TARGET INSPECTIONS
SUMMARY OF TOTAL DUCT LEAKAGE TESTING
RESULTS FOR:
Heating and Cooling Concepts
Project Located at:
77 Silver Leaf Lane
West Yarmouth, MA
Project Number: 1502
Report Version: 1.0
Target Inspections
'Steven Grevelis
P.O. Box 444
West Dennis, MA 02670 •
Phone: 508-737-4289
Email:steve@targetinspections.com
www.targetinspections.com
Certified HERS Rater(RIN—4958795),
&Certified Microbial Professional
Enclosures: •
- Summary of Results
- Retrotec Reports
- Calibration Data
PASS
Based on testing of the total duct systems,the observed total duct leakage at the time of
testing of the system was at or below the allowable limits (4 cfm per 100 sq ft)as set forth in
IECC 2015 with tested results of 3.7 cfm per 100 sq ft.
Target Inspections Summary of Testing Results Copyright 2010/2011
Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any findings may or may not be changed due to
environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections Is not responsible for Improvements as a result
of our inspection.
Page 1 of 4
TARGET INSPECTIONS
Testing Conditions
September 7, 2018
Wind— North 8 mph
Weather—Cloudy
Outdoor Temperature—73° F
Outdoor Relative Humidity- 93%
Barometric Pressure—30.1"
Target Inspections Summary of Testing Results Copyright 2010/2011
Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any endings may or may not be changed due to
environmental conditions or contractor decisionsractions that are beyond our control.Target Inspections is not responsible for improvements as a result
of our inspection.
Page 2 of 4
TARGET INSPECTIONS
Total Duct Leakage Test—Summary of Results
Test Date: 9/7/2018 Technician:Steven Grevelis
Test File: 1502_Heating Concepts_77 Silver Leaf Ln_W Yarmouth_Duct
Building Address: 77 Silver Leaf Lane
West Yarmouth, MA
Equipment Used
Retrotec—DU-200 Duct Blaster w/DM32 Manometer
Serial Numbers: FT9010674/404468
DM32 Factory Calibration Date: 11-05-2015
DM32 Next Factory Calibration Date by: 10-15-2020
Field Calibration of DU-200 Performed:06-26-2018
Tubing Integrity Testing Performed and Passed On-Site
The home has 1 system outside of conditioned space that was tested:
Test Results
In accordance with IECC 2015 the maximum allowable total duct leakage is 4 cfm per 100 sq ft
at+/-25 pa in the rough or final stage with the air handler installed. Currently MA Stretch Code
Towns must meet the same requirements.
Square footage of conditioned space tested is 1056 square feet:
- Maximum allowable leakage of 4 cfm per 100 sq ft=42.24 cfm: (4 cfm x 1056 sq ft/100
sq ft=42.24 cfm)
System#1—Servicing the 151 Floor—
- Tested total duct leakage was 39.59 cfm @-25.0 pa
Total duct leakage was 39.59 cfm=3.7 cfm per 100 sq ft
cfm=cubic feet per minute pa=pascals sq ft=square feet
Target Inspections Summary of Testing Results Copyright 2010/2011
Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any findings may or may not be changed due to
environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections is not responsible for Improvements as a result
of our inspection.
Page 3 of 4
TARGET INSPECTIONS
Conclusion
Based on testing of the total duct systems,the observed total duct leakage at the time of
testing of the one (1)system was at or below the allowable limits (4 cfm per 100 sq ft) as set
forth in IECC 2015 with tested results of 3.7 dm per 100 sq ft.
The systems as installed meets the recommended guidelines and no further sealing is required.
Note 1:Square footage provided by town assessor web page.
Note 2: Baseline measurements are based on 60 second averages.
The systems as installed meet the recommended guidelines and no further sealing is required.
3 4•••••---4.
rerA,'rf,' '
a� ` a
I
@ -24.8
; in 39.59
IV,lI a....
114
l (. bitVM am. S..In,.
W
d C ij, h 4 /
' Y
F ' a .!i.. . :ate ' 140,4'
PHOTO SUMMARY PHOTO SUMMARY
Setup of tested system. Manometer reading of tested system.
This inspection report is solely based on the conditions within the defined area at the time of inspection
only and makes no express or implied warrant or guarantee as to future changes in condition or
conditions outside of the described job scope.
Sincerely,
a.
Steven Grevelis
Certified HERS Rater(RIN—4958795),
&Certified Microbial Professional
Target Inspections Summary of Testing Results Copyright 2010/2011
Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any 6ndmgs may or may not be changed due to
environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections Is not responsible for improvements as a result
of our inspection.
Page 4 of 4
j ilitecJ Test Date:2017-09-13
Duct Leakage
Test Report
Client Tester
Building Description Single Family/1st Floor Company Target Inspections
Building Address 77 Silver Leaf Lane Address 24 School Street,Unit 6
West Yarmouth,MA West Dennis,MA 02670
Contact Nunzi Napolitano/Heating&Cooling Technician Steven Grevelis
Phone (508)498-4489 Phone (888)280-2108
Test Type Total Duct Leakage Gauge S/N 404468
Test Equipment Retrotec DU200 Fan S/N FT9010674
Building and Duct Details
Conditioned Floor Area 1056.0 sq ft
Supply Return
Average Duct Operating Pressure 25.0 Pa 25.0 Pa
Leakage Split 50% 50%
Leakage Penalty 100% 50%
Leakage Data
Baseline Pressure 0.1 Pa
Depressurization
Duct Test Pressure -25.1 Pa
Duct Leakage 40 CFM
Leakage Area 7.3 sq In
Leakage constant, C 5.73
Leakage Exponent 0.60(assumed)
Leakage Results
Total Duct Leakage 40 CFM at 25 Pa
Leakage/Conditioned Floor Area 0.037 CFM/sq ft at 25 Pa
3.7 CFM/100 sq ft at 25 Pa
37 CFM/1,000 sq ft at 25 Pa
•
1r
Gauge Calibration
Verification Report
Calibrated Equipment Calibration Facility
Serial Number 404377 Company Retrotee,Inc.
Firmware Version 2.3 Build 62 Address 1060 E Pole Rd i
Gauge Type DM32
Manufacturer Retrotec,Inc. City Everson
Calibration Date 2015-11-13 State WA
AutoVerification Version 1.1.2 Zip Code 98247 1
Master Gauge Reference FC0550 5N0704353 County USA
Phone (360)738-9835
Technician Mike Shtunyuk
Pressure calibration verification data
The accuracy of this dual channel(DM32)pressure gauge was calibrated against one of two NIST traceable Fumess 550(master g uge)pressure
calibrators,0704353 and 0907002,whose pressure accuracies are 3 0.15%of Its reading. A 32 point verification check was perfo d after
calibration to verify pressure readings are accurate when used with Door Fans.
Master gauge Calibrated gauge Calibrated gauge
Channel A Channel B
Pressure • Pressure ' • Error Pressure _ .. Error-
' (Pa) ._ . • -- (Pa) • ' ;:. . (%) ! (Pa). (%) . •
400.0 400.0 0.0% 400.1 0.0%
•
300.0 300.1 0.0% 300.3 0.1%
200.0 200.5 0.2% 200.3 0.2%
150.0 150.7 0.5% 150.7 0.5%
100.0 100.3 0.3% 100.9 0.9%
75.0 75.4 0.5% 75.3 0.4%
50.0 50.1 0.2% 50.4 0.8%
25.0 25.2 0.8% 25.1 0.4%
-25.0 -24.8 0.8% -25.1 0.4%
-50.0 -50.0 0.0% -49.7 0.6%
-75.0 -75.2 0.3% -75.0 0.0%
-100.0 -100.4 0.4% -99.9 0.1%
-150.0 -150.2 0.1% -150.4 0.3%
-200.0 -200.5 0.2% -200.5 0.2%
-300.0 -301.0 0.3% 300.8 0.2%
-400.0 -401.3 0.3% -401.1 0.3%
Digital pressure gauges should be checked for calibration every five years.
Calibration for the gauge should be checked before:2020-09-30
This gauge meets the accuracy requirements of the following Standards:
NFPA 2001 EN13829 ATTMA:TS1 ASTM E779-10 CGSB 15014520 EN15004 i RESNET
31 Pa 32 Pa 32Pa 35%or0.25Pa 31 Pa 31 Pa *1 Pa 1%or0.5 Pa
2(10 to 50)Pa (up to 360 Pa) (up to 3100 Pa) whichever Is greater - (up to 350 Pa) (up to 3S0 Pa) (up to 3100 Pa) yeti chaser Is greater
•
i.
,111
TARGET INSPECTIONS
ent Field Calibration Record for Retrotec Duct Blast Fan
rial Number: FT9O1O674 Part Number: FN253
Technician CFM @ 25 Pressurized=P Comments
n Pa on Mid Depressurized
Range =D
97-106 is a
Pass. Field
Steven 104=Pass D calibration
Grevelis plate used
(p/n: DU-
159)
etc
240
103.9
Mid CFM Q 2J'0
V S
Seeking Value 25,0 h � ..
nometer during field calibration of Duct Blast fan.