HomeMy WebLinkAbout47 Workshop- DetailsMOD EXHAUST FAN TO DDC f=H OA APPLICATION SPECIFIC CONTROLLER GENERAL: 1. THE EXHAUST/SUPPLY FANS ARE CONTROLLED THROUGH THE DDC. 2. THE SEQUENCE LISTED BELOW IS REVERSIBLE SEQUENCE OF OPERATIONS: EXHAUST FAN - OCCUPIED HOURS: 1. MOTOR OPERATED DAMPER OPENS 2. EXHAUST FAN ENERGIZES AND RUNS CONTINUOUSLY EXHAUST FAN - UNOCCUPIED HOURS 1. EXHAUST FAN SHUTS OFF 2. MOTOR OPERATED DAMPER CLOSES SUPPLY FAN - OCCUPIED HOURS: 1. MOTOR OPERATED DAMPER OPENS 2. SUPPLY FAN ENERGIZES AND RUNS CONTINUOUSLY SUPPLY FAN - UNOCCUPIED HOURS 1. SUPPLY FAN SHUTS OFF 2. MOTOR OPERATED DAMPER CLOSES SUPPLY/EXHAUST FAN SEQUENCE OF OPERATION 2 HVAC J 999 BROADWAY SUITE 206 Q SAUGUS, MA O1 906 L 3 761 -233-4606 170 COMMERCE WAY w ENGINEERING c�1 PORTSMOUTH, NH 03BOl _ 603-31 9-B244 FIRE PROTECTION FLEX CONNECTION (TYP) PHOA REFER TO SPECS OR MATE AL TO DDCICATION SPECIFIC — — S/SEXHAUST FAN -0AIR CONTROLLE FLOW I eD" AD L----------- GENERAL: 1. THE EXHAUST FANS ARE CONTROLLED THROUGH THE DDC. 2. THE SEQUENCE LISTED BELOW IS REVERSIBLE SEQUENCE OF OPERATIONS: OCCUPIED HOURS. 1. UPON ACTIVATION OF THE EXHAUST FAN BY THE DDC: A. THE EXHAUST FAN MOTORIZED DAMPER OPENS B. THE EXHAUST FAN IS ENERGIZED THROUGH ITS RESPECTIVE DAMPER END SWITCH C. EXHAUST FANS ARE ENERGIZED AND RUN CONTINUOUSLY 2. WHEN A FAILURE OF THE EXHAUST FAN SENSED BY THE CURRENT SENSOR CT, AN ALARM IS SENT TO THE ATC SYSTEM CENTRAL WORKSTATION. UNOCCUPIED HOURS: 1. EXHAUST FANS ARE DEENERGIZED. 2. THE EXHAUST FAN MOTORIZED DAMPER IS CLOSED. EXHAUST FAN SEQUENCE OF OPERATION ACCESS DOOR (BOTH SIDES) FOR ALL FANS WITH DUCT CONNECTIONS LARGER THAN 36"(ROUND OR SQUARE). COORDINATE WITH OWNER FOR LOCATION AND SIZE. 1 NOTES: 1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES. 2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION. 3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA INLINE FAN SEE NOTE 3 ALV HANGE THREADS[ HANGER HANGER STRAP UNISTRUT ANGLE IR, DUCT HANGER SUPPORT EXHAUST FAN SCHEDULE TAG NO. SERVICE SUPPORT ROD HUNG ANCHOR DUCT" FAN TYPE E.S.P. (IN.WG) FROM CEILING TO PREVENT MOTOF MANUFACTURER AND MODEL NUMBER (AS STANDARD) REMARKS LATERAL � AA OW VIBRATION ISOLATOR Z MOVEMENT HP V SPRING ASSEMBLY EF -B-3 BLOWER RM. o z SEE SPECS FLEX CONNECTION (TYP) PHOA REFER TO SPECS OR MATE AL TO DDCICATION SPECIFIC — — S/SEXHAUST FAN -0AIR CONTROLLE FLOW I eD" AD L----------- GENERAL: 1. THE EXHAUST FANS ARE CONTROLLED THROUGH THE DDC. 2. THE SEQUENCE LISTED BELOW IS REVERSIBLE SEQUENCE OF OPERATIONS: OCCUPIED HOURS. 1. UPON ACTIVATION OF THE EXHAUST FAN BY THE DDC: A. THE EXHAUST FAN MOTORIZED DAMPER OPENS B. THE EXHAUST FAN IS ENERGIZED THROUGH ITS RESPECTIVE DAMPER END SWITCH C. EXHAUST FANS ARE ENERGIZED AND RUN CONTINUOUSLY 2. WHEN A FAILURE OF THE EXHAUST FAN SENSED BY THE CURRENT SENSOR CT, AN ALARM IS SENT TO THE ATC SYSTEM CENTRAL WORKSTATION. UNOCCUPIED HOURS: 1. EXHAUST FANS ARE DEENERGIZED. 2. THE EXHAUST FAN MOTORIZED DAMPER IS CLOSED. EXHAUST FAN SEQUENCE OF OPERATION ACCESS DOOR (BOTH SIDES) FOR ALL FANS WITH DUCT CONNECTIONS LARGER THAN 36"(ROUND OR SQUARE). COORDINATE WITH OWNER FOR LOCATION AND SIZE. 1 NOTES: 1. ON DUCTS OVER 48" WIDE, BOTTOM SHALL BE BRACED BY ANGLE. FOR CROSS SECTION AREA MORE THAN 8 SQ FT, DUCT SHALL BE BRACED BY ANGLES ON ALL FOUR SIDES. 2. CUTTING AND PATCHING SHALL BE LIMITED TO A MINIMUM AS REQUIRED FOR PROPER INSTALLATION. 3. SUPPORTS SHALL BE SPACED AND SIZED AS PER SMACNA INLINE FAN SEE NOTE 3 ALV HANGE THREADS[ HANGER HANGER STRAP UNISTRUT ANGLE IR, DUCT HANGER SUPPORT EXHAUST FAN SCHEDULE TAG NO. SERVICE LOCATION CFM FAN TYPE E.S.P. (IN.WG) WHEEL OUTLET VELOCITY (FPM) MOTOF MANUFACTURER AND MODEL NUMBER (AS STANDARD) REMARKS DIA. (IN.) TYPE DRIVE RPNI BHP HP V PH EF -B-3 BLOWER RM. BASEMENT MECH. RM, 5700 INLINE EXISTING FAN SEE DWG. H-2 SF -B-1 BLOWER RM. BASEMENT MECH. RM. 5700 INLINE - EXISTING FAN SEE DWG. H-2 EF -2-6 VENT RM. 2ND FLOOR MECH. RM. 920 INLINE 1.5 13.125 CENT. BELT 420 1914 0.55 3/4 208 3 GREENHECK BSQ-130HP-7 SEE NOTES EF -2-8 VENT RM. 2ND FLOOR MECH. RM. 1270 INLINE 1.5 14.625 CENT. BELT 469 1767 0.66 3/4 208 3 GREENHECK BSO-140HP-7 SEE NOTES NOTES: 1. PROVIDE FAN WITH SPARK RESISTANT CONSTRUCTION. COPYRIGHT 2013 WESTON & SAMPSON cn ;_i cn c- r- i _u y CJ U O � I cu co co cu i [ Q D C I i I a �( w� U Q Q) 0 F- f U) 1 jz'`�! w i W j i 1 : 3 i v w? O j ( o i m c:> .- 1w �z m W a Q � Q 0 m I I IU Lij 10 1a - m p LLJ L Q LLJ V) r M a� (� l w Lo C) 0 I N i c o O i €z DAVID H. 6� MAHONEY m C ANICAL �-4 q p � T j Lfi m � m Y S U { ra m UJ 0 z (10 �'y 0 C)' 0 Q- 0 v� C: Ld <C cv O' Cil z uI ! _ice V_,.r)^ L j IL � � m O LL) cff 0 :"� > U CL < _ n Q } a - z O ". U 0 - I� 1.11 J Q U l -x t c-' Ise O z .�__..-.�_ ..,..I w LL