HomeMy WebLinkAboutBLD-17-5693SEE VALVE
DETAIL
4- — -
2" WATER
SERVICE
_.---SPARE HEAD CABINET
1ofTO_� 0
SYSTEM
1 1/4" VICTAULIC RISER MANIFOLD
/ FLOW SWITCH, PRESSURE
GAUGE, TEST AND DRAIN VALVE
Litu 1 1/4" BUTTERBALL
® i VALVES
W/ TAMPER SWITCHES
TEST & DRAIN
VALVE//TO DOMESTIC
WATER METER
3/4" DRAIN 0--'�2- WATER
PIPE T0/ SERVICE
EXTERIOR) 11/4' AMES
ODEL 20008—FP
DOUBLE CHECK VALVE
Valve Detail
NOT TO SCALE
SITE PLAN
NOT TO SCALE
j,
LO
I
FLOW HYDRANT
GAUGE HYDRANT
ELEV: 7'
21 TOTAL SPRINKLERS
MAX RESIDENTIAL HEAD SPACING: 16'x16'
DRY SIDEWALLS AT
UNHEATED CLOSET
V-0" MINIMUM LENGTH
HYDRAULIC REMOTE AREA #1
D. FPE STAMP
A.H.J. LOCAL FIRE DEPT./F.P.E.
SPRINKLER SYMBOLS
PIPE TYPES
t7u.,
0 'N WA,
SYM
CNT
NAME
FINISH
TEMP K -FAC NPT MFG.
MODEL#
ESCU
IDEN#
Q
10
RES. PENDENT
WHITE
155 4.90 1/2" RELIABLE
171RES
WHITE
R3516
d
9
RES. SIDEWALL
WHITE
155 4.40 1/2" RELIABLE
FIRES
WHITE
R3531
1001
2
DRY SIDEWALL
WHITE
155 4.40 1" RELIABLE
F3RES44
WHITE
RA5231
21 TOTAL SPRINKLERS
MAX RESIDENTIAL HEAD SPACING: 16'x16'
DRY SIDEWALLS AT
UNHEATED CLOSET
V-0" MINIMUM LENGTH
HYDRAULIC REMOTE AREA #1
D. FPE STAMP
A.H.J. LOCAL FIRE DEPT./F.P.E.
DESIGN STD. N.F.P.A. 13D (2013 EDITION)
PIPE TYPES
t7u.,
0 'N WA,
MAINS CPVC
co
°''03
BRANCHES CPVC
SPRINKLER ORIFICE K=
4.40
AREA LOCATION 2nd FLOOR LIVING
# OF FLOWING SPRINKLERS 2
NOT TO SCALE
DENSITY 0.05 G.P.M./SQ.FT
256
REMOTE AREA TWO SPRINKLERS
SQ.FT.
DEMAND AT SOURCE CONNECTION
�f
FLOW 32
G.P.M.
PRESSURE 43.0
P.S.I.
OUTSIDE HOSE STREAM _(INCLUDED) 0
G.P.M.
AVAILABLE PRESSURE OF 75.0 psi EXCEEDS THE
REQUIRED PRESSURE OF 43.0 psi. THIS IS A
SAFETY MARGIN OF 32.0 psi OR 439 OF THE SUPPLY
WATER FLOW TEST
DATE: 4/3/17
STATIC: 75 PSI
RESIDUAL: 70 PSI
FLOW: 1250 GPM
BY: MASS FIRE PROTECTION
Jlr/'1LC 1/Y - I 'V
3
GENERAL NOTES
1. PROJECT IS A NEW 2 STORY SINGLE FAMILY HOME (NO BASEMENT).
TYPICAL WOOD CONSTRUCTION. 2965 TOTAL SQUARE FEET (BOTH
FLOORS INCLUDED).
2. FIRE SPRINKLER SYSTEM SHALL BE INSTALLED THROUGHOUT
BUILDING. WET SPRINKLER SYSTEM SHALL BE PROVIDED.
3. SPRINKLER SYSTEM IS DESIGNED IN ACCORDANCE WITH NFPA 13D
(2013) "INSTALLATION OF SPRINKLER SYSTEMS IN ONE & TWO FAMILY
DWELLINGS".
4. OWNER TO PROVIDE ADEQUATE HEAT THROUGHOUT TO AVOID PIPES
FREEZING. MAINTAIN TEMPERATURE ABOVE 407.
5. ALL WORK AND MATERIALS WILL BE IN ACCORDANCE WITH NFPA 13D
STANDARD.
6. ALL SPRINKLER PIPING SHALL BE BLAZEMASTER CPVC JOINED BY
COMPATIBLE CPVC FITTINGS. CPVC PIPE SHALL BE INSTALLED PER
MANUFACTURER LISTING. EXCEPTION: VALVE ROOM PIPING SHALL BE
BLACK STEEL PIPE THREADED OR GROOVED.
7. INSTALLING PENDENT AND SIDEWALL SPRINKLERS THROUGHOUT
LIVING SPACE.
8. SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS WHICH DO NOT
EXCEED 55 SQUARE FEET.
9. SPRINKLERS SHALL NOT BE REQUIRED IN CLOSETS WHICH DO NOT
EXCEED 24 SQUARE FEET AND HAVE A LEAST DIMENSION WHICH DOES
NOT EXCEED 3 FEET.
10. SPRINKLERS ARE NOT REQUIRED IN ATTICS AND CONCEALED SPACES
NOT INTENDED FOR LIVING, STORAGE, AND CONTAIN NO FUEL FIRED
EQUIPMENT IN ACCORDANCE WITH NFPA 13D.
11. SPRINKLERS ARE NOT REQUIRED IN GARAGES.
12. SPRINKLERS ARE NOT REQUIRED AT COVERED UNHEATED
PROJECTIONS OF THE BUILDING AT ENTRANCES/EXITS.
13. ALL ELECTRICAL WIRING FOR ALARM DEVICES SHALL BE PROVIDED BY
OTHERS.
14. ALL CPVC PIPING SHALL BE CONCEALED IN WALLS AND JOIST SPACE.
IF THIS IS NOT POSSIBLE, SOFFITS SHALL BE PROVIDED BY OTHERS.
CPVC PIPE STRAP
O
o
CPVC PIPE HEX HEAD SELF
TAPPING SCREW
_1-1n
DOUBLE FASTENER
CPVC PIPE STRAP
HANGER APPLICATION
O RESTRAINERAPPLICATION
CPVC PIPE / O
HEX HEAD SELF
TAPPING SCREW`
T
SINGLE FASTENER
CPVC PIPE STRAP
WOOD BEAM
--------SAMMY SIDEWINDER
�3/8" ALL THREAD ROD
SWIVEL RING HANGER
1P41
2S'
Q)
U
r
W
00
Q) Cit
o
Q)
u
cd p
0
O
Co �
Scott
Henderson
D. FPE STAMP
rR�
0140-01*0*0ritf
t7u.,
0 'N WA,
-1
co
°''03
2017.04.
C
NOT TO SCALE
J `
'sL Q
2S'
Q)
U
r
W
00
Q) Cit
o
Q)
u
cd p
0
O
Co �
Scott
Henderson
D. FPE STAMP
HANGER DETAIL
w�x
co
°''03
2017.04.
C
NOT TO SCALE
J `
'sL Q
10:49-026
�f
cf) I
4) C
z
1001
4_
�
LL .69
z
I-
9
Ofa
N
Rt
O �
O 00
UN
- o0
Ja
w
O
co
d -
O
O
Lid
0
0
U
a�
0
a
w
V3
A
0 m n
Q z C
I T
u-
0 Cn 0
L
0Co