SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED
DESIGN FLOW: 3 BEDROOMS @ 110 GPD = 330 GPD
USE A 330 GPD DESIGN FLOW
SEPTIC TANK: 330 GPD (2) = 660
(1) 2500 GAL. COMBINATION-201500/IC TANK/PUMP CHAMBER
LEACHING:
330 GPD / (.74) = 446 SF REQUIRED
15'X30'= 450 SF OK
450 SF X .74 = 333 GPD OK
USE A 15' X 30' LEACHING FIELD
PRESSURE DOSED WITH 2.0" LATERALS WITH
1/4" SHIELDED ORIFICES AT 5' O.C.
*THE INSTALLER SHALL VERIFY THE
LOCATIONS OF ALL UTILITIES AND ALL
BUILDING SEWER OUTLETS AND
ELEVATIONS PRIOR TO INSTALLING ANY
PORTION OF SEPTIC SYSTEM
MA
APPROVED DATE BOARD OF HEALTH
BUOYANCY CALC:
2500 H-20 TANK WEIGHT: 28,560 LBS
11.83 x 6.33 x 3.3 x 62.4 = 15,420 UP (OK)
TEST HOLE
LOGS
ENGINEER: DANIEL
E. GONSALVES,
SE #13587
WITNESS: AMY VON
HONE,
RS
DATE: 12/3/15
FRONT SETBACK
MANUFACTURER'S SPECIFICATIONS FOR
o
y
PERC. RATE _ <
2 MIN/INCH
PROPER FILTER INSTALLATION
2" SCH40 PRESSURE LINE
CLASS I SOILS
MAX.
,
1/4" SHIELDED 8 42' ORIFICES 0.75" MIN.
1
4
ELEV.
Powers
Od
LOCUS
d Ro
Nantucket
Gteo
Sound
� 0� o
� D o
/LS
BUILDING. ALARM TO BE ON INV. IN 8.10'
38'
3-
3"
10YR 2/2
11.3'
C,
SEPARATE CIRCUIT FROM PUMP
2" PRESSURE LINE
2500 GAL H-20
18"
1OYR 5/8
10.0'
LEVEL AT 8.2
A
FLOAT SWITCH ALARM ON OUTLET TEE W/EXTENSION
10" SEPTIC TANK/
/,LS
20"
10YR 2/2
9.8'
1657 GAL.
B
BOTTOM
LSA
EL. 7.75
24"
1OYR 6/6
9.5'
C2
MS
5" WORKING RANGE
UNSUITABLE SOIL
46"
1OYR 5/8
7.7'
A
CONNECT ENDS
5
/,LS/
SEE DETAIL BELOW
-
48
10YR 2/2
7.5'
a
B3
SYSTEM (OR EQUAL)
/ LS/
60"
10YR 6/6
6.5'
G -W ADJ. DATA:
DOSE (5" WORKING RANGE)
C3
C3
000
000
WELL: MIW 29
SIEVE
6" BAFFLE
ZONE: A
138MS
"
10YR 5/8
0.0'
ADJ: 2.3'
GROUNDWATER ENCOUNTERED @ 138"
20
EL. 16.8' 24"0 H-20 CAST IRON
INSULATE PIPE WHERE COVERS TO GRADE
ABOVE GRADE
SYSTEM PROFILE
(NOT TO SCALE) PROVIDE INSPECTION PORT TO GRADE
SEE DETAIL 4" VENT, PERF.
RUNS UNDER 2"
2% SLOPE REQUIRED OVER SYSTEM DRILL LAST HOLE IN EACH
LATERAL ON TOP TO VENT FEMALE ADAPTOR & THREADED PLUG
AIR (WHILE LATERAL FILLS 2.0"0 THREADED END CONNECTION
OF COVER OVER PRECAST SCH 40 PVC
MANHOLE COVER
MORTAR ALL COMPONENTS (TYP.)
// 24" I.D. PRECAST CONC. RISER AS REQ.
/4;0 PRECAST DONUT 1" OVER FIELD
J 4' THICK 4000 PSI CONC. W/WWF
18"0 OBSERVATION HOLE IN CTR.
LEACHING FIELD
\-12" PERF. HDPE
PUMP OUT WELL
TO SAND AT BOTTOM L.F.
INSPECTION PORT DETAIL
NOT TO SCALE
MIRAF1140N NONWOVEN FILTER FAE
OVER WASHED STONE
2.0" LATERAL WITH
BOTTOM OF STONE ELEVATION LISTED
ORIFICES & SHIELDS \3/4" TO 1-1/2" DOUBLE _
WASHED STONE
COMPACTED CLEAN MEDIUM SAND FILL ONLY.
CROSS SECTION LEACHING FIELD
2.0"0
I/4"0 HOLE AT 5' O.C. SNAP-ON
EXACT DIAMETER HOLES SHIELD
SHOULD BE SHOP DRILLED WITH
A DRILL PRESS TO ENSURE
UNIFORMITY. REMOVE BURRS D DRAINAGE SLOTS
PRIOR TO PLACING PIPE.
2.7'
ORIFICE SHIELD OS200
ORENCO SYSTEMS INC
PH. 1-800-348-9843
OR EQUAL.
24 REQ.
ORIFICE SHIELD DETAIL
NOT TO SCALE
0
25 50 75 100
CAPACITY -GPM
PUMP CURVE FOR MYERS SRM4 4/10 HP PUMP
DCE #15-015
BENCHMARK:
MAG NAIL ELEV.
= 9.7 NAVD88
LEACHING DETAIL
1" - 10'
CUT AND PATCH
PAVEMENT AS
/ REQUIRED
/
/
ZONE/ >, -VE ((EL 13)
ZONE
HERS 1. ,�4
PAVED ORl
INSPECTION PORT
5' REMOVAL OF UNSUITABLE SOIL REQUIRED
AROUND PERIMETER OF LEACHING FACILITY, ick
DOWN TO SUITABLE SOIL LAYER. REPLACE =_
WITH CLEAN MED. SAND, TO MEET
SPECIFICATIONS OF 310 CMR 15.255(3)
PROP. VENT WITH CHARCOAL
FILTER AND BUGSCREEN (FINAL�,�7
PLACEMENT BY CONTRACTOR
WITH HOMEOWNER CONSULTATION)
ACCESS FOR ROUTINE MAINTENANCE
24"0 H-20
CAST IRON
MUST BE PROVIDED FOR ZABEL FILTER.
COVERS TO
GRADE
INSTALLER MUST FOLLOW ALL
10.0 -11.0
MIN.
FRONT SETBACK
MANUFACTURER'S SPECIFICATIONS FOR
o
y
Lewis
830 GAL RESERVE
PROPER FILTER INSTALLATION
2" SCH40 PRESSURE LINE
Bay
MAX.
,
1/4" SHIELDED 8 42' ORIFICES 0.75" MIN.
�'odia
MAX.
Powers
Od
LOCUS
d Ro
Nantucket
Gteo
Sound
� 0� o
� D o
BUILDING. ALARM TO BE ON INV. IN 8.10'
38'
SEPARATE CIRCUIT FROM PUMP
2" PRESSURE LINE
2500 GAL H-20
19" TEE
2" INVERTS
LEVEL AT 8.2
SLOPE TO DRAIN BACK
FLOAT SWITCH ALARM ON OUTLET TEE W/EXTENSION
10" SEPTIC TANK/
WEEP HOLE
SETTINGS:
1657 GAL.
TEE PUMP CHAMBER
BOTTOM
LEACHING LEVEL AT
EL. 7.75
THIS SIDE
COMBINATION
2" CENTRAL FED MANIFOLD
5" WORKING RANGE
6
OF BAFFLE
PITCH TO DRAIN BACK TO
CONNECT ENDS
5
6.8'
SEE DETAIL BELOW
-
PUMP CHAMBER- NO LOW SPOTS.
PUMP OFF
5.45,
a
SYSTEM (OR EQUAL)
00
(ON BLOCK)
C
4 DOSES PER DAY, AT 110 GAL. PER 000000 0000 00
3/4" TO 1 1/2" DOUBLE WASHED STONE
DOSE (5" WORKING RANGE)
000
000
00 0000 000 0
0 o0 00 0oa o0oo00 00n
o
6" BAFFLE
W(r
no,00
PnD n.o o
2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION
6" CRUSHED STONE OR MECHANICAL
(NOT TO SCALE)
-'
COMPACTION. (15.221 [21)
N
(2_5 % SLOPE) (--L-% SLOPE)
USE ADJUSTED
SEPTIC TANK/
LEACHING
GROUNDWATER 0 EL.
2.3
FOUNDATION- 23' 5.
(TIDALLY INFLUENCED)
PUMP CHAMBER
FACILITY
MANHOLE COVER
MORTAR ALL COMPONENTS (TYP.)
// 24" I.D. PRECAST CONC. RISER AS REQ.
/4;0 PRECAST DONUT 1" OVER FIELD
J 4' THICK 4000 PSI CONC. W/WWF
18"0 OBSERVATION HOLE IN CTR.
LEACHING FIELD
\-12" PERF. HDPE
PUMP OUT WELL
TO SAND AT BOTTOM L.F.
INSPECTION PORT DETAIL
NOT TO SCALE
MIRAF1140N NONWOVEN FILTER FAE
OVER WASHED STONE
2.0" LATERAL WITH
BOTTOM OF STONE ELEVATION LISTED
ORIFICES & SHIELDS \3/4" TO 1-1/2" DOUBLE _
WASHED STONE
COMPACTED CLEAN MEDIUM SAND FILL ONLY.
CROSS SECTION LEACHING FIELD
2.0"0
I/4"0 HOLE AT 5' O.C. SNAP-ON
EXACT DIAMETER HOLES SHIELD
SHOULD BE SHOP DRILLED WITH
A DRILL PRESS TO ENSURE
UNIFORMITY. REMOVE BURRS D DRAINAGE SLOTS
PRIOR TO PLACING PIPE.
2.7'
ORIFICE SHIELD OS200
ORENCO SYSTEMS INC
PH. 1-800-348-9843
OR EQUAL.
24 REQ.
ORIFICE SHIELD DETAIL
NOT TO SCALE
0
25 50 75 100
CAPACITY -GPM
PUMP CURVE FOR MYERS SRM4 4/10 HP PUMP
DCE #15-015
BENCHMARK:
MAG NAIL ELEV.
= 9.7 NAVD88
LEACHING DETAIL
1" - 10'
CUT AND PATCH
PAVEMENT AS
/ REQUIRED
/
/
ZONE/ >, -VE ((EL 13)
ZONE
HERS 1. ,�4
PAVED ORl
INSPECTION PORT
5' REMOVAL OF UNSUITABLE SOIL REQUIRED
AROUND PERIMETER OF LEACHING FACILITY, ick
DOWN TO SUITABLE SOIL LAYER. REPLACE =_
WITH CLEAN MED. SAND, TO MEET
SPECIFICATIONS OF 310 CMR 15.255(3)
PROP. VENT WITH CHARCOAL
FILTER AND BUGSCREEN (FINAL�,�7
PLACEMENT BY CONTRACTOR
WITH HOMEOWNER CONSULTATION)
ACCESS FOR ROUTINE MAINTENANCE
24"0 H-20
CAST IRON
MUST BE PROVIDED FOR ZABEL FILTER.
COVERS TO
GRADE
INSTALLER MUST FOLLOW ALL
150'
MIN.
FRONT SETBACK
MANUFACTURER'S SPECIFICATIONS FOR
o
y
Lewis
830 GAL RESERVE
PROPER FILTER INSTALLATION
pond
Bay
MAX.
ALARM AND CONTROL PANEL
TO BE INSTALLED INSIDE
�'odia
MAX.
Powers
Od
LOCUS
d Ro
Nantucket
Gteo
Sound
BUILDING. ALARM TO BE ON INV. IN 8.10'
SEPARATE CIRCUIT FROM PUMP
2" PRESSURE LINE
ZABEL FILTER
(A100)
19" TEE
SLOPE TO DRAIN BACK
FLOAT SWITCH ALARM ON OUTLET TEE W/EXTENSION
WEEP HOLE
SETTINGS:
1657 GAL.
PUMP ON
THIS SIDE
CHECK VALVE
5" WORKING RANGE
6
OF BAFFLE
MYERS SRM 4
5
6.8'
SUBMERSIBLE 4/10 HP PUMP
PUMP OFF
12"
SYSTEM (OR EQUAL)
00
(ON BLOCK)
C
4 DOSES PER DAY, AT 110 GAL. PER 000000 0000 00
0000
DOSE (5" WORKING RANGE)
6" BAFFLE
H-20
2500 GAL. SEPTIC TANK/PUMP CHAMBER COMBINATION
(NOT TO SCALE)
0WELLING
D #7
i
m IPAV£D DR/l�E
I UNDER
J o
IPA VE. EL.10.0'
IITOF £L. 16.8'
I
12 \� EX/ST. DWELL.
3 r /
APPROX. LIMIT OF
PRIORITY �VVATED
H 1TA
r -✓_OA! KATHY LUNDSTROM
J
L-7-i0`T F
9,6751 SF 1i
a
COASTAL BEACH
L/N£/SILT, f£N
SECOND
.fZ60R WITHIN
EVS77NG
F007PRIIVT A
/WALL
Q
AL DUNE
NOTES
2. MUNICIPAL WATER IS EXISTING
3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT
4. DESIGN LOADING FOR ALL PROPOSED PRECAST
UNITS TO BE AASHO H -2Q
5. PIPE JOINTS TO BE MADE WATERTIGHT.
6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE
WITH 310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND
NOT TO BE USED FOR LOT LINE STAKING OR ANY
OTHER PURPOSE.
8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR
CONCEALED WITHOUT INSPECTION BY BOARD OF
HEALTH AND PERMISSION OBTAINED FROM BOARD
OF HEALTH.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR
CALLING DIGSAFE (1-888-344-7233) AND
VERIFYING THE LOCATION OF ALL UNDERGROUND &
OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF
WORK.
11. ANY UNSUITABLE MATERIAL ENCOUNTERED
SHALL BE REMOVED 5' BENEATH AND AROUND THE
PROPOSED LEACHING FACILITY.
12. EXISTING LEACHING FACILITY SHALL BE PUMPED
AND REMOVED.
13. ACCESS FOR ROUTINE MAINTENANCE MUST BE
PROVIDED FOR ZABEL FILTER. INSTALLER MUST
FOLLOW MANUFACTURER'S SEPCIFICATIONS FOR
PROPER FILTER INSTALLATION.
14. INSTALLER TO VERIFY THE ELECTRICAL SYSTEM
IS SUITABLE FOR PUMP CONNECTION. ELECTRICAL
PERMIT REQUIRED.
15. ROOF RUN-OFF TO BE DIRECTED TO DRYWELLS,
OR ROOF DRIPLINES TO STONE TRENCHES
EXIST. DWELL.
els
A £ 2
7R
/GAMBPPOWERS
R�
�i
l�
7
XIS7INL 2; PATH TO
I COASTAL B£
PR/
Lewis 2' W. ��
N10N `n
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 14 PARCEL 68
LOCUS IS WITHIN FEMA FLOOD ZONE VE (EL 14)
& VE (EL 13) AS SHOWN ON COMMUNITY
PANEL#25001CO588J DATED 7/16/2014
ZONING SUMMARY
ZONING DISTRICT: R25
DISTRICT
MIN.
LOT SIZE
25,000 S.F.
MIN.
�3
�
150'
MIN.
FRONT SETBACK
30'
o
y
Lewis
5 n
Lewis
MIN.
pond
Bay
MAX.
BUILDING HEIGHT
�'odia
MAX.
Powers
Od
LOCUS
d Ro
Nantucket
Gteo
Sound
LOCUS MAP
NOT TO SCALE
ASSESSORS MAP 14 PARCEL 68
LOCUS IS WITHIN FEMA FLOOD ZONE VE (EL 14)
& VE (EL 13) AS SHOWN ON COMMUNITY
PANEL#25001CO588J DATED 7/16/2014
ZONING SUMMARY
ZONING DISTRICT: R25
DISTRICT
MIN.
LOT SIZE
25,000 S.F.
MIN.
LOT FRONTAGE
150'
MIN.
FRONT SETBACK
30'
MIN.
SIDE SETBACK
15'
MIN.
REAR SETBACK
20'
MAX.
BUILDING HEIGHT
XX'
MAX.
BUILDING COV.
25%
SITE
IS NOT LOCATED
WITHIN A ZONE It
OWNER OF RECORD
BEVERLY A. BRUNO
83 CIDER MILL ROAD
HAWTHORNE, NJ 07506-3042
REFERENCES
CTF 166758
LCP 11781B LOT 7
VERTICAL DATUM: NAVD '88
v.,_
I T
12 R
L;I
kkSinn 211 c /\ )
OF
LtlJ/LTIJYR/ 15 POWERS LANE
-- WEST YARMOUTH.
ARM®UTH. A
PREPARED FOR
>• .o m LN
11111111 I f i ii
DATE: JULY 26, 2016
REV. 9/28/16 (ADD'L DETAIL, MOVE STAIRS)
Scale: 1"= 20'
0 10 20 30 40 50 FEET
DANIEL��,
q. DANIEL A.
ojA%L/ m o OJALA
No. 096o " CIVIL
Na. 46502
-Z �3 -1(,�
DATE DANIEL A. OJALA, P.E., P.L.S.
off 508-362-4541
fax 508-362-9880
downcope.com
down cope engineering, h7C.
civil engineers
land surveyors
939 Main Street ( Rte 6A)
YARMOUTHPORT MA 02675
15-015