Loading...
HomeMy WebLinkAboutBono Sunoco- Stage 2 Vapor Recovery002OBSERVATION OF LEAKS AS EVIDENCE BY SOAP BUBBLES. CAUTION MUST BE TAKEN THAT ALL TANKS BE COMPLETELY 1 ISOLATED FROM THE PIPING DURING THIS TEST AS THE f ` I TANKS THEMSELVES ARE NOT CAPABLE OF WITHSTANDING THIS AMOUNT OF PRESSURE.. ANY DAMAGE TO TANKS AS A RESULT OF OVER -PRESSURING SHALL BE CORRECTED AT THE I I I I EXPENSE OF THE CONTRACTOR. ALL TERMINAL POINTS SHALL BE CAPPED AND/OR PLUGGED DURING TEST AND BE AVOIDED WHILE UNDER PRESSURE. NO LINES SHOULD BE BACKFILLED UNTIL TESTED AND CERTIFIED TIGHT. I � I REG. `ULTRA U/L * ` ECONO U/L %%mon.* �...... mow..... 2' FRP PIPE CAPPE - LL w �. J e EDGE OF TANK MAT 8 1/16" 8 3/8' 8 3/8' 4 7/8" 9 3/4' 13 3/4' 13 3/4' z o a- 3/4' CONDUIT FROM BLDG. - PLUGGED 0 a EDGE OF TANK MAT 3 - 1 1/2' $ 2'VAPOR RETURN HEADER o —,— — — — - — — — — — — — — — — — —'J — — — — 7/8'v i PRODUCT RISERS UNDERGROUND FRP PIPING MUST BE PROVIDED L, ----1 2 3/4 _ _ _ I_ �1 _ W/ A METAL PROTECTOR PLATE OF ADEQUATE M - — - - - OF DISP. - POSITIONED NO MORE THAN j� � � ,J� STRENGTH AND SIZE io �, (+}- -- {`, - - — {+}- - -'— - (+}- - - — {+}- - - — + - - - fL OF DISP. '" mi SIX INCHES ABOVE THE PIPING TO PREVENT DAMAGE 6 - 1 1/2'0 PRODUCT J.B. TO THE PIPING DURING FUTURE EXCAVATIONS.. r I N IN ADDITION, A WARNING TAPE BURIED NO MORE — RISERS .. I 1'>�V/R RISER — — — BASE FRAME (34�A i i THAN SIX INCHES BELOW GRADE SHALL BE -- ---- ----T------- - -"- -- _ _ �.J LO BASE FRAME 34 — POSITIONED OVER THE FIBERGLASS PIPING WARNING FRONT FRONT , THAT FIBERGLASS PIPING IS BELOW. y 1' HEALY JET PUMP RISER . Ll' 9' HEALY JET JMF RISER RETRO -BLENDER ' •--5 3l8' 43' (SEE BASE RETRO -SINGLE 59 3/!3' 47' FRAME DETAIL) (SEE BASE FRAME DETAIL) PLAN PLAN '385' MGB BASE FRAME 1395' HI -HOSE MGB BASE FRA" iE 1 1/2•95PRODUCT ' RISER 1 1/2116 PRODUCT RISER 2 - 1 1/2' OPROOUCT RISERS 6 1/4' 10V/R RISER BASE r-RAME 3s w J.B• w CD wz ------ --- !-- - -- OF D!SP. ww 1- 0_., v oco I � FRONT r� 1' IDV/R RISER 20 3/4' 24 3/4' PLAN 6 1/4' - ELECTRONIC RETROFIT ELECTRONIC RETROFIT (SINGLE OR DUO - 1) BASE FRAME (BLENDER OR DUO - 2) BASE FRAME TO VENT RISER _ k I NOTES: EVR MANIFOI -0 !, i I. SEE DWG. 3-410 SHT. 2 FOR BILL OF MATERIALS. STAGE I VAPOR RECOVERY SYSTEM 2. 1/8'/FT. MIN. SLOPE MUST BE MAINTAINED ,FOR PROPER SYSTEM OPERATION. ALL PIPING 10 BE *.� INSTALLED FREE OF SAGS, PEAKS OR ANY. OTHER `� � CONDITIONS WHERE PRODUCT COULD COLLECT. 3. TESTING - SEE DWG. 3-410, SHT. I, SECT. 5.8 FOR DETAILS rN 3.1 50* AIR TEST - PIPING SHALL BE AIR TESTED TO 50 PSI (POUNDS PER SQUARE INCH) WHICH WHICH MUST BE MAINTAINED WITHOUT PRESSURE DROP UNTIL BACKFILLING, CONCRETE MAT, ISLAND AND DRIVE WORK ARE COMPLETE. DURING THIS TEST, PRIOR TO BACKFILLING, ALL PIPE JOINTS CONNECTIONS AND FITTINGS NSHALL BE CHECKEd 8Y COATING THEM WITH A RICH SOLUTION OF SOAP AND WATER FOR PHYSICAL OBSERVATION OF LEAKS AS EVIDENCE BY SOAP BUBBLES. CAUTION MUST BE TAKEN THAT ALL TANKS BE COMPLETELY 1 ISOLATED FROM THE PIPING DURING THIS TEST AS THE f ` I TANKS THEMSELVES ARE NOT CAPABLE OF WITHSTANDING THIS AMOUNT OF PRESSURE.. ANY DAMAGE TO TANKS AS A RESULT OF OVER -PRESSURING SHALL BE CORRECTED AT THE I I I I EXPENSE OF THE CONTRACTOR. ALL TERMINAL POINTS SHALL BE CAPPED AND/OR PLUGGED DURING TEST AND BE AVOIDED WHILE UNDER PRESSURE. NO LINES SHOULD BE BACKFILLED UNTIL TESTED AND CERTIFIED TIGHT. I � I REG. `ULTRA U/L * ` ECONO U/L %%mon.* �...... mow..... 2' FRP PIPE CAPPE - LL w �. J e EDGE OF TANK MAT 8 1/16" 8 3/8' 8 3/8' 4 7/8" 9 3/4' 13 3/4' 13 3/4' z o a- 3/4' CONDUIT FROM BLDG. - PLUGGED 0 a EDGE OF TANK MAT 3 - 1 1/2' $ 2'VAPOR RETURN HEADER o —,— — — — - — — — — — — — — — — — —'J — — — — 7/8'v i PRODUCT RISERS UNDERGROUND FRP PIPING MUST BE PROVIDED L, ----1 2 3/4 _ _ _ I_ �1 _ W/ A METAL PROTECTOR PLATE OF ADEQUATE M - — - - - OF DISP. - POSITIONED NO MORE THAN j� � � ,J� STRENGTH AND SIZE io �, (+}- -- {`, - - — {+}- - -'— - (+}- - - — {+}- - - — + - - - fL OF DISP. '" mi SIX INCHES ABOVE THE PIPING TO PREVENT DAMAGE 6 - 1 1/2'0 PRODUCT J.B. TO THE PIPING DURING FUTURE EXCAVATIONS.. r I N IN ADDITION, A WARNING TAPE BURIED NO MORE — RISERS .. I 1'>�V/R RISER — — — BASE FRAME (34�A i i THAN SIX INCHES BELOW GRADE SHALL BE -- ---- ----T------- - -"- -- _ _ �.J LO BASE FRAME 34 — POSITIONED OVER THE FIBERGLASS PIPING WARNING FRONT FRONT , THAT FIBERGLASS PIPING IS BELOW. y 1' HEALY JET PUMP RISER . Ll' 9' HEALY JET JMF RISER RETRO -BLENDER ' •--5 3l8' 43' (SEE BASE RETRO -SINGLE 59 3/!3' 47' FRAME DETAIL) (SEE BASE FRAME DETAIL) PLAN PLAN '385' MGB BASE FRAME 1395' HI -HOSE MGB BASE FRA" iE 1 1/2•95PRODUCT ' RISER 1 1/2116 PRODUCT RISER 2 - 1 1/2' OPROOUCT RISERS 6 1/4' 10V/R RISER BASE r-RAME 3s w J.B• w CD wz ------ --- !-- - -- OF D!SP. ww 1- 0_., v oco I � FRONT r� 1' IDV/R RISER 20 3/4' 24 3/4' PLAN 6 1/4' 1 1/2' P PRODUCT RISER CL OF DISP. BASE FRAME ss F1 71 w I � � 1' i(V/R P,ISER wZ ------ oN I E�� FRONT 20 3/4' I 24 3/4' PLAN DRESSER/WAYNE ELECTRONIC (SINGLE OR DUO - I) BASE FRAME THIS DRAWING IS AND SHALL REMAIN THE PROPERTY OF S' -!N REFINING AND MARKETING COMPANY. USE, REPRODUCTION OR ALTERATION OF THIS DRAWING WITHOUT THE EXPRESSED WRITTEN PERMISSION OF SUN REFINING AND MARKETING, COMPANY IS PROHIBITED. ;AME 3s G OF DISP. i FOR FUTURE CONNECTION TO 12 PIPE CAP DISPENSER VAPOR RECOVERY SEE 'CAMBRIDGE ENGINEERING' DWGS. 8501-395MJ, TOP OF 1' 8501-518MJ, 8501-511MJ OR 8502-124 V/R RISER u' TOP OF ISLAND 2" X 1' FRP I tin'D. REC`!rFR BUSHING es 1' GALV. STL. RISER 2' FRP SLEEVE COUPLING eT 73 2' FRP VAPOR LINE (SLOPE DOWN 1/8'/FT. TO JET PUMP 0 ECO. TK.) O1 1/2` X 30' FLEX CONNECTOR —2' X 1 1/2' FRP THR'D. REDUCER BUSHING z3 VAPOR RISER .AND BRANCH LINE ELEVATION (MGB'S AND ALL ELECT. RETRO. DISPENSERS) 1"16 V/R RISER r -- I ❑ 1 1/2'0 PRODUCT RISER- 2'VAPOR RETURN LINE (SLOPE 1/8'/FT., MIN.) _ 395 MULTI -GRADE BLENDER u- PRODUCT LINES o TO DISPENSERS L O F -- U ' W C� (SEE BASE FRAME DETAIL) TYPICAL VAPOR RECOVERY PIPING FOR BALANCE SYSTEM REFERENCE DRAWINGS STANDARD FIBERGLASS PIPING DETAILS 3-410 REV.5 SHEETS 1 & 2 FIBERGLASS TANKS & DETAILS 3-411 REV. 4, EXTERIOR CONCRETE DETAILS 4-501 REV.3 r t f 1 r N0 DATE REVtS!DNS MADE Cl -A"' APPV'D. BY BY SUN REFINING & MARKETING COMPANY �'aailiEiee �: �i�£ribuiion �aparExroni PbOa.aelplia, PA OF A9gs�� STAGE :II VAPOR RECOVERY TWE ` HEALY CENTRAL SYSTEM OS'PIPING ONLY' ' Pilo- 27286 �FGISTER�� •F`�" - DRAWN M„A �fiG_t'S APPROVAL DRAWN.' NUMBER � .REV, hi0 ' r F __/ • CHECKED . I"x' ,.�"� � �� ' DATE /14; ES ti 3-424 "- 4 �j L.. 4 0, SCALE - ELECTRONIC RETROFIT ELECTRONIC RETROFIT (SINGLE OR DUO - 1) BASE FRAME (BLENDER OR DUO - 2) BASE FRAME 1 1/2' P PRODUCT RISER CL OF DISP. BASE FRAME ss F1 71 w I � � 1' i(V/R P,ISER wZ ------ oN I E�� FRONT 20 3/4' I 24 3/4' PLAN DRESSER/WAYNE ELECTRONIC (SINGLE OR DUO - I) BASE FRAME THIS DRAWING IS AND SHALL REMAIN THE PROPERTY OF S' -!N REFINING AND MARKETING COMPANY. USE, REPRODUCTION OR ALTERATION OF THIS DRAWING WITHOUT THE EXPRESSED WRITTEN PERMISSION OF SUN REFINING AND MARKETING, COMPANY IS PROHIBITED. ;AME 3s G OF DISP. i FOR FUTURE CONNECTION TO 12 PIPE CAP DISPENSER VAPOR RECOVERY SEE 'CAMBRIDGE ENGINEERING' DWGS. 8501-395MJ, TOP OF 1' 8501-518MJ, 8501-511MJ OR 8502-124 V/R RISER u' TOP OF ISLAND 2" X 1' FRP I tin'D. REC`!rFR BUSHING es 1' GALV. STL. RISER 2' FRP SLEEVE COUPLING eT 73 2' FRP VAPOR LINE (SLOPE DOWN 1/8'/FT. TO JET PUMP 0 ECO. TK.) O1 1/2` X 30' FLEX CONNECTOR —2' X 1 1/2' FRP THR'D. REDUCER BUSHING z3 VAPOR RISER .AND BRANCH LINE ELEVATION (MGB'S AND ALL ELECT. RETRO. DISPENSERS) 1"16 V/R RISER r -- I ❑ 1 1/2'0 PRODUCT RISER- 2'VAPOR RETURN LINE (SLOPE 1/8'/FT., MIN.) _ 395 MULTI -GRADE BLENDER u- PRODUCT LINES o TO DISPENSERS L O F -- U ' W C� (SEE BASE FRAME DETAIL) TYPICAL VAPOR RECOVERY PIPING FOR BALANCE SYSTEM REFERENCE DRAWINGS STANDARD FIBERGLASS PIPING DETAILS 3-410 REV.5 SHEETS 1 & 2 FIBERGLASS TANKS & DETAILS 3-411 REV. 4, EXTERIOR CONCRETE DETAILS 4-501 REV.3 r t f 1 r N0 DATE REVtS!DNS MADE Cl -A"' APPV'D. BY BY SUN REFINING & MARKETING COMPANY �'aailiEiee �: �i�£ribuiion �aparExroni PbOa.aelplia, PA OF A9gs�� STAGE :II VAPOR RECOVERY TWE ` HEALY CENTRAL SYSTEM OS'PIPING ONLY' ' Pilo- 27286 �FGISTER�� •F`�" - DRAWN M„A �fiG_t'S APPROVAL DRAWN.' NUMBER � .REV, hi0 ' r F __/ • CHECKED . I"x' ,.�"� � �� ' DATE /14; ES ti 3-424 "- 4 �j L.. 4 0, SCALE