HomeMy WebLinkAbout83-2036 - Site Planv ROOF RUN OFF
6 IF USING GUTTERS PROVIDE DRY WELLS OTHER-
°' WISE PROVIDE STONE TRENCH FOR DRIP LINE
00
M MAXIMUM BUILDING HEIGHT
ti
GRADE AT STREET SIDE OF BUILDING=19.5
19.5 + 35=54.5=MAX. PEAK ROOF
54.5-(33'-11.5"*)=TOP FOUND.=20.5
*DESIGN DISTANCE FROM PEAK TO TOP FOUND.
RIVERFRONT
ALL OF LOT IS IN THE RIVERFRONT
NEW CONSTRUCTION BEYOND EXISTING FOOTPRINT:
WINDMILL & DECK (RAISE) 661±S.F.
STONE PATIO 846±S.F.
HOUSE, DECK, STEPS 1290±S.F.
TOTAL NEW AREA 2797±S,F.
r •z.�,8
HARDSCAPE PATIO E
DESIGN
(SEE PHILIP CHENEY PLAN)
REMOVE SPRUCE
TREE
/ 6.9
RAISE IN PLACE EXISTING
ONE BEDROOM DWELLING
ON PIERS PER MCKENNA
ENGINEERING CONSULTANTS PLAN
WITH BOTTOM OF LOWEST HORI-
ZONTAL BEAMS TO BE AT
ELEVATION 14 NAVD88
PLUMBER TO INSTALL EJECTOR PUMP
4" PVC CAPABLE OF 40 GPM 0 14.2' OF HEAD,
A NON GRINDER PUMP NEEDS TO PASS 2" DIAM. SOLIDS
OR, A GRINDER PUMP MEETING PLUMBING CODE
10.5 MAY BE USED ONLY IF TWO COMPARTMENT
11.2 1500 GALLON SEPTIC TANK IS USED
11XBENCH MARK --TOP & CENTER OF
CONC. BOUND= 30.22 ASSIGNED
r 1zs
PROPOSED FENCE TT ` / i
ALONG TOP BANK / 77J
/ 3 1419
,91 y T y
1163/ r
�� . 13.9 13 6 7qS
1.3 X/ m
�h
G�
0
17,2
✓.7.6
Ctn,7 i
i<
i
_ �O• i
1.3
1 0 171
• 12.03
14,7
N /F
KILMAN
17.0
76
17,7
PROPOSED WATER
LONG STANDING /
OCCUPATION
17.48
N /F
COFFEY
1
9
PROPOSED 2390±S.F.
4 BEDROOM DWELLING
16.8 WITH 241±S.F. EN-
CLOSED DECK
E EDGE PROP.
DRIVE
18.5
18 4 17.96
1800
ZONING DISTRICT:
LEGEND
TH 1
TEST HOLE LOCATION, NUMBER
-W-
WATER LINE MARKINGS
E
OVERHEAD ELECTRIC WIRES (IF SHOWN)
-G--
GAS LINE MARKINGS
9.5 X 18,3
EXISTING & PROPOSED ELEVATIONS ('X' MARKS POINT)
2.
ELEVATIONS SHOWN ARE NAVD88 10.1' USING VERTCOM.
/--6-�
EXISTING CONTOUR
LOCUS IS IN FLOOD ZONES: VE(EL.13), AE(EL.11), X(0.2% RISK), X (OUTSIDE 0,2% RISK)
PROPOSED CONTOUR
UTILITY POLE (IF SHOWN)
®
EXISTING DRAINAGE CATCH BASIN
x -
FENCE (IF SHOWN, NOT ALL SHOWN)
5.
TREE (IF SHOWN, NOT ALL SHOWN)
__________
PROPOSED WORK LIMIT
REV, 10/23/2015
--PATIO
17.0
76
17,7
PROPOSED WATER
LONG STANDING /
OCCUPATION
17.48
N /F
COFFEY
1
9
PROPOSED 2390±S.F.
4 BEDROOM DWELLING
16.8 WITH 241±S.F. EN-
CLOSED DECK
E EDGE PROP.
DRIVE
18.5
18 4 17.96
1800
ZONING DISTRICT:
R25
FRONT YARD:
30'
SIDE YARD:
15'
REAR YARD:
20'
LOT COVERAGE:
25%
14. ALL CONSTRUCTION TO MEET TITLE 5 AND LOCAL REGULATIONS. 0
TEST HOLE DATE: November 5, 2014 8"
PERFORMED BY: Ron Cadillac, Soil Evaluator
WITNESSED BY: Amy Von Hone, RS, CHO
PERC RATE: <2'-00"/inch (Cl &C2 layers)
SOIL SURVEY(1993): Carver coarse sand 30"
PROP.TOP FOUND=20.5 GEOLOGIC MAP(1986): Harwich outwash plain deposits
2 Compartment Tank
Needed .f grinder invert 15.10 3 DRY WELLS (H-20)
Invert 15.85 1 Elector Pump used
Use Gas Baffle Use Gas Baffle Invert 14.33WITH TWO H-10 COVERS 64"
----------- Two H-10 COVERS P ro Proposed Posed Top Conc.=15.0
S=1 /4"/ft IteP Cloth=14.5
SLAB=15.3
1500 Gal. S-1/4" /ft Screened
-1_
S=1 /8"/ft F --6' Max /vent
THIS PLAN IS A VALID COPY ONLY IF IT BEARS
AN ORIGINAL RED STAMP AND SIGNATURE.
HEALTH AGENT APPROVAL
DATE
A layer 10yr 3/3
sandy loam
B layer 10yr 5/6
sandy loam
C1 layer 2.5y 6/4
'fine to med.
loamy sand
C2 layer 2.5y 6/
med. coarse sand
(trace fines)
no water
17.6
15.1
12.3
62
Invert 15.35 Septic Tank j/ 137
Proposed H-20 --- - -------
24
T TEST HOLE 2
Invert 14.50 Invert 14.17 12.17
6" Stone or compact Proposed , 9.6' 5.97' Bottom DEPTH (inches) ELEV,(feet)
P P Proposed i
NOTES
JOB NO. Y14-37
15 i
PALMER2.DWG
25' -�
1.
LOCUS IS A.M. 22, PARCEL 59.
FB 30/63 SB 13/62
2.
ELEVATIONS SHOWN ARE NAVD88 10.1' USING VERTCOM.
°
3.
LOCUS IS IN FLOOD ZONES: VE(EL.13), AE(EL.11), X(0.2% RISK), X (OUTSIDE 0,2% RISK)
<
ON FIRM PANEL 0569J DATED JULY 16, 2014. BOUNDARIES SHOWN ARE SCALED.
4.
ALL PIPES TO BE 4" SCH 40,, AND PITCHED AT 1/4" PER FOOT. (UNLESS NOTED)
5.
MUNICIPAL WATER IS AVAILABLE. LOTS WITHIN 100' ARE ON TOWN WATER.
Sao
6.
COMPONENTS TO BE AASHTO H-10, UNLESS NOTED.
7.
INLET TEE TO PROJECT DOWN 13", OUTLET TEE DOWN 14".
DESIGNDATA
8.
IF TWO OR MORE LINES, WATER TEST D -BOX FOR EQUAL FLOW
D -BOX EXIT PIPES TO BE LEVEL FOR FIRST TWO FEET.
NOT TO
9.
DEPTH OF COMPONENTS NOT TO EXCEED 3', OR VENTING MUST BE PROVIDED.
SCALE
BEDROOMS:
COVER : BUILD UP H-10 COVERS TO 6" BELOW GRADE --2 ON TANK, 2 ON D -BOXES, 2 ON LEACHING.
LEACH AREA
10.
STONE TO BE DOUBLE WASHED 3/4 TO 1 1/2" WITH 2" MIN. 1/8 TO 1/2" PEA STONE ON TOP.
LOCATION MAP
11.
IF UNSUITABLE SOILS, OR,501LS DIFFERING FROM THE SOIL LOG ARE FOUND,
REQUIRED CAPACITY:
CONTACT THE BOARD OF HEALTH, OR R.J. CADILLAC.
WITH
12.
IF AN OVERDIG IS CALLED FOR BELOW, FILL MATERIAL FOR 5' AROUND AND UNDER LEACHING
TEST HOLE 1
1500 GAL.
IS TO BE CLEAN GRANULAR SAND MEETING SPECIFICATIONS OF 310 CMR 15.255(3).
APPROX.-3'-OF STONE ON THE
13.
PUMP AND FILL ANY EXISTING CESSPOOLS. REMOVE ANY CLOGGED SOIL, BLOCK, AND STONE IN
522.5 SF
SIDES, FOR A 47-6" LONG BY 11'
LEACH AREA, AND DISPOSE OF AS DIRECTED BY HEALTH AGENT.
DEPTH (Inches) ELEV.(feet)
14. ALL CONSTRUCTION TO MEET TITLE 5 AND LOCAL REGULATIONS. 0
TEST HOLE DATE: November 5, 2014 8"
PERFORMED BY: Ron Cadillac, Soil Evaluator
WITNESSED BY: Amy Von Hone, RS, CHO
PERC RATE: <2'-00"/inch (Cl &C2 layers)
SOIL SURVEY(1993): Carver coarse sand 30"
PROP.TOP FOUND=20.5 GEOLOGIC MAP(1986): Harwich outwash plain deposits
2 Compartment Tank
Needed .f grinder invert 15.10 3 DRY WELLS (H-20)
Invert 15.85 1 Elector Pump used
Use Gas Baffle Use Gas Baffle Invert 14.33WITH TWO H-10 COVERS 64"
----------- Two H-10 COVERS P ro Proposed Posed Top Conc.=15.0
S=1 /4"/ft IteP Cloth=14.5
SLAB=15.3
1500 Gal. S-1/4" /ft Screened
-1_
S=1 /8"/ft F --6' Max /vent
THIS PLAN IS A VALID COPY ONLY IF IT BEARS
AN ORIGINAL RED STAMP AND SIGNATURE.
HEALTH AGENT APPROVAL
DATE
A layer 10yr 3/3
sandy loam
B layer 10yr 5/6
sandy loam
C1 layer 2.5y 6/4
'fine to med.
loamy sand
C2 layer 2.5y 6/
med. coarse sand
(trace fines)
no water
17.6
15.1
12.3
62
Invert 15.35 Septic Tank j/ 137
Proposed H-20 --- - -------
24
T TEST HOLE 2
Invert 14.50 Invert 14.17 12.17
6" Stone or compact Proposed , 9.6' 5.97' Bottom DEPTH (inches) ELEV,(feet)
P P Proposed i
A layer 10yr 3/3
sandy loam
B layer 10yr 5/6
sandy loam
C1 layer 2.5y 6/4
dine to med.
loamy sand
C2 layer 2.5y 6/6
med. coarse sand
(trace fines)
no water
17.7
15.4
12.4
( USE 4 DRY WELLS CENTERED IN 10' 137 6.3
DESIGN CAPACITY: 559.8 GPD X 50.5' X 2' LEACH AREA=552 GPD.
[(522.5 SF + 234 SF) X .74 GPD/SF]
SITE PLAN
FOR
DAVID & MELISSA PALMER
LOT 41 33 CREST CIRCLE, WEST YARMOUTH, MA
OCTOBER 1, 2015 SCALE: 1"=20'
RONALD J. CADILLAC, PLS, RS, P.C.
PROFESSIONAL LAND SURVEYOR & REGISTERED SANITARIAN
P.O. BOX 258
WEST YARMOUTH, MA 02673
(508) 775-9700
0)2015 BY R.J. CADILLAC PAGE 1 OF 1
N
15 i
D
25' -�
I---- 30 --i
i r-
1'-+
Bottom TH1=6.2
I
15'
8„
al
N
Estimated High Groundwater=2.5 NAVD88
DESIGNDATA
28"
BEDROOMS:
5
LEACH AREA
GARBAGE GRINDER:
No
USE
3 DRY -WELLS SET 7' APART 60"�
REQUIRED CAPACITY:
550 GPD
WITH
4' OF STONE ON THE ENDS
64"
SEPTIC TANK:
1500 GAL.
AND
APPROX.-3'-OF STONE ON THE
BOTTOM LEACHING AREA:
522.5 SF
SIDES, FOR A 47-6" LONG BY 11'
[(47.5' X 11'A
WIDE
BY 2' DEEP LEACH AREA.
SIDE LEACHING AREA:
234 SF
RESERVE
[2 11'+ 4_75') X 2' DEEP)]
A layer 10yr 3/3
sandy loam
B layer 10yr 5/6
sandy loam
C1 layer 2.5y 6/4
dine to med.
loamy sand
C2 layer 2.5y 6/6
med. coarse sand
(trace fines)
no water
17.7
15.4
12.4
( USE 4 DRY WELLS CENTERED IN 10' 137 6.3
DESIGN CAPACITY: 559.8 GPD X 50.5' X 2' LEACH AREA=552 GPD.
[(522.5 SF + 234 SF) X .74 GPD/SF]
SITE PLAN
FOR
DAVID & MELISSA PALMER
LOT 41 33 CREST CIRCLE, WEST YARMOUTH, MA
OCTOBER 1, 2015 SCALE: 1"=20'
RONALD J. CADILLAC, PLS, RS, P.C.
PROFESSIONAL LAND SURVEYOR & REGISTERED SANITARIAN
P.O. BOX 258
WEST YARMOUTH, MA 02673
(508) 775-9700
0)2015 BY R.J. CADILLAC PAGE 1 OF 1