Loading...
HomeMy WebLinkAboutDOA - 10 Whale Rd - Site PlanSYSTEM DESIGN: GARBAGE DISPOSER IS NOT ALLOWED DESIGN FLOW: 5 BEDROOMS ® 110 GPD = 550 GPD USE A 550 GPD DESIGN FLOW SEPTIC TANK: 550 GPD (2) = 1100 USE AN H-10 2500 ST/PC COMBINATION (SEE DETAIL) LEACHING: BOTTOM AREA ONLY: 748 SF X (74) = 553.5 GPD USE A 748 SF LEACHING FIELD AS SHOWN APPROVED MA DATE BOARD OF HEALTH ALL SYSTEM COMPONENTS SHALL BE MARKED - SEPTIC SYSTEM PROFILE WITH MAGNETIC TAPE COMPARABLE MEANS *THE INSTALLER SHALL VERIFY THE FOR FUTURE LOCATION.. MARK CORNERS of LOCATIONS OF ALL UTILITIES AND ALL LEACH FIELD WITH 24" #5 REBAR WITH SAFETY BUILDING SEWER OUTLETS AND (NTS) CAP DRIVEN JUST BELOW GRADE EACH CORNER OF LEACH FIELD. ELEVATIONS PRIOR TO INSTALLING ANY PORTION OF SEPTIC SYSTEM 4" DIA PERF. INSP. PORT TO SAND AT BOTTOM OF PROVIDE MIN. 20' DIAM. WATERTIGHT 40 MIL LINER FROM ELEV. 8.8' TO ELEV. 4.8' MIN. FIRST FLOOR BLDG ELEV. 12.0' CONCRETE ACCESS COVERS TO WITHIN 6" OF FIN. GRADE LEACHING FIELD. 4" THREADED CAP TO WITHIN 3" OF FINISH GRADE RETAINING WALL SCHE ATIC SHOWN, EXACT FASCADE RAWLSPACE SLAB 6' TOP FOUNDATION 11.0' AND CONSTRUCTION B OTHERS. TOP OF WALL HT. AS NOTED WITHIN 20' OF SASI 9.3' MIN. TOP PIPE 8.6' REMAINDER OF CRAWLSPACE .75' OF COVER OVER PRECAST 10,0 FINISHED GRADE- 4" LOAM & SEED 2% MIN. SLOPE OVER SYSTEM SLAB AT EL. 7.4' PRECAST H-10 PROP. TEE / { �,;�.•.; �. RISERS (TYP.) TOP RET. WALL ELEV. 8.8' FLOOD VENTS WITHIN 12" GRADE SO CAP 2'• PIPES PVC R 7c CLEAN FILL PIPES LEVEL 1ST 2' n� CAP ENDS (GROUND AT EL. 7.4) REQ. 4 ER o o Pvc, s=o.00s a A 0. ' 2500 GAL H-10 g; ^•' ' SEPTIC TANK/PC a l VENTS ON 2 SIDES REQ. ` 7.2' COMBINATION 3/4"-1-1/2" DOUBLE WASHED STONE LEACHING FIELD o 6"DEPTH i MIN BELOW INV. , < a, O FLOOD VENT/FOUNDATION DESIGN S eoee0000000e ga o a PROPOSED ROCK WALL VENEER BY OTHERS. SHOREY OR EQUAL " "- 8.25' LEVEL BOTTOM o 8.00 TEST HOLE LOGS ENGINEER: ARNE H. OJALA PE, PLS SE1804 WITNESS: PHIL RENAUD DATE: 2/10/2010 PERC. RATE < 22 MIN/INCH CLASS I SOILS ELEV. ELEV. 4 FI LL 28" 4.5' A LS 32" 10YR 2/1 4.1' E FS 36" 1OYR .6/1 3.8' FILL 36" 4.3' A LS 38" 1OYR 2/1 4.1' E FS 40" 1OYR 6/1 4.0' B LS B LS 50" 1OYR 5/6 2.6' 66" 1OYR 5/6 C1 C1 PERC MCS MCS BOTT. AT 1 OYR 6/6 1 OYR 6/6 60" 60" V EL. 1.8' 114" DICE #10-006 V EL. 1.8' -2.2' 7.5'* (SEE DETAIL) 8.52 5' MIN.UNSUITABLE <: • BLOCK UP FOR 24" COVER TYP. SOIL REMOVAL O O O O O O O O O O O C D -BOX ACME DB -9 OR EQ. 7.50' 0 0 0 0 0 0 0 0 0 0 0 WHERE SPECIFIED ' 000 O O O O O O O O O C O�O�O�O�O�O�O�O�O�O�O�O� DEPTH PER SOIL LOGS '• 5'D, 6" CRUSHED STONE OR MECHANICAL oo°000000°oa f - COMPACTION. (15.221 [21) WATER TEST O'BOX FOR LEVELNESS USE TIDALLY INFLUENCED ADJ. GROUNDWATER _ ELEV. 2.5' LEACHING: USE A 748 SF LEACHING FIELD 748 SF X .74 = 553 GPD O.K. (2-+% SLOPE) 10' - ST/PC 40' D' BOX _ LEACHING ACCESS FOR ROUTINE MAINTENANCE FOUNDATION FACILITY MUST BE PROVIDED FOR ZABEL FILTER. INSTALLER MUST FOLLOW ALL MANUFACTURER'S SPECIFICATIONS FOR PROPER FILTER INSTALLATION 1 \ EXIST;NG DWE.-LiNG FLOOD --VENT (TYP,- . i AND CONTROL PANEL ALARM A BUOYANCY CALCS: TO BE INSTALLED INSIDE 2500 H-10 TANK WGT: 22560 LBS NOTES LOT SIZE SEPARATE CIRCUIT FROM PUMP 0.6' x 11.8' x 6.3 x 62.4 = 2753 1. DATUM IS NGVD29 UP (OK) 2. MUNICIPAL WATER IS EXISTING 130' 3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT. 1500 GAL NI 4. DESIGN LOADING FOR ALL PROPOSED PRECAST UNITS . THIS SIDE TO BE AASHO H -1Q OF BAFFLE 5. PIPE JOINTS TO BE MADE WATERTIGHT. 8.5' 6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE WITH REAR SETBACK 310 CMR 15.000 (TITLE 5.) DOSE (5" WORKING RANGE) 7. THIS PLAN IS FOR PROPOSED WORK ONLY AND NOT TO LOT COVERAGE BE USED FOR LOT LINE STAKING OR ANY OTHER 2500 GAL. SEPTIC PURPOSE. IS LOCATED NOT WITHIN MASS 8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC. ZONE II. 9. COMPONENTS NOT TO BE BACKFILLED OR CONCEALED WITHOUT INSPECTION BY BOARD OF HEALTH AND RECORD PERMISSION OBTAINED FROM BOARD OF HEALTH. 10. CONTRACTOR SHALL BE RESPONSIBLE FOR CALLING DIGSAFE (1-888-344-7233) AND VERIFYING THE LOCATION OF ALL UNDERGROUND & OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK. 11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL BE REMOVED 5' BENEATH AND AROUND THE PROPOSED LEACHING FACILITY. 12. EXISTING SEPTIC SYSTEM SHALL BE PUMPED AND REMOVED. 13. ALL RUN-OFF TO BE CONTAINED ON-SITE DESIGN REQUIRED (BY OTHERS). FINAL GRADING TO BE IN ACCORDANCE WITH FEMA REGULATIONS. 14. DRYWELLS (OR DRIP TRENCHES) SHALL BE INSTALLED TO CONTAIN ROOF RUN-OFF. 15. CONTRACTOR TO COORDINATE ALL UTILITY DISCONNECTS AND NEW SERVICES WITH APPROPRIATE VENDORS. 16. SHOULD PRIMARY LEACHING FACILITY FAIL, IT SHALL BE REMOVED IN ITS ENTIRETY, ALL CONTAMINATED SOILS REMOVED AND SYSTEM TO BE REPLACED IN KIND. TEST HOLE LOGS ENGINEER: ARNE H. OJALA PE, PLS SE1804 WITNESS: PHIL RENAUD DATE: 2/10/2010 PERC. RATE < 22 MIN/INCH CLASS I SOILS ELEV. ELEV. 4 FI LL 28" 4.5' A LS 32" 10YR 2/1 4.1' E FS 36" 1OYR .6/1 3.8' FILL 36" 4.3' A LS 38" 1OYR 2/1 4.1' E FS 40" 1OYR 6/1 4.0' B LS B LS 50" 1OYR 5/6 2.6' 66" 1OYR 5/6 C1 C1 PERC MCS MCS BOTT. AT 1 OYR 6/6 1 OYR 6/6 60" 60" V EL. 1.8' 114" DICE #10-006 V EL. 1.8' -2.2' 7.5'* (SEE DETAIL) 8.52 5' MIN.UNSUITABLE <: • BLOCK UP FOR 24" COVER TYP. SOIL REMOVAL O O O O O O O O O O O C D -BOX ACME DB -9 OR EQ. 7.50' 0 0 0 0 0 0 0 0 0 0 0 WHERE SPECIFIED ' 000 O O O O O O O O O C O�O�O�O�O�O�O�O�O�O�O�O� DEPTH PER SOIL LOGS '• 5'D, 6" CRUSHED STONE OR MECHANICAL oo°000000°oa f - COMPACTION. (15.221 [21) WATER TEST O'BOX FOR LEVELNESS USE TIDALLY INFLUENCED ADJ. GROUNDWATER _ ELEV. 2.5' LEACHING: USE A 748 SF LEACHING FIELD 748 SF X .74 = 553 GPD O.K. (2-+% SLOPE) 10' - ST/PC 40' D' BOX _ LEACHING ACCESS FOR ROUTINE MAINTENANCE FOUNDATION FACILITY MUST BE PROVIDED FOR ZABEL FILTER. INSTALLER MUST FOLLOW ALL MANUFACTURER'S SPECIFICATIONS FOR PROPER FILTER INSTALLATION 1 \ EXIST;NG DWE.-LiNG FLOOD --VENT (TYP,- . i AND CONTROL PANEL ALARM A COURT TO BE INSTALLED INSIDE 'P'jtovW'1�D BUILDING. ALARM TO BE ON INV. IN 7.2' LOT SIZE SEPARATE CIRCUIT FROM PUMP 15,600 S.F. ZA (A100)TER I 24' TEE FLOAT SWITC H ALARM ON OUTLET TEE w/ExTENSION 130' SETTINGS: 1500 GAL NI PUMP ON 6" . THIS SIDE 5' WORKING RANGE OF BAFFLE 5" 8.5' PUMP OFF 12 REAR SETBACK 4 Do SES PER DAY, AT 110 GAL. PER DOSE (5" WORKING RANGE) MAX. LOT COVERAGE 25% 2500 GAL. SEPTIC TANK/PUN IS LOCATED NOT WITHIN MASS DEP ZONE II. -'N'� (NOT TO SCALE) 5' REMOVAL OF UNSUITABLE SOIL REQUIRED AROUND PERIMETER OF LEACHING FACILITY, DOWN TO SUITABLE SOIL LAYER. REPLACE WITH CLEAN MED. SAND, TO MEET SPECIFICATIONS OF 310 CMR 15.255(3) 3., PROP. RETAINING WALL T.O.W. - EL 8.8' (SEE DETAIL, DESIGN BY OTHERS) S� o ` D-6 7W I I I I D-5 D-3 `PNDWpRO E�G� f vUN� - D-4 ZONE j oa DAN /121 o OJ. / p12 (_t' CI / z No.4 'FF G 5 $310 DATE DANIEL NOTE: 550± GAL RESERVE PROVIDED IN PC WEEP HOLE CHECK VALVE MYERS SRM 4 SUBMERSIBLE 4710 HP PUMP SYSTEM (OR EQUAL) (ON BLOCK) `6- BAFFLE HAMBER COMBINATION LOCUS MAP SCALE 1"=2000'± ASSESSORS MAP 14 PARCEL 128 LOCUS IS WITHIN FEMA FLOOD ZONE Al2 (EL 10) AND B AS SHOWN ON COMMUNITY PANEL #250015 0005D DATED 7/2/1992 DATUM: NGVD ZONING SUMMARY THEODORE WOJNAR 104 CALM COURT BELLAIRE, TX 77401 REFERENCES LAND COURT 1'�.ECq. 'P'jtovW'1�D MIN. LOT SIZE 25,000 S.F. 15,600 S.F. MIN. LOT FRONTAGE 150' 130' MIN. FRONT SETBACK 30' 31.3' MIN. SIDE SETBACK 15' 15.9' MIN. REAR SETBACK 20' 29.7' MAX. LOT COVERAGE 25% 22.0% SITE IS LOCATED NOT WITHIN MASS DEP ZONE II. OWNER OF RECORD THEODORE WOJNAR 104 CALM COURT BELLAIRE, TX 77401 REFERENCES LAND COURT DOC: 1,045,034 LAND COURT CTF; 181185 LAND COURT PLAN 14426-H (SHEET 2) REQUIRED INSPECTIONS AND CERTIFICATIONS 1. ENGINEER SHALL INSPECT WHEN REQUIRED EXCAVATION IS COMPLETE. 2. ENGINEER SHALL STAKE FOOTING PRIOR TO POURING SAS DETAIL 3. ENGINEER SHALL INSPECT FOOTING AND REBAR PRIOR TO POURING 1" - 20' OF WALL 4. ENGINEER SHALL INSPECT WHEN CLEAN FILL HAS BEEN PROPERLY DEPOSITED 5. ENGINEER SHALL INSPECT AND CERTIFY SEPTIC COMPONENTS AND PUMP MECHANISMS AFTER INSTALLATION ENGINEER SHALL CERTIFY TO YARMOUTH HEALTH DEPARTMENT THAT THE RETAINING WALL, SEPTIC SYSTEM AND PUMP MECHANISMS HAVE BEEN INSTALLED IN SUBSTANTIAL COMPLIANCE WITH THE APPROVED PLAN. TITLE 5 SITE PLA D-7 OF 10 WHALE ROAD WEST YARMOUTH PREPARED FOR THEODORE WOJNAR DATE: MARCH 15, 2010 REV 4/20/10 (MOVE/ROTATE HSE) REV 5/25/10 (ROOF & PATIO) Scale:1 "= 20' 0 10 20 30 40 50 FEET I off 508-362-4541 fax 508-362-9880 downcape.comID down cape engineering, inc. civil engineers fond surveyors 939 Main Street ( Rte 6A) YARMOUTHPORT MA 02675 10-006 WOJNAR.DWG