HomeMy WebLinkAboutSprint - PCS Site Plan Review - Cell Site Installation NotesSCALE: N.T.S. W:\SPRINT\7472\CAPECOD\73\RNA663C7.DWG 6/18/99 J.R.H.
CELL SITE INSTALLATION NOTES:
THE FOLLOWING INSTALLATION NOTES HAVE BEEN COMPILED FROM THE EXISTING PROJECT DOCUMENTS (I.E. PROJECT
SPECIFICATIONS, SPRINT STANDARD PRACTICE, LUCENT DOCUMENTS, ETC.) FOR USE. THESE NOTES SHALL BE UTILIZED
FOR THE CONSTRUCTION OF THE CELL SITES TO ENSURE COMPLIANCE WITH THE PROJECT DESIGN AND SPECIFICATION
REQUIREMENTS.
A. GROUNDING:
1. ALL METAL CONDUIT FOR GROUNDING DOWN CONDUCTORS SHALL BE BONDED TO THE GROUND SYSTEM AT BOTH ENDS.
2. GROUNDING CONDUCTORS SHALL BE CONNECTED TO THE MAIN WATER PIPE USING A BURNDY TYPE GAR—TC CLAMP.
3. KOPR—SHIELD ANTI—OXIDATION COMPOUND SHALL BE USED ON ALL GROUNDING CONNECTIONS.
4. ALL UNDERGROUND GROUNDING CONNECTIONS SHALL BE MADE BY THE CADWELD @PROCESS.
5. ALL CADWELDS @ SHALL BE INSTALLED USING THE PROPER CONNECTION/MOLD AND MATERIALS FOR THE PARTICULAR
CONNECTION AND/OR APPLICATION.
TEF CONNECTION SWEEP CONNECTION POST CONNECTION
ANTENNA POST
CADWELD
ADWELD
#2 AWG BCW -CADWELD #2 AWG BCW
�+
#2 AWG BCW
6. ALL BOLTED GROUNDING CONNECTIONS SHALL BE INSTALLED WITH A MK WASHER UNDER THE NUT. HARDWARE FOR
BOLTED CONNECTIONS SHALL BE MINIMUM OF 3/8" DIAMETER AND SHALL BE STAINLESS STEEL.
7. GROUNDING WIRE SHALL NOT BE INSTALLED OR ROUTED THROUGH HOLES IN ANY METAL OBJECTS OR SUPPORTS TO
PRECLUDE ESTABLISHING A "CHOKE" POINT.
`#2 AWG BCW
DEPICTS CHOKE POINT (NOT ACCEPTABLE)
8. FERROUS METAL CLIPS WHICH COMPLETELY SURROUND THE GROUNDING CONDUCTOR SHALL NOT BE USED. CLIPS OF THE
FOLLOWING MATERIALS AND TYPES MAY BE USED TO FASTEN AND SUPPORT GROUNDING CONDUCTORS.
• PLASTIC CLIPS
b
METAL CLIPS WHICH DO NOT COMPLETELY SURROUND THE GROUNDING CONDUCTOR
b
9. STANDARD BUSS BARS (CIGBES AND MIGBS) SHALL BE FURNISHED AND INSTALLED. THEY SHALL NOT BE FABRICATED OR
MODIFIED IN THE FIELD.
10. THE GROUNDING CONNECTION TO THE POWER AND TELCO CABINETS OF THE PPC SHALL BE MADE BY CONNECTING THE
CONDUCTOR FROM THE GROUND RING TO THE FACTORY FURNISHED BUSS BAR IN EACH COMPARTMENT.
11. ALL GROUNDING WIRES SHALL BE INSTALLED WITHOUT LOOPS (PIGTAILS) AND SHARP BEND RADIUS.
B. ANTENNA COAXIAL CABLES (WAVEGUIDE)
NOTE: THE RF TRANSMISSION LINE INSTALLED BETWEEN THE PRIMARY RADIO CABINET (PRC), FURNISHED BY LUCENT, AND
THE ANTENNA CONSISTS OF A COAXIAL CABLE, SOMETIMES REFERRED TO AS A WAVEGUIDE.
1. ALL ANTENNA COAXIAL CABLES AND JUMPERS SHALL BE INSTALLED WITHOUT LOOPS AND/OR PIGTAILS.
2. ANTENNA COAXIAL CABLE GROUND KITS SHAI.L.NOT BE INSTALLED ON THE JUMPER BETWEEN THE ANTENNA AND MAIN LINE
CABLE. '
3. ANTENNA COAXIAL CABLE GROUND KITS SHALL BE INSTALLED AS CLOSE TO THE CONNECTOR AS POSSIBLE AT EACH
ANTENNA. IF THIS IS NOT FEASIBLE THE GROUND .KIT SHALL BE INSTALLED IMMEDIATELY AFTER THE BEND ON THE FIRST
STRAIGHT RUN OF CABLE. THE GROUND KIT SHALL BE INSTALLED ON STRAIGHT SECTION OF CABLE ONLY AND NOT ON
BENDS.
4. ANTENNA COAXIAL CABLE SHALL BE INSTALLED TO COMPLY WITH THE MANUFACTURE'S MINIMUM BEND RADIUS SPECIFIED
BELOW. THE CONTRACTOR SHALL INSTALL RACEWAY FOR COAXIAL CABLE USING THE PROPER FITTINGS NECESSARY TO
ENSURE THAT THE MINIMUM BEND RADIUS REQUIREMENTS ARE MET. (REFERENCE: TECHNICAL INFORMATION BULLETIN NO.
96-026)
COAXIAL CABLE MINIMUM BEND RADIUS
MANUFACTURER
CABLE TYPE
CABLE SIZE
(DIAMETER)
MINIMUM BEND
RADIUS IN TRAY
MINIMUM BEND RADIUS IN 4"
OR 6" CONDUIT
CABLEWAVE
FLC 12-50J
1/2" .
5"
10"
CABLEWAVE
FLC 78-50J
7/8"
10"
18"
CABLEWAVE
FLC 1 14-50J
1 1/4-
1511
22"
CABLEWAVE
FLC 158-50J
1 5/8"
20"
28"
STRIPE)
ISSUED FOR REVIEW
RIGHT ANTENNA AS VIEWED
WHILE
JPS
5. THE GPS ANTENNA COAXIAL CABLE SHALL 6E A CONTINUOUS CABLE RUN, FROM THE CONNECTOR AT THE ANTENNA HEAD
TO THE CONNECTION AT THE BTS CABINET, WITHOUT JUMPERS.
6. THE ANTENNA COAXIAL CABLE AT THE BTS SHALL BE INSTALLED IN THE ANTENNA CABLE COVER ASSEMBLY (RCCA) IN
ACCORDANCE WITH DETAIL 513. THE FINISHED. ANTENNA' CABLES (WITH CONNECTOR AND GROUND KIT INSTALLED) SHALL
BE INSTALLED SO THAT THE END OF THE CONNECTOR PROTRUDES NO FARTHER THAN 12 INCHES INTO THE ACCA.
7. THE COAXIAL CABLE ENTRY HATCHPLATE ON THE REAR OF THE ACCA SHALL BE INSTALLED WITH THE SMALL 1/2 -
DIAMETER
/2"DIAMETER HOLES (FOR THE GPS ANTENNA AND GROUND WIRES) TO THE RIGHT (WHEN FACING THE ACCA FROM THE REAR
OF THE PRC).
8. ALL ANTENNA COAXIAL CABLES SHALL BE MARKED AND TAGGED IN ACCORDANCE WITH THE REQUIREMENTS IN PROJECT
SPECIFICATION G-002, SECTION 16000, PARAGRAPHS 36 AND 37. THE FIGURE TO THE RIGHT INDICATES AN EXAMPLE OF THE
COLOR CODE MARKED ON THE COAXIAL CABLES.
9. SINCE THERE ARE A NUMBER OF DIFFERENT COAXIAL CABLE ENTRY HATCHPLATES THAT MAY BE SUPPLIED WITH THE ACCA,
THE CONTRACTOR SHALL ORIENT THE COAXIAL 'CABLE ENTRANCE INTO THE ACCA IN ACCORDANCE WITH THE DIRECTION
ISSUED BY EACH MTA. THE FIGURE SHOWN BELOW INDICATES THE PROPER ORIENTATION FOR THE COAXIAL CABLE
ENTRANCE INTO THE ACCA.
HATCH PLATE/BOOT ON REAR OF ACCA
SPARE KNOCKOUTS (TYP.
CLOUGH, HARBOUR
CHA� ASSOCIATES LLP
DRAWING COPYRIGHT ENGINEERS, SURVEYORS, PLANNERS
p tsss LANDSCAPE ARCHITECTS
171 PARK AVENUE — WEST SPRINGFIELD, MA - 01.090
P.O. BOX 626 413-746-0796
CHA Project No. 7472-73
TELCO RECEPTACLE (TYP.)
YARMOUTH, PROSPECT HILL WATER TANK
YARMOUTH WATER DEPT.
OLD HYANNIS ROAD/ PROSPECT HILL
YARMOUTH, MA. 02664
E
An
Sprint Spectrum, LP
v , `
CROSSROADS CORPORATE CENTER
1 INTERNATIONAL BOULEVARD, SUITE 800
' MAHWAH, NEW JERSEY 07495
BOSTON MTA
SITE NO.: BS23XC66382
3
C. EMERGENCY GENERATORS:
1. THE GENERAC EMERGENCY GENERATORS SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS INSTALLATION
INSTRUCTIONS THAT ARE SHIPPED WITH THE UNITS.
2. THE START—UP OF THE GENERAC EMERGENCY GENERATOR SHALL BE PERFORMED BY CERTIFIED ELECTRICAL DISTRIBUTORS
(CED) OR ANOTHER FACTORY AUTHORIZED AGENT. THE FIELD SHALL COORDINATE THIS EFFORT WITH TOM CARROLL OF
CED [1-800-727-9119] TO ENSURE THAT THE SAFETY AND WARRANTY ISSUES ARE ADDRESSED.
D. ELECTRICAL:
1. THE ELECTRICAL RACEWAY INSTALLED FROM THE MINI—PPC TO THE PRIMARY RADIO CABINET, FURNISHED BY LUCENT,
SHALL HAVE AN 1 1/4" MALE CONNECTOR/REDUCER FOR THE TIE TO THE ELECTRICAL FITTING ON THE CABINET. THIS
MAY BE ACCOMPLISHED USING EITHER A 1 1/4" CONDUIT, 1 1/4" FLEXIBLE CONDUIT OR A 1 1/4" BUSHING.
SPARE KNOCKOUTS (TYP.)
5" DIA. COMMON PORT FOR COAX
CABLE ENTRANCE INTO ACCA.
GROUND LEAD EXIT PORT WITH
GROMMET (TYP. OF 2)
GAMMA
AZIMUTH
G1
B2
ALPHA
AZIMUTH
oo
A2'
B1
4LIiA
BETA
AZIMUTH
Al =
ALPHA FACE, RED (SINGLE
STRIPE)
RIGHT ANTENNA AS VIEWED
WHILE
LOOKING AT THE FACE OF
THE ARRAY
A2
= ALPHA FACE, RED/RED (DOUBLE STRIPE)
LEFT ANTENNA AS VIEWED
WHILE
ISSUED FOR CONSTRUCTION
LOOKING AT THE FACE OF
THE ARRAY
B1 =
BETA FACE, WHITE (SINGLE
STRIPE)
ISSUED FOR REVIEW
RIGHT ANTENNA AS VIEWED
WHILE
JPS
LOOKING AT THE FACE OF
THE ARRAY
82
= BETA FACE, WHITE/WHITE (DOUBLE STRIPE)
CHK
LEFT ANTENNA AS VIEWED
WHILE
DESIGNED B.R.B.
LOOKING AT THE FACE OF
THE ARRAY
G1 =
GAMMA FACE, BLUE (SINGLE
STRIPE)
RIGHT ANTENNA AS VIEWED
WHILE
LOOKING AT THE FACE OF
THE ARRAY
G2
= GAMMA FACE, BLUE/BLUE
(DOUBLE STRIPE)
LEFT ANTENNA AS VIEWED
WHILE
LOOKING AT THE FACE OF
THE ARRAY
4LIiA
I
8/4
ISSUED FOR CONSTRUCTION
K8K
KJW
JPS
2%9
ISSUED FOR REVIEW
JRH
KJW
JPS
No.
DATE
REVISIONS
BY
CHK
APP'D
SCALE N.T.S
DESIGNED B.R.B.
DRAWt�� : J.R.H.7
2
Sprint Spectrum, LP
CELL SITE INSTALLATION NOTES
JOB NO. DRAWING NUMBER REV
RBA663C7 1
22 x 34 D SIZ