29 PROPOSED ROCK WALL VENEER ACCESS FOR ROUTINE MAINTENANCE EXISTING CONTOUR MUST BE PROVIDED FOR ZABEL FILTER. EXIST. SPOT ELEV. 99 INSTALLER MUST FOLLOW ALL f98.4] PROPOSED SPOT EL. MANUFACTURER'S SPECIFICATIONS FOR PROPER FILTER INSTALLATION Z>A SLOPE OF GROUND UTILITY POLE yy FIRE HYDRANT -W- NOTE 5003 GAL. RESERVE PROVIDED IN PC ALARM AND CONTROL PANEL FENCE LINE TO BE INSTALLED INSIDE BUILDING. ALARM TO BE ON INV. IN 7.2' POST LIGHT SEPARATE CIRCUIT FROM PUMP 2" PRESSURE UNE ZABEL FILTER FLOAT SNITCH ALARM ON (A/oo) u'TEE SLOPE 70 DRAIN BACK OUTLET TEE W/EXTENSION SETTINGS: 1500 CAL MI WEEP HOLE PUMP ON B" THIS SIDE CHECK VALVE 5" WORKING RANGE OF BAFFLE MYERS SRM 4 5" PUMP OFF 12 S.B• SUBMERSIBLE 4/10 HP PUMP SYSTEM (OR EQUAL) (ON BLOCK) 4 DOSES PER DAY, AT 110 GAL. PER 000000 0000 00 0000 DOSE (5" WORKING RANGE) 5" BAFFLE 2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION (NOT TO SCALE) TEST HOLE LOGS ENGINEER: DANIEL A. OJALA PE, PLS SE1805 WITNESS: AMY VON HONE RS, CHO DATE: JULY 1, 2009 PERC. RATE _ < 2 MIN/INCH CLASS I SOILS 4 ELEV. V p" 7.0' 0^ 7.4' FILL FILL 3" LOAM 3" LOAM THEN SAND THEN SAND 24" 24" A LS A LS 27 tOYR 3/2 27" 10YR 3/2 B LS B LS 42„ 10YR 5/6 3.5' 42„ 10YR 5/6 3.5' PERC Cl C1 BOTT. AT 52', 24 GAL IN 9:30 < 2 MIN/INCH M/C S M/C S GROUNDWATER DEPTH 56.4" 2.5 Y 7/3 0 2.5 Y 7/3 el. 2.3' BUT TIDALLY INFLUENCED EL. 2.3' = SEE BELOW 120" I I -3.0 120" I -3.0 NOTE: MONITORING WELL OVER LUNAR CYCLE EL. 2.5 TIDALLY INFLUENCED- USE 2.5 NGVD29 AS ADJUSTED HIGH GROUNDWATER ELEVATION (AUTOMATED MONITORING WELL SET, AND READINGS TAKEN OVER NEW MOON CYCLE DURING HIGHEST TIDES OF JUNE) 4" DIA PERF. INSP, ORT TO SAND AT BOTTOM OF LEACHING FIELD. 4" THREADED CAP, SCH40 PVC THREADED CAP TO 4THIN 3" OF FINISH \GRADE 2% MIN. FINISH GRADE \ LOAM AND SEED notMIRAFI 140N FABRIC DIS 44444OR 2" PEASTONE 5' MIN. ADJ. GROUNDWATER 5' MIN.UNSUITABLE SOIL REMOVAL WHERE SPECIFIED DEPTH PER SOIL LOGS LEACHING TO 1 1/2" DOUBLE ) STONE (NO FINES) ELD TYPICAL DETAIL NOT TO SCALE °t !tip/ori DATE DANIEL A. OJALA, P.E., P.L.S. off 508-362-4541 fax 508-362-9880 downcope.com 170wn cope engineering, inc, civil engineers land surveyors 939 Moin Street ( Rte 6A) YARMOUTHPORT MA 02575 e Lewis Bay h ROd%p , s RDod 6 S1D� t1 e�rP Oleo Nantucket Sound LOCUS MAP SCALE 1"=2000'± ASSESSORS MAP 14 PARCEL 3 DATUM: NGVD LOCUS IS WITHIN FEMA FLOOD ZONE B & Al2 ELEV. 10 AS SHOWN ON COMMUNITY PANEL #250015 0005 D DATED JULY 2, 1992 (NOTE: ELEVATIONS, BASED ON NGVD, INDICATE ENTIRE SITE IS WITHIN THE 100 YEAR FLOOD ELEVATION) WETLAND RESOURCE AREAS FLAGGED BY LEC ENVIRONMENTAL CONSULTANTS, INC. ZONING SUMMARY ZONING DISTRICT: R-25 MIN. LOT SIZE 25,000 S.F. MIN. FRONT SETBACK 30' MIN. SIDE SETBACK 15' MIN. REAR SETBACK 20' MAX. LOT COVERAGE: 25% UPLAND AREA (TO C. BANK) = 12745 SF PROP. LOT COVERAGE: 23.8% SITE IS LOCATED WITHIN AP DISTRICT REFERENCES CTF 139728 LCP 14426H, LOT 80 LEGEN D EXISTING CONTOUR X 9.9 EXIST. SPOT ELEV. 99 PROPOSED CONTOUR f98.4] PROPOSED SPOT EL. TH1 TEST HOLE Z>A SLOPE OF GROUND UTILITY POLE yy FIRE HYDRANT -W- WATER LINE -X FENCE LINE LOT LINE POST LIGHT NOTE NOT ALL SYMBOLS MAY APPEAR IN DRAWING 'Varmot,th 4tealth 11?epartmrnt dame jU:ft-- ka SITE PLAN SHOWING PROPOSED DWELLING AT 355 GREAT ISLAND ROAD WEST YARMOUTH PREPARED FOR B. RODOALPH & M. MICOZZI JUNE 12, 2009 REV. JULY 1, 2009 (TH LOGS ETC.) REV. JULY 14, 2009 (FLOODZONES, ETC.) REV AUG. 10, 2009 (CRAWLSP. ELEV.) REV AUG. 18, 2009 (HEALTH DEPT. NOTES) REV AUG. 24, 2009 (FRONT STEPS) REV. SEPT. 15, 2009 (LOT COV.) REV. SEPT. 22, 2009 (T.W. EL) Scale: 1 "= 20' 0 10 20 30 40 50 FEET