HomeMy WebLinkAboutBlueberry Path - Kingsway - Bldg125 Fire Protection - Ground FloorTEST WrDRANT
FIRST FLQ.
GRADE
i r
RiC' R
i
I
® GROUND =LR
L I NODE L WATER MAIN
HYDRAUL G
NOTE: THIS DETAIL IS INTENDED FOR HYDRAILIC CALCJLATICN RE=ER=NCE
ONLY AND IS NOT A CCN5 7 RUCTION DETAIL.
UJATER `LRVICE DETAIL
FOR I-J"CRGJLIC CALCULATIONS Cti_Y
GROUND FLOOR FLAN
SCALE:
EXTERIOR
I
TRERICE NO 600C PRESSURE
WALL
GAUGE (0-160 PSI), INSTALL
CENTRAL MODEL LF RESIDENTIAL
WITH NO. 865 GAUGE COCK.
FIRE DEPT. CONN
POTTER MODEL VSR-SF
OF A TYPE A SIZE
PIPE RISER THROUGH FLOOR
C
FLOW SWITCH.
APPROVED BY
FD
..LO
CNK VLv
LOCAL
z
FIRST FLOOR
SUPERVISED
BALL VALVE
(TYPICAL)
w
2
i���" FILL CUP /
I
3E
co(0
I/2 "
W
LI P
O
x
O
�
REDUCED PR=55uQE
BACKFLOW PR=_v.
AP'iTROL EXP.
0 �
(Y
ww
TANK MODEL
0
WATTS 02Q CR
NO. ST -5
AMES 400C1✓.
,
�
FOUNDATION -
D, 0. VLV
TO DRAIN
�--i Y)
11/2" FIRE
SERVICE
RISER DET,41L
NTS WITH GLYCOL
REFER TO RISER DETAIL
FIRE WATER SERVICE
BY OTHERS
GENERAL NOTES
1. All work shall be installed in a First-class manner consistent with the best current
practices. Items not shown on the Drawing, but which are necessary to make a
complete Fire Protection System, shall be furnished and installed as part of
the work under this contract.
2. All work shall be installed in compliance with NFPA 13R and all governing Codes.
3. All materials and workmanship shall carry the standard warrarnty against all defects
For a period not less than one (1) year from the date of acceptance of the work.
Any fault due to defective materials, equipment, or workmanship which may develop
within that period shall be made good, forthwith, by and at the expense of the
Mechanical Contractor, including any damage done to areas, materials, and other
systems resulting From this failure.
4. All layouts are diagrammatic and final arrangement shall suit field conditions.
5. Cutting and patching of masonry, concrete, wood framing and other parts or
the structure shall be performed by the General Contractor.
6. All piping shall be CPVC and/or Schedule 40 steel.
1. A final system test shall be conducted in the presence of the Yarmouth Fire Dept.
S. The sprinkler system shat be Filled with a non-toxic antifreeze solution equal to
FireFighter freeze protection solution speciricaly listed for use with BaizeMaster CPVC.
HYDRANT TEST
TEST DATE 10rv98
TES1; HYDRANT - 44 PSI STATIC
1 38 PSI RESIDUAL
FLOW HYDRANT - 662 GPM
AVAILABLE RESIDUAL PRESSURi= - 43 PSI
TEST PERFOR"iiED BY ARH ENGINEERING, INC.
SPRINKLER LEGEND
HYDRAULICALLY DESIGNED SPRINKLER SYSTEM
NFPA 13 R "UJET SYSTEM"
DESIGN AREA - DWELLING UNIT
NO. OF DESIGN SPRINKLERS - 4
SPRINKLER DEMAND FLOW - 33.18 GPM
INSIDE NOSE STREAM - 0
OUTSIDE HOSE STREAM - 100 GPM
RESIDUAL PRESSURE AVAILABLE - 43 SS PSI
RESIDUAL PRESSURE REQUIRED - 25.53 PSI
EXCESS AVAILABLE PRESSURE - 18.45 PSI
14 SPRINKLERS - CENTRAL MODEL LF PENDANT
k=3.0, LISTED RESIDENTAL
2 SPRINKLERS - CENTRAL MODEL LF SIDEWALL
115'-346", k=3.5, LISTED RESIDENTAL
YAR"'VIOUTH FIRE DEPT,
{
DEPUTY Ci 17"t
CENTRAL MODEL LF RESIDENTAIL
SIDE WALL, 3/8" ORIFICE, 3.5 K (115')
RECESSED ESCUTCHEON (WHITE)
CENTRAL MODEL LF RESIDENTIAL
i
PENDANT, 3/8" ORIFICE, 3.0 K 055')
RECESSED ESCUTCHEON (WHITE)
U
PIPE RISER THROUGH FLOOR
C
PIPE DROP
HYDRAULICALLY DESIGNED SPRINKLER SYSTEM
NFPA 13 R "UJET SYSTEM"
DESIGN AREA - DWELLING UNIT
NO. OF DESIGN SPRINKLERS - 4
SPRINKLER DEMAND FLOW - 33.18 GPM
INSIDE NOSE STREAM - 0
OUTSIDE HOSE STREAM - 100 GPM
RESIDUAL PRESSURE AVAILABLE - 43 SS PSI
RESIDUAL PRESSURE REQUIRED - 25.53 PSI
EXCESS AVAILABLE PRESSURE - 18.45 PSI
14 SPRINKLERS - CENTRAL MODEL LF PENDANT
k=3.0, LISTED RESIDENTAL
2 SPRINKLERS - CENTRAL MODEL LF SIDEWALL
115'-346", k=3.5, LISTED RESIDENTAL
YAR"'VIOUTH FIRE DEPT,
{
DEPUTY Ci 17"t
°
04
u7
CL
i
ca
Q
U
M
W
� �g
w
..LO
z
a
°
u7
I
Uj
^o
03
nz
o
w
..LO
z
W
z
�
w
co(0
W
N to
CO CQ
O
x
O
�
Qw
ww
E 4o
F,
�--i Y)
DRAWING TITLE:
FIRE PROTECTION
GROUND FLOOR
DRAWN BY:
NDG
CHECKED BY:
DAG
DATE:
FEB. 21, 2000
REVISED:
PROJECT NO.
48331
SHEET