Loading...
HomeMy WebLinkAbout2017 Feb 07 - Email from EAS Survey vonHone, Amy i From: Edward Stone<eas.survey@yahoo.com> ' Sent: Tuesday, February 07, 2017 5:10 PM ; To: vonHone, Amy , Subject: Re: 371 Route 28, Yarmouth Hi Amy Will review the elevations The existing septic tank is a very strange animal The construction unlike I've only seen ' a couple of time in 50 years I've run into this type in Wareham and Dave has also seen it there and around Carver and ; Rochester There is a built in conc baffle that is a good foot and a half out into the tank from the inside end with a ' circulation hole about two feet plus down in the baffle One inlet comes in at above the usual tank height The other ; comes in below the other inlet but still maintains the four foot depth to the inside bottom of the tank Unusual but effective The tank for a multi family was reasonably clean Some sludge isolated in the baffle compartment and zero ' scum and sludge in the rest of the tank Thanks Ed Sent from my iPhone ! � On Feb 7, 2017,at 2:46 PM,vonHone,Amy<AVonHone@varmouth.ma.us>wrote: � Hi Ed- Just reviewed this plan and have a couple of comments to address: 1. The breakout elevation of the leach facility is the top of the leach unit (EL. 10.27). This ' will require the top of the polyliner to be at EL. 10.27 and be installed around the entire leach facility to meet breakout. Your regrading contours will need to be adjusted to � accommodate the higher liner and still meet the 3:1 slope. You will probably also need to raise the wall by one tie to meet the 3:1 slope unless you bring the top of wall up to the same elevation as breakout. 2. The 2 inverts from the foundations on page 2 are shown with a 6" difference into the septic tank. Is one pipe entering the existing septic tank 6" higher than the other pipe? If so, what is the total capacity of the tank and was one of the tank inlets altered to accommodate the 6" difference? 3. Page 3, General Notes#14 needs to be altered to state Polyliner to be placed around entire leaching area. - I have attached a copy of the marked up plan for your review. Please call or email with questions. � Thanks, Amy Amy L.von Hone, R.S., C.H.O. Assistant Health Director i Yarmouth Health Department 1146 Route 28 South Yarmouth, MA 02664 ; i (0)508-398-2231 X1241 � (F) 508-760-3472 avonhoneCc�varmouth.ma.us <371 RTE 28 SEPTIC PLAN.PDF> i