HomeMy WebLinkAboutDuct Leakage Test • - QL0Srn - j9 - oo)o) 3 RECEIVED [ OCT 1 - 2018 1 BUILDING DEPARTMENT ■■ er' _. TARGET INSPECTIONS SUMMARY OF TOTAL DUCT LEAKAGE TESTING RESULTS FOR: Heating and Cooling Concepts Project Located at: 77 Silver Leaf Lane West Yarmouth, MA Project Number: 1502 Report Version: 1.0 Target Inspections 'Steven Grevelis P.O. Box 444 West Dennis, MA 02670 • Phone: 508-737-4289 Email:steve@targetinspections.com www.targetinspections.com Certified HERS Rater(RIN—4958795), &Certified Microbial Professional Enclosures: • - Summary of Results - Retrotec Reports - Calibration Data PASS Based on testing of the total duct systems,the observed total duct leakage at the time of testing of the system was at or below the allowable limits (4 cfm per 100 sq ft)as set forth in IECC 2015 with tested results of 3.7 cfm per 100 sq ft. Target Inspections Summary of Testing Results Copyright 2010/2011 Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any findings may or may not be changed due to environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections Is not responsible for Improvements as a result of our inspection. Page 1 of 4 TARGET INSPECTIONS Testing Conditions September 7, 2018 Wind— North 8 mph Weather—Cloudy Outdoor Temperature—73° F Outdoor Relative Humidity- 93% Barometric Pressure—30.1" Target Inspections Summary of Testing Results Copyright 2010/2011 Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any endings may or may not be changed due to environmental conditions or contractor decisionsractions that are beyond our control.Target Inspections is not responsible for improvements as a result of our inspection. Page 2 of 4 TARGET INSPECTIONS Total Duct Leakage Test—Summary of Results Test Date: 9/7/2018 Technician:Steven Grevelis Test File: 1502_Heating Concepts_77 Silver Leaf Ln_W Yarmouth_Duct Building Address: 77 Silver Leaf Lane West Yarmouth, MA Equipment Used Retrotec—DU-200 Duct Blaster w/DM32 Manometer Serial Numbers: FT9010674/404468 DM32 Factory Calibration Date: 11-05-2015 DM32 Next Factory Calibration Date by: 10-15-2020 Field Calibration of DU-200 Performed:06-26-2018 Tubing Integrity Testing Performed and Passed On-Site The home has 1 system outside of conditioned space that was tested: Test Results In accordance with IECC 2015 the maximum allowable total duct leakage is 4 cfm per 100 sq ft at+/-25 pa in the rough or final stage with the air handler installed. Currently MA Stretch Code Towns must meet the same requirements. Square footage of conditioned space tested is 1056 square feet: - Maximum allowable leakage of 4 cfm per 100 sq ft=42.24 cfm: (4 cfm x 1056 sq ft/100 sq ft=42.24 cfm) System#1—Servicing the 151 Floor— - Tested total duct leakage was 39.59 cfm @-25.0 pa Total duct leakage was 39.59 cfm=3.7 cfm per 100 sq ft cfm=cubic feet per minute pa=pascals sq ft=square feet Target Inspections Summary of Testing Results Copyright 2010/2011 Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any findings may or may not be changed due to environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections is not responsible for Improvements as a result of our inspection. Page 3 of 4 TARGET INSPECTIONS Conclusion Based on testing of the total duct systems,the observed total duct leakage at the time of testing of the one (1)system was at or below the allowable limits (4 cfm per 100 sq ft) as set forth in IECC 2015 with tested results of 3.7 dm per 100 sq ft. The systems as installed meets the recommended guidelines and no further sealing is required. Note 1:Square footage provided by town assessor web page. Note 2: Baseline measurements are based on 60 second averages. The systems as installed meet the recommended guidelines and no further sealing is required. 3 4•••••---4. rerA,'rf,' ' a� ` a I @ -24.8 ; in 39.59 IV,lI a.... 114 l (. bitVM am. S..In,. W d C ij, h 4 / ' Y F ' a .!i.. . :ate ' 140,4' PHOTO SUMMARY PHOTO SUMMARY Setup of tested system. Manometer reading of tested system. This inspection report is solely based on the conditions within the defined area at the time of inspection only and makes no express or implied warrant or guarantee as to future changes in condition or conditions outside of the described job scope. Sincerely, a. Steven Grevelis Certified HERS Rater(RIN—4958795), &Certified Microbial Professional Target Inspections Summary of Testing Results Copyright 2010/2011 Disclaimer:Although we seek to provide the most accurate information possible we cannot guarantee any 6ndmgs may or may not be changed due to environmental conditions or contractor decisions/actions that are beyond our control.Target Inspections Is not responsible for improvements as a result of our inspection. Page 4 of 4 j ilitecJ Test Date:2017-09-13 Duct Leakage Test Report Client Tester Building Description Single Family/1st Floor Company Target Inspections Building Address 77 Silver Leaf Lane Address 24 School Street,Unit 6 West Yarmouth,MA West Dennis,MA 02670 Contact Nunzi Napolitano/Heating&Cooling Technician Steven Grevelis Phone (508)498-4489 Phone (888)280-2108 Test Type Total Duct Leakage Gauge S/N 404468 Test Equipment Retrotec DU200 Fan S/N FT9010674 Building and Duct Details Conditioned Floor Area 1056.0 sq ft Supply Return Average Duct Operating Pressure 25.0 Pa 25.0 Pa Leakage Split 50% 50% Leakage Penalty 100% 50% Leakage Data Baseline Pressure 0.1 Pa Depressurization Duct Test Pressure -25.1 Pa Duct Leakage 40 CFM Leakage Area 7.3 sq In Leakage constant, C 5.73 Leakage Exponent 0.60(assumed) Leakage Results Total Duct Leakage 40 CFM at 25 Pa Leakage/Conditioned Floor Area 0.037 CFM/sq ft at 25 Pa 3.7 CFM/100 sq ft at 25 Pa 37 CFM/1,000 sq ft at 25 Pa • 1r Gauge Calibration Verification Report Calibrated Equipment Calibration Facility Serial Number 404377 Company Retrotee,Inc. Firmware Version 2.3 Build 62 Address 1060 E Pole Rd i Gauge Type DM32 Manufacturer Retrotec,Inc. City Everson Calibration Date 2015-11-13 State WA AutoVerification Version 1.1.2 Zip Code 98247 1 Master Gauge Reference FC0550 5N0704353 County USA Phone (360)738-9835 Technician Mike Shtunyuk Pressure calibration verification data The accuracy of this dual channel(DM32)pressure gauge was calibrated against one of two NIST traceable Fumess 550(master g uge)pressure calibrators,0704353 and 0907002,whose pressure accuracies are 3 0.15%of Its reading. A 32 point verification check was perfo d after calibration to verify pressure readings are accurate when used with Door Fans. Master gauge Calibrated gauge Calibrated gauge Channel A Channel B Pressure • Pressure ' • Error Pressure _ .. Error- ' (Pa) ._ . • -- (Pa) • ' ;:. . (%) ! (Pa). (%) . • 400.0 400.0 0.0% 400.1 0.0% • 300.0 300.1 0.0% 300.3 0.1% 200.0 200.5 0.2% 200.3 0.2% 150.0 150.7 0.5% 150.7 0.5% 100.0 100.3 0.3% 100.9 0.9% 75.0 75.4 0.5% 75.3 0.4% 50.0 50.1 0.2% 50.4 0.8% 25.0 25.2 0.8% 25.1 0.4% -25.0 -24.8 0.8% -25.1 0.4% -50.0 -50.0 0.0% -49.7 0.6% -75.0 -75.2 0.3% -75.0 0.0% -100.0 -100.4 0.4% -99.9 0.1% -150.0 -150.2 0.1% -150.4 0.3% -200.0 -200.5 0.2% -200.5 0.2% -300.0 -301.0 0.3% 300.8 0.2% -400.0 -401.3 0.3% -401.1 0.3% Digital pressure gauges should be checked for calibration every five years. Calibration for the gauge should be checked before:2020-09-30 This gauge meets the accuracy requirements of the following Standards: NFPA 2001 EN13829 ATTMA:TS1 ASTM E779-10 CGSB 15014520 EN15004 i RESNET 31 Pa 32 Pa 32Pa 35%or0.25Pa 31 Pa 31 Pa *1 Pa 1%or0.5 Pa 2(10 to 50)Pa (up to 360 Pa) (up to 3100 Pa) whichever Is greater - (up to 350 Pa) (up to 3S0 Pa) (up to 3100 Pa) yeti chaser Is greater • i. ,111 TARGET INSPECTIONS ent Field Calibration Record for Retrotec Duct Blast Fan rial Number: FT9O1O674 Part Number: FN253 Technician CFM @ 25 Pressurized=P Comments n Pa on Mid Depressurized Range =D 97-106 is a Pass. Field Steven 104=Pass D calibration Grevelis plate used (p/n: DU- 159) etc 240 103.9 Mid CFM Q 2J'0 V S Seeking Value 25,0 h � .. nometer during field calibration of Duct Blast fan.