HomeMy WebLinkAboutBLD-19-1418Calculation results for Design Area 1
- 3rd Floor -Residential
Calculation -results for Design Area 3
- Attic
company print no dated
This system as shown on.
w:- -- - company print no dated
for Yarmouth Apartments - Building A
at 881 Route 28
This system as shown on
company print no dated
contract no is designed
to discharge at a rate of 0.1 gpm/ft2 (L/min/m2) of floor area over
for Yarmouth Apartments - Building A
at 881 Route 28 -
a maximum area of 400 ft2 when supplied
with water at a rate of 99.9 qpm at 52.8 psi at the base of the riser.
for Yarmouth Apartments - Building A
at 881 Route 28
Hose stream allowance of
Is Included in the above
contract no is designed to discharge at a rate of 0.1 gpm/ft2 (L/min/m2) of floor area over
I,/2 -AND
LARGER sv+1Ep
Occupancy classification: Light Hazard
contract no is designed to discharge at a rate of 0.1 gpm/ft2 (L/min/m2) of floor area over
BLACK E' -ACK
STEEL STEEL
..
a maximum area of 360 ft2 when supplied with water at a rate of 57.6 qpm at 48.8 psi at the base of the riser.
System Type: Wet
TYPE
a maximum area of 600 ft2 when supplied with water at a rate of 248.9 gpm at 57.4 psi at the base of the riser.
Maximum storage height:
Maximum velocity: 15.99 ft/s
Hose stream allowance of
is included in the above.
Storage arrangement:
SCHEDULE
Hose stream allowance of
is included in the above.
Flow from In -Rack sprinklers:
0 gpm
Occupancy classification: NFPA 13 - Residential Number of heads flowing: 4
I
Flow from Overhead sprinklers
Occupancy classification: Light
Number of heads flowing: 16
D.I. GRV BUCK
&HOLE CUT CAST IRON
Flow from Inside Hoses:
Commodity classification:
System Type: Wet
FITTINGS
Flow from Outside Hoses:
Commodity classification:
System Type: Dry
Other fixed flows:
Maximum storage height:
Maximum velocity: 13.74 ft/s
Total flow in system piping:
Maximum storage height:
Maximum velocity: 11.52 ft/s
PEAK FIRE PROTECTION, INC,
Additional flow at/beyond source:
Storage arrangement:
Total of all flows:
"199.9 gpm
Storage arrangement:
1
Attic Plan,''
Flow from In -Rack sprinklers:
`: 0 gpm
Pressure Required at Source: 48.8 psi
Flow from In -Rack sprinklers`
0 gpm
Pressure Required at Source: 57.4 psi
Flow from Overhead sprinklers
57.6 gpm
Pressure Available at Source: 63.9 psi
Flow from Overhead sprinklers:
248.9 gpm
Pressure Available at Source: 63.4 psi
Flow from Inside Hoses:
0 gpm
Surplus Pressure at Source: 15 psi
Flow from Inside Hoses:
0 gpm
Surplus Pressure at Source: 6 psi
13.781-232-7272
Flow from Outside Hoses:
0 gpm
I
Flow from Outside Hoses:
0 gpm
Other fixed flows:
0 qpm
CONTRACTOR: LIC. # SC -210022
EXPIRES: 9-30-19
Other fixed flows:
0 gpm
I , ..._
SYM
Total flow in system piping.
57.6 gpm
FINISH
TEMP
Total flow in system piping:
248.9 gpm
COUNT SPACING MODEL
-
Additional flow at/beyond source
100 qpm
Additional flow at/beyond source:
100 qpm
Total of all flows:157.6
gpm
Total of all flows:
348.9 gpm
C I 1 f It f D' A ea 2 - 3rd Floor - Hallway
a can ror u Ioesu s ea g" r
1. All materials & installations of this automatic fire sprinkler system to
This system as shown on
company print no dated
WET
for Yarmouth Apartments - Building A
at 881 Route 28
APPLICATIONS)
conform to N,F.P.A. #13, #,14, #20, #22,& #24
contract no is designed
to discharge at a rate of 0.1 gpm/ft2 (L/min/m2) of floor area over
BRANCHLINES
a maximum area of 400 ft2 when supplied
with water at a rate of 99.9 qpm at 52.8 psi at the base of the riser.
3
-
2. System to be hydrostatically tested. 200 SI for 2 hours - per `
Y Y Y @ p
N.F.P.A. #13.. -
Hose stream allowance of
Is Included in the above
2 -AND
I SMALLER
I,/2 -AND
LARGER sv+1Ep
Occupancy classification: Light Hazard
Number of heads flowing: 7
BLACK E' -ACK
STEEL STEEL
..
Commodity classification:
System Type: Wet
TYPE
scH.,o1SCH.
Maximum storage height:
Maximum velocity: 15.99 ft/s
,.
Storage arrangement:
SCHEDULE
GROOVED
THREADED
Flow from In -Rack sprinklers:
0 gpm
Pressure Required at Source: 52.8 psi :.
I
Flow from Overhead sprinklers
99.9 gpm
Pressure Available at Source: 63.8 psi
D.I. GRV BUCK
&HOLE CUT CAST IRON
Flow from Inside Hoses:
0 gpm
Surplus Pressure at Source: 10.9 psi
FITTINGS
Flow from Outside Hoses:
0 gpm
-
Other fixed flows:
0 qpm
48Z1
F GISTE�` .
Total flow in system piping:
99.9 gpm
PEAK FIRE PROTECTION, INC,
Additional flow at/beyond source:
100 qpm
Total of all flows:
"199.9 gpm
INDICATING BUTTERFLY
VALVE WITH TAMPER SWITCH
CHECK VALVE
"r WATER FLOW SWITCH
FEED MAIN
W 1 " X V-6"
W
L
Z UNION TEST AND DRAIN DEVICE
Z WITH PRESSURE RELIEF
Q ORIFICE GIVING FLOW EQUIVALENT
TO S6dA,LLEST SPRINKLER ORIFICE
IN SPRINKLER SYSTEM
ZONE CONTROL VALVE DETAIL
nts
PIPING NOTES
RESIDENTIAL
BRANCHLINES
2" AND
SMALLER
CPVC
SCH. 40
SOCKETS
CPVC FITTINGS
is
L_
I
HANGER DETAIL
Wood Joist Member f
f Wood Joist Member
- 3/8" Hangermate.
3/8"Hangermale i
I
- 3 - 3/8" A.T.Rod
!B" A.T.Rod
I
i
1
1e7 - Hanger Ring
! 'Hanger Ring i
Sprinkler Pipe Sprinkler Pipe -
!
1. All materials & installations of this automatic fire sprinkler system to
WET
DRY
RESTRAINT COMPONENTS (TYPICAL
APPLICATIONS)
conform to N,F.P.A. #13, #,14, #20, #22,& #24
PIPE LINE
MAINS
BRANCHLINES
MAINS Bc x.p^yr_IN=S
-
3
-
2. System to be hydrostatically tested. 200 SI for 2 hours - per `
Y Y Y @ p
N.F.P.A. #13.. -
SIZE
„/2"AND
LARGER _
2 -AND
I SMALLER
I,/2 -AND
LARGER sv+1Ep
BLACK
STEEL
'BLACK
(STEEL
BLACK E' -ACK
STEEL STEEL
..
._
_ _. ; -
\/ ers
3. All electrical & paintingto be provided b others.
TYPE
scH.,o1SCH.
40
SCH. 10 SCH 47
,.
4. Pi a sizin er hydraulic calculations
p 9 p Y
SCHEDULE
GROOVED
THREADED
GROOVED T OE+.DED
:....
.. ....': .. -.. z,
Is,
I
JOINTS....
D I GRV
D.I.
&HOLE CUT
BLACK
CASTIRON
D.I. GRV BUCK
&HOLE CUT CAST IRON
. -. .. . .: j. .... .. . .. :. .:
11 V
FITTINGS
1!8=, 0
.. SCALE .. .:.
RESIDENTIAL
BRANCHLINES
2" AND
SMALLER
CPVC
SCH. 40
SOCKETS
CPVC FITTINGS
is
L_
I
HANGER DETAIL
Wood Joist Member f
f Wood Joist Member
- 3/8" Hangermate.
3/8"Hangermale i
I
- 3 - 3/8" A.T.Rod
!B" A.T.Rod
I
i
1
1e7 - Hanger Ring
! 'Hanger Ring i
Sprinkler Pipe Sprinkler Pipe -
!
SEISMIC
RESTRAINT COMPONENTS (TYPICAL
APPLICATIONS)
-:
NOT TO SCALE
z
jH OF AkS�
1
JASON CATALFO
I
I
KAMAN
11 V
PRE PROTECTION
H
-
48Z1
F GISTE�` .
a".
PEAK FIRE PROTECTION, INC,
No- RevisionsD
�aiAL
4 BROOK ST. SUITE 25E
1
Attic Plan,''
SCITUATE MA. 02066
SPRINKLER LEGEND
.M..__�.�r
'FRI, r
13.781-232-7272
I
- -
A
FIRE PROTECTION
CONTRACTOR: LIC. # SC -210022
EXPIRES: 9-30-19
I , ..._
SYM
POSITION
FINISH
TEMP
K
MFG.
COUNT SPACING MODEL
UPRIGHT
BRASS
200
5.6
TYCO
113
12X12 TY3131
Description
- --'?
'
DETAILS & ATTIC FIRE PROTECTION PLAN
i
- --Draw€no
YARMOUTH APARTMENTS
�o. I
r
08/13/18
BUILDING C
Designed
9
E00
881 ROUTE 28
F P
Scale
1 8" = 1'-0"
YARMOUTH, MA
NIT1A i tyv +90
2 BED I E[
IFF 7
SYM
CNT
IPOSITION '
FINISH
TEMPK
II materials & installations of this automatic fire sprinkler system to
conform to N.F.P.A. #13, #,14, #20, #22,& #24
2System to be hydrostatically tested 200psi for 2 hours -per
. y y Y @
N F P.A. #13
3. All electrical & painting to be provided by others.
4 Pipehydraulic calculations.
NPT
SIN
MFG.
MODEL
Q
131
PEND
WHITE
155
4.90
1/2"
TY2234
Tyco
LFII
D
6
HSW
WHITE
155
5.60
1/2"
TY3355
Tyco
DS -1
@2
TYCO
UPR i
WHITE
155
5.60
1/2"
TY3131
Tyco
TY—FRB
01 1.4 02 03 04
7
06
Source Information
Date of Flow Test/ Info : 07117/2018
Location of flow test data
CONCEALED SPACES SHOWN WITHOUT AUTOMATIC
S"!1 SPRINKLER COVERAGE TO BE FILLED WITH INSULATION.
TYPICAL
VALVE STATION - SEE DETAIL
I
— FDC SIZE AND LOCATION TBD \ I
ELECTRIC BELL
F1
't,,� , 11 1 � I � 1 � I;�
- -- ;
i 1
— — _
_.._ _
,I
I
l- . _.. -_..._._
- I
P
i
i I t -w90 Vii, � i -J� _...,.._.. FlA,� � _.�...
I
,,1.2 : __ t 11 0,
I:\07 2 j 1�j I 15,1
CONCEALED SPACES SHOWN WITHOUT AUTOMATIC
` SPRINKLER COVERAGE TO BE FILLED WITH INSULATION.
f
TYPICAL�
112
11 2 11
: I
Design Area 1 Wet System
3rd Floor Residential
+'; z I 11 t 2 1 2 112 t I r
1 i 112 2 ill - .:....,.:... _ �. _.
i
t
3
t.
i f
!'
4°
' 1
3 ,
F
_._.
'
.
Classification: ReDemand Calculations usingHazen Williams Method t
_
occupancy
NFPA 13
. _ .._.... .....
,
( i
E _
r Density: 0.1 t.
. DesE n A ea y � I r � • ; _I
„ l
a 1
Outside Hose. 100 ...: , � __...__:.. t � �. ,, wA ,
Additional Outs � � �
Size: 360 I l r
Area S I
Design ---__.._
1 I _ __... �- -- I 1
-_ -
,
1 11.3.1.3 -
Notes. NFPA 3 �,.� _ "
... _... ...
,
. ..
..
Ji
rT
Wet System
Desi nArea 2
€
I
3rd Floor Hallway -----
.
Demand Calculations using Hazen
Williams Method 1JIT—
. , _ � NIT 2A
I r _
i i ation: Li ht Hazard :, ., +a . i r , �: 5E U�pA
Occupancy Classic g g _ _.. 2-�_D
ED i
Design Density:
0.1 _ s
9 Y I „ i
ditional Outside Hose: 100 ' - !; I - --.. --
Ad 1
t
kA OF At4
Design Area Size. 400
P 1311.2.3.4.2 1 1 �� . N ,
Notes: NFA : i i I w�..; -'l ���� JASON CATALF _
_,KA 4
n.-
Wa,
1 FIRE PROTECTION rn I
S102 I - CONCEhED SPACES SHOWN WITt ou-r AUTOMATIC
1
-, SPRINKLER COVERAGE TO BE FILLED WITH INSULATION. Q
1 GG lSTER
I= TYPICAL I j H t!;
— -- _ CONCEALED SPACES_SHOWN WITHOUT .UTOMATIC '
_ ---- _, E SPRI LER COVERAG TO BE FILLED
NSULATION.
TYPICAL
SYM CNT POSI110N FINISH TEMP K NPT SIN MFG. MODEL
�ECOND FLOOR PL
AN
Q 143 BEND WHITE 155 4.90 11/2" TY2234 Tyco LFII
{
No Revisions �>, w,:
.
`1.
'
_
-.'
:
..
PLAN NORTH
-
.71 -
p 8'18 '.:.
- - - - -
— — —
�i
II materials & installations of this automatic fire sprinkler system to
conform to N.F.P.A. #13, #,14, #20, #22,& #24
2System to be hydrostatically tested 200psi for 2 hours -per
. y y Y @
N F P.A. #13
3. All electrical & painting to be provided by others.
4 Pipehydraulic calculations.
PIPE LINE
sizE
TYPE
SCHEDULES;>;
INTS
FITTINGS
U
DRY
MAINS
112"AND :.
LARGER �•
BLACK �.►�.
STEEL
SCH. 10
- —
GROOVED--n.-r-
D.I. GRV —
HOLE CL .. caw.
U
C
r
J
U
U
U
F
+'; z I 11 t 2 1 2 112 t I r
1 i 112 2 ill - .:....,.:... _ �. _.
i
t
3
t.
i f
!'
4°
' 1
3 ,
F
_._.
'
.
Classification: ReDemand Calculations usingHazen Williams Method t
_
occupancy
NFPA 13
. _ .._.... .....
,
( i
E _
r Density: 0.1 t.
. DesE n A ea y � I r � • ; _I
„ l
a 1
Outside Hose. 100 ...: , � __...__:.. t � �. ,, wA ,
Additional Outs � � �
Size: 360 I l r
Area S I
Design ---__.._
1 I _ __... �- -- I 1
-_ -
,
1 11.3.1.3 -
Notes. NFPA 3 �,.� _ "
... _... ...
,
. ..
..
Ji
rT
Wet System
Desi nArea 2
€
I
3rd Floor Hallway -----
.
Demand Calculations using Hazen
Williams Method 1JIT—
. , _ � NIT 2A
I r _
i i ation: Li ht Hazard :, ., +a . i r , �: 5E U�pA
Occupancy Classic g g _ _.. 2-�_D
ED i
Design Density:
0.1 _ s
9 Y I „ i
ditional Outside Hose: 100 ' - !; I - --.. --
Ad 1
t
kA OF At4
Design Area Size. 400
P 1311.2.3.4.2 1 1 �� . N ,
Notes: NFA : i i I w�..; -'l ���� JASON CATALF _
_,KA 4
n.-
Wa,
1 FIRE PROTECTION rn I
S102 I - CONCEhED SPACES SHOWN WITt ou-r AUTOMATIC
1
-, SPRINKLER COVERAGE TO BE FILLED WITH INSULATION. Q
1 GG lSTER
I= TYPICAL I j H t!;
— -- _ CONCEALED SPACES_SHOWN WITHOUT .UTOMATIC '
_ ---- _, E SPRI LER COVERAG TO BE FILLED
NSULATION.
TYPICAL
SYM CNT POSI110N FINISH TEMP K NPT SIN MFG. MODEL
�ECOND FLOOR PL
AN
Q 143 BEND WHITE 155 4.90 11/2" TY2234 Tyco LFII
{
No Revisions �>, w,:
.
`1.
'
_
-.'
:
..
PLAN NORTH
-
.71 -
p 8'18 '.:.
- - - - -
— — —
P
PIPING ssOTFs
II materials & installations of this automatic fire sprinkler system to
conform to N.F.P.A. #13, #,14, #20, #22,& #24
2System to be hydrostatically tested 200psi for 2 hours -per
. y y Y @
N F P.A. #13
3. All electrical & painting to be provided by others.
4 Pipehydraulic calculations.
PIPE LINE
sizE
TYPE
SCHEDULES;>;
INTS
FITTINGS
WET
DRY
MAINS
112"AND :.
LARGER �•
BLACK �.►�.
STEEL
SCH. 10
- —
GROOVED--n.-r-
D.I. GRV —
HOLE CL .. caw.
--is
11TAND - -
7At_
LA"'°R C_VL EV
-"= or
=
S=" 10�7
–
GRr VSD _ '-�'�'E__.`--
^I GN •..„
HE CUT CA-" V__1%8
"_XE
SCALE 1/8'= 1.-0. . _...
.....
SYM
PEAK FIRE PROTECTION, INC, ~�
1 Attic Plan 0912A�;',l 8
4 BROOK ST. SUITE 25E I
- SCITUATE MA. 02066 I
P:781-232-7272
CONTRACTOR: LIC. SC -210022
FIRE PROTECTION EXPIRES: 9-30-19
Description
FIRST & SECOND FLOOR FIRE PROTECTION PLAN
SPRINKLER
LEGEND
-
RESIDENTIAL
— - -- --
e==.r x�-s
F _
-- --
-
- _..
'�r�
SYM
POSMON
FINISH TEMP
K
MFG.
COUNT
SPACING
MODEL
_.
• PENDENT RECESSED WHITE 155
4.9
TYCO
274 16X16 TY2234
—'
HSW WHITE : 155
5.6
TYCO
6
14x14 TY3355
UPRIGHT WHITE 155
5.6
TYCO
2
15X15
TY3131
YARMOUTH APARTMENTS
BUILDING C
881 ROUTE 28
YARMOUTH, MA
Drawing ��:.
t
P i
- ----
Date
08/13/18
Designed
9
E00
Scale
1/811 =1'-0"