HomeMy WebLinkAbout83-2052 - Site PlanLEGEN D
99-
EXISTING CONTOUR
X 991
EXIST. SPOT ELEV.
�--
LOT SIZE 40,000 SF*
& STAKED
PROPOSED CONTOUR
99
PROPOSED SPOT EL.
TH1
FRONT SETBACK 30'
ow SL
m
t o
TEST HOLE
2J
SLOPE OF GROUND
MIN.
UTILITY POLE
a
FIRE HYDRANT
NOTE: NOT ALL SYMBOLS MAY APPEAR IN DRAWING
■
*THE INSTALLER SHALL VERIFY THE
LOCATIONS OF ALL UTILITIES AND ALL
BUILDING SEWER OUTLETS AND
ELEVATIONS PRIOR TO INSTALLING ANY
PORTION OF SEPTIC SYSTEM
SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED
DESIGN FLOW: 3 BEDROOMS @ 110 GPD = 330 GPD
USE A 330 GPD DESIGN FLOW
SEPTIC TANK: 330 GPD (2) = 660
USE A 1500 GAL. SEPTIC TANK
LEACHING:
SIDES: N/A
BOTTOM 30 x 15 (.74) = 333 GPD
TOTAL: 450 S.F. 333 GPD
USE 4" PERF. PVC PIPE AND STONE LEACH FIELD
DIMENSIONS: 30' x 15' x 0.5 DEEP
SEE DETAIL
v
LEACH FIELD DETAIL 1
` 1._20. 1
1 3 11
J In
00
1
0
U 1
co
d Q 1
� 1
� 1
1
1
�1
\ /
r?
RUN POND
(TIDAL)
�u
1
13-314
4
4/
4L
`1J
4
LOT 1
17,765+/- SQ. FT.
0.41+ ACRES (U
APPROX.�O� A WETLAND
0. AC. OTAL
LOT 2
14966+/- SQ. FT.
0.34+/- ACRES
SYSTEM PROFILE
(NOT TO SCALE)
PROVIDE WATERTIGHT
ACCESS COVERS TO WITHIN 6" OF FIN. GRADE
PRECAST H-10
RISERS (TYP.)
40 PVC 24
85'* 10" u"
8.55' TEE 1500 GAL H-10 TEE
SEPTIC TANK
4' LIO. LEVEL
ACME OR EQUAL GAS &
(__L% % SLOPE)
FOUNDATION- 15' - SEPTIC TANK
FLOODZOtE DESIGN FO ND OF R DWELLIN AND A
NOTE: FJJ��`11AL GRADING BE IN CORDANCE WITH FE
NO BASEMENT AL ED. LE. VENTED CRAWLSPA E TO
GRA 1 SMAR ENT PER 200 SF CRAWLSPACE OC
STAKED SILT FENCE ALONG
SWALE
_rj4"0SCH40 PVC
PIPES LEVEL 1ST 2'
8.30' o 00000000000 0� 6" MIN. SUMP
0 0 0 0 0 0 0
LE .. o ppOOOppppppp pp
_ ° °p�p�pgoxo�p p.
8.15' " 7.98'
6" CRUSHED STONE OR MECHANICAL
COMPACTION. (15221 [2])
WATER TEST D'BOX FOR LEVELNESS
(--!-% SLOPE) (-l-% SLOPE)
- 15' D' BOX 5'
REQUIRED ( Y26 HERS)
)UIREMENT
3LA6 A R ABOVE OUTSIDE
H 12" OF GRADE 2 SIDES.
0
0
0
am
ALL SYSTEM COMPONENTS SHALL BE
MARKED WITH MAGNETIC TAPE OR
COMPARABLE MEANS FOR FUTURE LOCATION.
VENT WITH CHARCOAL FILTER
/1
2% SLOPE REQUIRED OVER SYSTEM 9.3'
PROVIDE INSPECTION PORT TO WITHIN " OF FINAL GRADE
2" DOUBLE -WASHED PEASTON 40 MIL LINER 5' MIN. OFF LEACHING, TOP AT
OR GEOTEXTILE FABRIC EL. 8.5, BOTTOM AT EL. 4.5
8.5'
o°o°°°o°o°o°°o°o°o°e°o°°°o°00°°0°ob0bo°oonou".000poaaooppop
7.95' °0°0000°0°000°0000000°o°0op°O°0o0op°poo°oo0°eo o p o 0 0 0 o 0
O
o_o_o o°°°°°o eo°o°00000 poop 00000 po
5' REMOVAL OF UNSUITABLE SOIL REQUIRED
AROUND PERIMETER OF LEACHING FACILITY,
DOWN TO SUITABLE SOIL LAYER. REPLACE
WITH CLEAN MED. SAND, TO MEET
SPECIFICATIONS OF 310 CMR 15.255(3)
PROVIDE APPROXIMATELY 88' OF 40 MIL
LINER TO BE PLACED ALONG REMOVAL LIMIT
TOP AT EL 6._6\BOTTOM AT EL. 4.5 ,
113•;
ogogogo o�ogogo %gSgo°g8gog S oag"o' °oSg%QooSg%goee 7.3'
4" PVC SET AT .005'/' SLOPE
)N 6" DOUBLE WASHED 3/4" - 1 1/2" STONE
6.0'
TIDALLY INFLUENCED GROUNDWATER ELEV. 1.3'
MONITORING WELL SET AND AUTOMATED READINGS
TAKEN OVER A FULL MOON CYCLE NOTES
(HIGHEST TIDES OF THE MONTH)
1 DATUM IS
LEACHING
FACILITY 2. MUNICIPAL WATER IS AVAILABLE
MONITORING WE)_L` SET 7/18, A
GROUNDWATER (READINGS WERE
3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT.
\/ 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS
TO BE AASHO H -1Q
5. PIPE JOINTS TO BE MADE WATERTIGHT.
�0))) 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH
310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO
BE USED FOR LOT LINE STAKING OR ANY OTHER
PURPOSE.
8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED
WITHOUT INSPECTION BY BOARD OF HEALTH AND
PERMISSION OBTAINED FROM BOARD OF HEALTH.
THE FULL 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING
DIGSAFE (1-888-344-7233) AND VERIFYING THE
LOCATION OF ALL UNDERGROUND & OVERHEAD UTILITIES
PRIOR TO COMMENCEMENT OF WORK.
11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE
REMOVED 5' BENEATH AND AROUND THE PROPOSED
LEACHING FACILITY.
12. WETLAND FLAGGED BY HAMLYN CONSULTING.
UTIL POLE - 13. ROOF RUN-OFF TO BE DIRECTED TO DRYWELLS,
OR TO DRIP TRENCHES
PROP. DW
MIN. TOP
ELEVATION
jSWALE l
[41
l
0
o '
PROP. WORK LIMIT
\
LINE OF SILT FENCE
LOT SIZE 40,000 SF*
& STAKED
{\
STRAWBALES �
_rj4"0SCH40 PVC
PIPES LEVEL 1ST 2'
8.30' o 00000000000 0� 6" MIN. SUMP
0 0 0 0 0 0 0
LE .. o ppOOOppppppp pp
_ ° °p�p�pgoxo�p p.
8.15' " 7.98'
6" CRUSHED STONE OR MECHANICAL
COMPACTION. (15221 [2])
WATER TEST D'BOX FOR LEVELNESS
(--!-% SLOPE) (-l-% SLOPE)
- 15' D' BOX 5'
REQUIRED ( Y26 HERS)
)UIREMENT
3LA6 A R ABOVE OUTSIDE
H 12" OF GRADE 2 SIDES.
0
0
0
am
ALL SYSTEM COMPONENTS SHALL BE
MARKED WITH MAGNETIC TAPE OR
COMPARABLE MEANS FOR FUTURE LOCATION.
VENT WITH CHARCOAL FILTER
/1
2% SLOPE REQUIRED OVER SYSTEM 9.3'
PROVIDE INSPECTION PORT TO WITHIN " OF FINAL GRADE
2" DOUBLE -WASHED PEASTON 40 MIL LINER 5' MIN. OFF LEACHING, TOP AT
OR GEOTEXTILE FABRIC EL. 8.5, BOTTOM AT EL. 4.5
8.5'
o°o°°°o°o°o°°o°o°o°e°o°°°o°00°°0°ob0bo°oonou".000poaaooppop
7.95' °0°0000°0°000°0000000°o°0op°O°0o0op°poo°oo0°eo o p o 0 0 0 o 0
O
o_o_o o°°°°°o eo°o°00000 poop 00000 po
5' REMOVAL OF UNSUITABLE SOIL REQUIRED
AROUND PERIMETER OF LEACHING FACILITY,
DOWN TO SUITABLE SOIL LAYER. REPLACE
WITH CLEAN MED. SAND, TO MEET
SPECIFICATIONS OF 310 CMR 15.255(3)
PROVIDE APPROXIMATELY 88' OF 40 MIL
LINER TO BE PLACED ALONG REMOVAL LIMIT
TOP AT EL 6._6\BOTTOM AT EL. 4.5 ,
113•;
ogogogo o�ogogo %gSgo°g8gog S oag"o' °oSg%QooSg%goee 7.3'
4" PVC SET AT .005'/' SLOPE
)N 6" DOUBLE WASHED 3/4" - 1 1/2" STONE
6.0'
TIDALLY INFLUENCED GROUNDWATER ELEV. 1.3'
MONITORING WELL SET AND AUTOMATED READINGS
TAKEN OVER A FULL MOON CYCLE NOTES
(HIGHEST TIDES OF THE MONTH)
1 DATUM IS
LEACHING
FACILITY 2. MUNICIPAL WATER IS AVAILABLE
MONITORING WE)_L` SET 7/18, A
GROUNDWATER (READINGS WERE
3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT.
\/ 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS
TO BE AASHO H -1Q
5. PIPE JOINTS TO BE MADE WATERTIGHT.
�0))) 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH
310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO
BE USED FOR LOT LINE STAKING OR ANY OTHER
PURPOSE.
8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED
WITHOUT INSPECTION BY BOARD OF HEALTH AND
PERMISSION OBTAINED FROM BOARD OF HEALTH.
THE FULL 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING
DIGSAFE (1-888-344-7233) AND VERIFYING THE
LOCATION OF ALL UNDERGROUND & OVERHEAD UTILITIES
PRIOR TO COMMENCEMENT OF WORK.
11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE
REMOVED 5' BENEATH AND AROUND THE PROPOSED
LEACHING FACILITY.
12. WETLAND FLAGGED BY HAMLYN CONSULTING.
UTIL POLE - 13. ROOF RUN-OFF TO BE DIRECTED TO DRYWELLS,
OR TO DRIP TRENCHES
PROP. DW
MIN. TOP
ELEVATION
jSWALE l
[41
l
0
o '
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 34 PARCEL 266
LOCUS IS WITHIN FEMA FLOOD ZONE AE(EL
12) AS SHOWN ON COMMUNITY PANEL
#25001CO589J DATED 7/16/2014 SITE IS IN
AN OPA, NO FED. FLOOD INSURANCE
AVAILABLE
WETLAND FLAGGED BY HAMLYN CONSULTING
ZONING SUMMARY
ZONING DISTRICT: RS -40
5 a
PROVIDED
MIN.
LOT SIZE 40,000 SF*
17,765 SF UPLAND
cA
d r
91.00'
MIN.
FRONT SETBACK 30'
ow SL
m
t o
MIN.
� c
20,2'
MIN.
REAR SETBACK 20'
a
*LOT
CREATED 12/1/65 (GRANDFATHERED)
o
IS NOT LOCATED WITHIN
0
a
Locus
a
5r
Nantucket
tin
Sound
5D
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 34 PARCEL 266
LOCUS IS WITHIN FEMA FLOOD ZONE AE(EL
12) AS SHOWN ON COMMUNITY PANEL
#25001CO589J DATED 7/16/2014 SITE IS IN
AN OPA, NO FED. FLOOD INSURANCE
AVAILABLE
WETLAND FLAGGED BY HAMLYN CONSULTING
ZONING SUMMARY
ZONING DISTRICT: RS -40
PROVIDED
MIN.
LOT SIZE 40,000 SF*
17,765 SF UPLAND
MIN.
LOT FRONTAGE 150'*
91.00'
MIN.
FRONT SETBACK 30'
67.5'
MIN.
SIDE SETBACK 20'(6'*)
20,2'
MIN.
REAR SETBACK 20'
268'
*LOT
CREATED 12/1/65 (GRANDFATHERED)
SITE
IS NOT LOCATED WITHIN
MESA/NHESP
MAPPING
TEST HOLE LOGS
ENGINEER: LISA LYONS, RS
WITNESS: SUSAN RASK, RS
DATE: 6/15/05
PERC. RATE _ < 2 MIN/INCH
CLASS I SOILS
PERCOLATION TESTING PERFORMED 8/31/05 BY RICK
JUDD, RS, AMY VON HONE, RS WITNESSING; RATE IS
< 2 MIN/INCH IN LS LAYER
CID1 11 I BENCHMARK - CTR. OF CATCH) I Q ELEV. 4 ELEV.
1 1 0" 4_8' 0" 4.7'
1 BASIN ELEV. = 5.06' (NAND 88
FILL
9„ A IVIS
A/E 18 1OYR 3/1
LS
1OYR 5/1
22 B
B
LS
I� 1I I SMALL LS 10YR 4/3
'LONG PROP LINE
AREA 10YR 4/3 40 1.36'
I� DRAIN 39" 1.55'
\8 skaz
SPEED LIMIT SIGN , j`tAOFA;, a��iNOFa.wss i C 40TRtS o C
vy a� I.
=V DANIEL A. cy o> DANIEL 4m� MS (EL. taa')
MS
I IVIOJA�L 0.%AL• 44" ob . wa er 1.13' 42" obs water
4 502 1 � o No. 40 80 I 1.2'
UTIL POLE
'rC
a�Te��;, E' a� tOYR 5/4
I t L -t6 `fFsS osuR 2.5Y 5/3
120" -5.2 120" -5.3
DATE DANIEL A. OJALA, P.E., P.L.S.
\ 1
� II
td
ff 508-362-4541
ax 508-362-9880
owncape.comdown cope eeering, inc.
civil engineers
land surveyors
939 Main Street ( Rte 6A)
YARMOUTHPORT MA 02675
TITLE 5 S7E PLAN
OF
-v 145 !7.3"ONLYTH T T
T Y
PREPARED FOR
VIN T JAMEESON
DATE: 12-28-2015
Scale: 1 "= 20'
0 10 20 30 40 50 FEET
13-314 JAMESON.C4JG