SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED
DESIGN FLOW: 3 BEDROOMS @ 110 GPD = 330 GPD
USE A 330 GPD DESIGN FLOW
SEPTIC TANK: 330 GPD (2) = 660
(1) 2500 GAL. H-20 SEPTIC TANK/PUMP CHAMBER
COMBINATION 1500/1000 OK
LEACHING:
330 GPD / (.74) = 446 SF REQUIRED
15' X 30' = 450 SF OK
450 SF X .74 = 333 GPD OK
USE A 15' X 30' LEACHING FIELD
PRESSURE DOSED WITH 2.0" LATERALS WITH
1/4" SHIELDED ORIFICES AT 5' O.C.
APPROVED DATE
*THE INSTALLER SHALL VERIFY THE
LOCATIONS OF ALL UTILITIES AND ALL
BUILDING SEWER OUTLETS AND
ELEVATIONS PRIOR TO INSTALLING ANY
PORTION OF SEPTIC SYSTEM
MA
BOARD OF HEALTH
BUOYANCY CALC:
2500 H-20 TANK WEIGHT: 28,560 LBS
11.83 x 6.33 x 3.3 x 62.4 = 15,420 UP (OK)
TEST HOLE LOGS
ENGINEER: DANIEL E. GONSALVES, SE #13587
WITNESS: AMY VON HONE, RS
DATE: 12/3/15
PERC. RATE _ < 2 MIN/INCH
CLASS I SOILS
4 ELEV.
1
0" 11.5'
mUNSUITABLE SOIL
G -W
ADJ. DATA:
WELL:
MIW 29
ZONE:
A
3"
10YR 2/2
11.3
COVERS TO
C1
MANUFACTURER'S SPECIFICATIONS FOR
=ea
MS
MIN.
18"
1OYR 5/8
10.0
Lewis
A
Lewis
ALARM AND CONTROL PANEL
/,LSA
Pond
20"
10YR 2/2
9.8
32
BUILDING. ALARM TO BE ON INV. IN 8.10'
5/8
24"
10YR 6/6
9.5
G1e0
C2
ZABEL FILTER
(A10o)
MS
46"
1OYR
7.7
FLOAT SWITCH ALARM ON OUTLET TEE W/EXTENSION
SETTINGS:
A3
48"
10YR 2/2
7.5
B3
1657 GAL.
THIS SIDE
60"
10YR 6/6
6.5'
VE
C3
MS
38"
1OYR 5/8
0.0'
mUNSUITABLE SOIL
G -W
ADJ. DATA:
WELL:
MIW 29
ZONE:
A
ADJ:
2.3'
GROUNDWATER ENCOUNTERED @ 138"
20
LEACHING FIELD :"
SYSTEM PROFILE
EL. 16.8' (NOT TO SCALE)
2a'm N-20 CAST IRON PROVIDE INSPECTION PORT TO GRADE q" VENT, PERF.
COVERS TO GRADE SEE DETAIL
INSULATE PIPE WHERE RUNS UNDER 2"
ABOVE GRADE 2% SLOPE REQUIRED OVER SYSTEM DRILL LAST HOLE IN EACH
LATERAL ON TOP TO VENT FEMALE ADAPTOR & THREADED PLUG
10.0'AIR WHILE LATERAL FILLS 2.0"0 THREADED END CONNECTION
MINIMUM .75' OF COVER OVER PRECAST 10.0'-11.0' SCH 40 PVC
2" SCH40 PRESSURE LINE 1/4' SHIELDED g 42'
ORIFICES 0.75" MIN.
00-0
°
8.68' -20 C8 ° DO °08 ° o
2500 GAL H-20
10" SEPTIC TANK/ T 9.0 2" INVERTS LEVEL AT 8.2
8.10' TEE PUMP CHAMBER BOTTOM LEACHING LEVEL AT EL. 7.75
COMBINATION 2" CENTRAL FED MANIFOLD
PITCH TO DRAIN BACK TO CONNECT ENDS
SEE DETAIL BELOW PUMP CHAMBER- NO LOW SPOTS. 5.45'
3/4" TO 1 1/2" DOUBLE WASHED STONE s
eoo'000000'00000W
0 0 0 0 0 0 0 0°0°0°0°0 0 0°o°0
0 Doan 000°00°o o°Doo°00000000°00000 opo
6" CRUSHED STONE OR MECHANICAL o
COMPACTION. (15.221 [21) N
(2_5 R SLOPE) (--!--% SLOPE)
USE ADJUSTED
FOUNDATION- 23' SEPTIC TANK/ 5, LEACHING GRINFLUENCED)
23
PUMP CHAMBER FACILITY
MANHOLE COVER
MORTAR ALL COMPONENTS (TYP.)
24" I.D. PRECAST CONC. RISER AS REQ.
4'0 PRECAST DONUT 1" OVER FIELD
�4" THICK 4000 PSI CONC. W/WWF
18"0 OBSERVATION HOLE IN CTR.
LEACHING DETAIL
1 " = 10'
\_12" PERF. HDPE
PUMP OUT WELL
TO SAND AT BOTTOM L.F.
INSPECTION PORT DETAIL
/ CUT AND PATCH
NOT TO SCALE PAVEMENT AS
BENCHMARK: / / / REQUIRED
MAG NAIL ELEV.
= 9.7 NAVD88 t�A EL
ZjNEg SGG �0f
P0000
MIRAFI 140N NONWOVEN FILTER FABRIC 0080 ° 2.0„ 'o - PAl�EO DRI
OVER WASHED STONE INSPECTION PORT
2.0" LATERAL WITH BOTTOM OF STONE ELEVATION LISTED
ORIFICES & SHIELDS 3/O^RC1. _D
WASHED STONE
COMPACTED CLEAN MEDIUM SAND Fl5' REMOVAL OF UNSUITABLE SOIL REQUIRED
FILL ONLY. AROUND PERIMETER OF LEACHING FACILITY, �'�,,:•:
DOWN TO SUITABLE SOIL LAYER. REPLACE
CROSS SECTION LEACHING FIELD WI�� 'lEO
TH CLEAN MED. SAND, TO MEET �0� THi IDRIVE
IPAUNDER
N.T.S. SPECIFICATIONS OF 310 CMR 15.255(3)
^a m IPA £L.10.0'
° 1727E EL. 16.6'
2.0"0 SCH-40 PVC LATERAL PROP. VENT WITH CHARCOAL
ORIFICE SHIELD OS200 FILTER AND BUGSCREEN (FINAL -'z b ExrsT75 wELL. i
ORENCO SYSTEMS INC
PH. 1-800-348-9843 PLACEMENT BY CONTRACTOR 13 /
'
OR EQUAL WITH HOMEOWNER CONSULTATION)
24 REQ.
EKISTING6 G PECK
1/4"0 HOLE AT 5' O.C. SNAP-ON p LLIN
✓J % .� CX1(RIEN Bp1l.p)
EXACT DIAMETER HOLES SHIELD X17
SHOULD BE SHOP DRILLED WITH
A DRILL PRESS TO ENSURE
UNIFORMITY. PPEBURRS D DRAINAGE SLOTS
PRIOR O PLACING 1 0 \ ' \
ORIFICE SHIELD DETAIL
NOT TO SCALE
0
25 50 75 100
CAPACITY - GPM
PUMP CURVE FOR MYERS SRM4 4/10 HP PUMP
BICE #15-015
ACCESS FOR ROUTINE MAINTENANCE
DISTRICT
MIN.
MUST BE PROVIDED FOR ZABEL FILTER.
24"0 H-20
CAST IRON
INSTALLER MUST FOLLOW ALL
� <
MIN.
COVERS TO
GRADE
MANUFACTURER'S SPECIFICATIONS FOR
=ea
m1
MIN.
830 GAL RESERVE
PROPER FILTER INSTALLATION
MAX.
Lewis
°'
Lewis
ALARM AND CONTROL PANEL
25%
Pond
TO BE INSTALLED INSIDE
WITHIN A ZONE II
BUILDING. ALARM TO BE ON INV. IN 8.10'
Locus
RpDd
SIOnd
SEPARATE CIRCUIT FROM PUMP
G1e0
2" PRESSURE LINE
ZABEL FILTER
(A10o)
19" TEE
SLOPE TO DRAIN BACK
FLOAT SWITCH ALARM ON OUTLET TEE W/EXTENSION
SETTINGS:
WEEP HOLE
PUMP ON
1657 GAL.
THIS SIDE
CHECK VALVE
5" WORKING RANGE
6
OF BAFFLE
MYERS SRM 4
5
6g'
SUBMERSIBLE 4/10 HP PUMP
PUMP OFF
12"
SYSTEM (OR EQUAL)
(ON BLOCK)
4 DOSES PER DAY, AT 110 GAL. PER o 0
00 �0000 0
0000
DOSE (5" WORKING RANGE)
6" BAFFLE
H-20
2500 GAL. SEPTIC TANK/PUMP
CHAMBER COMBINATION
(NOT TO SCALE)
APPROX.
7ED
THY LUNDS7ROM
LINE/SIL
PRPP. SECOND
L W17N/N
TING
FOOTPRINT A
COASTAL DUNE/)
111 PROP AIk
LOT 7
1 9,675 '
11 Dt
11 AGE of
COASTAL BEACH
NOTES
1. DATUM IS NAVD 88
2. MUNICIPAL WATER IS EXISTING
3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT.
4. DESIGN LOADING FOR ALL PROPOSED PRECAST
UNITS TO BE AASHO H-20
5. PIPE JOINTS TO BE MADE WATERTIGHT.
S. CONSTRUCTION DETAILS TO BE IN ACCORDANCE
WITH 310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND
NOT TO BE USED FOR LOT LINE STAKING OR ANY
O'HER PURPOSE.
S. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR
CONCEALED WITHOUT INSPECTION BY BOARD OF
HEALTH AND PERMISSION OBTAINED FROM BOARD
OF HEALTH.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR
C4LLING DIGSAFE (1-888-344-7233) AND
WRIFYING THE LOCATION OF ALL UNDERGROUND &
OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF
WORK,
11. ANY UNSUITABLE MATERIAL ENCOUNTERED
SHALL BE REMOVED 5' BENEATH AND AROUND THE
PROPOSED LEACHING FACILITY.
12. EXISTING LEACHING FACILITY SHALL BE PUMPED
AND REMOVED.
13. ACCESS FOR ROUTINE MAINTENANCE MUST BE
PROVIDED FOR ZABEL FILTER. INSTALLER MUST
FOLLOW MANUFACTURER'S SEPCIFICATIONS FOR
PROPER FILTER INSTALLATION.
14. INSTALLER TO VERIFY THE ELECTRICAL SYSTEM
IS SUITABLE FOR PUMP CONNECTION. ELECTRICAL
PERMIT REQUIRED.
15. ROOF RUN-OFF TO BE DIRECTED TO DRYWELLS,
OR ROOF DRIPLINES TO STONE TRENCHES
EXIST. DWELL.
#19
�F ELAINE GAMBRAZ /0
�sATf, BRAZ/O POWERS
LANE 7RUS
O
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 14 PARCEL 68
LOCUS IS WITHIN FEMA FLOOD ZONE VE (EL 14)
& VE (EL 13) AS SHOWN ON COMMUNITY
PANEL#25001CO588J DATED 7/16/2014
ZONING SUMMARY
ZONING DISTRICT. R25
DISTRICT
MIN.
5
25,000 S.F.
MIN.
j
� <
MIN.
�e S
e Ol
�c/QI qC ale s
MIN,
=ea
m1
MIN.
REAR SETBACK
0
e�
h
MAX.
Lewis
°'
Lewis
Bay
25%
Pond
IS NOT LOCATED
WITHIN A ZONE II
Powers
Locus
RpDd
SIOnd
Nantucket
G1e0
Sound
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 14 PARCEL 68
LOCUS IS WITHIN FEMA FLOOD ZONE VE (EL 14)
& VE (EL 13) AS SHOWN ON COMMUNITY
PANEL#25001CO588J DATED 7/16/2014
ZONING SUMMARY
ZONING DISTRICT. R25
DISTRICT
MIN.
LOT SIZE
25,000 S.F.
MIN.
LOT FRONTAGE
150'
MIN.
FRONT SETBACK
30'
MIN,
SIDE SETBACK
15'
MIN.
REAR SETBACK
20'
MAX.
BUILDING HEIGHT
XX'
MAX.
BUILDING COV.
25%
SITE
IS NOT LOCATED
WITHIN A ZONE II
OWNER OF RECORD
BEVERLY A. BRUNO
83 CIDER MILL ROAD
HAWTHORNE, NJ 07506-3042
REFERENCES
CTF 166758
LCP 117818 LOT 7
VERTICAL DATUM: NAVD '88
TffLE II ;Ilu SITE P,II I u.11 N
OF
15 �: 1t91k,Io Il
WES3 h,,9 111
is h MA
PREPARED FOR
R
DATE: JULY 26, 2 6
�Y
Scale: 1"= 20'
0 10 20 30 40\ 50 FEET
7-4•I(,
DATE
OANIELA.
OJALA
CIVIL
NO 46502
DANIEL A. OJALA, P.E., P.L.S.
I off 508-362-4541
fox 508-362-9880
downcape.com
down cope engineering, idc.
Civil engineers
land surveyors
939 Main Street ( Rte 6A)
YARMOUTHPORT MA 02675