June 14, 2001
Yarmouth Board of Health
Town Hall
Yarmouth MA
Re: Sewage Disposal System Repair —15 Hervey Lines Lane
(Carswell) Yarmouth MA
Map 59 Parcel 14
Dear Board Members:
Registered Land Surveyor #8483
Registered Civil Engineer #12609
On June 14, 2001 tests were conducted on the captioned lot to determine suitability for a Title V subsurface sewage
disposal system The results of the tests and soil data were as follows:
Test
Pit Bottom
Pit
Depth Elevation
1
151" 34.4
2
Waived
Ground water was encountered at El. 34.4.
Soil
Classification
See attached by
Kevin Mullaney (Soil Evaluator)
Pere Rate
minTnch
<2 min/inch
Title V of the State Environmental Code requires the following dosage rates for percolation rate less than 5.0
munch:
Side wall area 0.74 gals/sq.ft.
Bottom area 0.74 gals/sq.ft.
For a three (3) bedroom house having plumbing fixtures and appliances in common usage, including an automatic
sequence laundry washer and a dishwasher, but not a mechanical garbage grinder, a daily sewage flow of 330
gallons is anticipated. A 343.3 G.P.D. has been provided.
It is recommended that a precast concrete septic tank having a required capacity of 1500 gallons be installed on this
lot in series with a precast concrete distribution box (3 outlets) and leaching chambers (Ref. 15.253).
Construct one (1) leaching chamber 28' x i l' by placing a row of two (2) leaching dry well units 500 gallon and
four (4) feet of stone on all sides.
This system provides for 464 sq. ft. of leaching area and a capacity of 343.3 G.P.D. using two 500 gallon H-10
leaching drywells. The enclosed plot plan indicates the location and grades of the system. The sections show the
type of construction and materials that are recommended. All piping in the system shall be 4" p.v.c., Schedule 40,
including replacement to the foundation.
There are no known or observed wells or wetlands within 100' Title V requirements (15.211) of the proposed septic
system
Page 2 June 14, 2001
Re: Sewage Disposal system Repair (Carswell)
The finish ground grading shall conform to Title V section 15.221 (7) in such a manner that surface water runoff
shall be diverted from the house and the leaching system. The existing cesspool is to be pumped and filled with
excavated clean medium to fine sand.
All trees, top and subsoil within ten (10) feet of the leaching area shall be removed for a depth of 18".
Construction shall conform to all Title V requirements.
Contractor to notify Engineer at the time of installation to verify soil conditions.
Very y ours,
Joseph H. Rego
Civil Engineer
/par
attachment
Permit Number: Date:
I Completed by:
HIGH GROUND -WATER LEVEL COMPUTATION
Site Location:� `✓� A/- f -ey L /:v es Lau Lot No.
/
Owner: (, /-x I've �/ Address: & �/�g� A Tze �e'a
Contractor: Address:
Notes: 16, C USJ o>YM o t� f`J p/ak Z
STEP 1
Measure depth to water table
15
tonearest 1/10 ft................................................................................Date
-S /2/6
m th ay/year
STEP 2
Using Water -Level Range Zone
and Index Well Map locate
site and determine:
-
OAppropriate index well ......................................
�VG7
OWater -level range zone
STEP 3
Using monthly report "Current
F
Water Resources Conditions"
'
determine current depth to
7,J
water level for index well ...........................
m th/Year
STEP 4
Using Table of Water -level Adjustments
for index well (STEP 2A), current depth
to water level for index well (STEP 3),
and water -level zone (STEP 26)
determine water -level adjustment ...............................................
................... ...............
STEP 5
Estimate depth to high water
by subtracting the water -
level adjustment (STEP 4)
from measured depth to water
levelat site (STEP 1).............................................................................................................
//r
Figure 13. --Reproducible computation form
R
15
Property gddress:' y
Date:
JJ r
Commonwealth of MassachtLsett,s
TOWN OF •}l���f�
PER COLA 7 O TEST
Illy
Time:
Site railed
Determination of Seasonal High Wafer Table
Depth Observed standing in hole• 15`I. 2" (IZ.(�') �'/ .,�4•�'
Depth weeping from side:
Does at least four feet of naturally occurring pervious material erist in all areas observed? �/ s
_ f �s
If not, what is the depth of naturally occurring pervious material?
Certification
I certify the in April 1993 I passed the examination approved by the Department of Environmental
Protection and that the above analysis was performed by me consistent with the required trainin
clpfrtise and ex
p
erience described in 310 CMR 15.017. g'
�cvin M. Mullaney *
•Certified Soil EvaIuator Date:
Nb. Date
Corrlr%!orlivcartli of Massachusetts udg
Asse,�suzent for Oil -Site Setivage .Disposal
•:y.{•�i•. -ry orf: �/L�. � � � I �/t�l
Witu z•seci By:
Pr•; poly f.::•..: SS (i ��� J�vL/,SCS �,��� Property Owner
ll.t•J LS,%V%/•ti lYf1L `li �'� Parc/e1i � � Gq�S�,JC �1..
I. t" •
Co:l`struction epair .
11993 Barnstablc County Soil Survey (1:2S,006) ' ' Soil Map Unit:
Drainabe CI ss: l.�SS.iSoil Limitations: Landform".Parent Material (Geologic): Lot .Vegetation:
Currcut'' -l:esoicrces c0,zditions-'(USGS) '.j:-.Mont.h: Range:
°:Tiiri'c 66 .: : - Weather• C�E�� r 66 °
cpt ror zon 'exture _ o or(MunscllMottliniComments
LIMA
Ap
4/A
' y a (zb
i
• '•ham �• •'.' +
•'•••; •: .�1�•'•'..,
Septic Tank
1,500 Gallons
ST -1500-H-10
QOM
Rvvsdi gins bafyfi 'on buflai:`�P .
r +�
---
Distribution Box
DB -5
H-10
(3 Inlet with. Baffle)
IV Xyl%
DISTRIBUTION BOX DB -5 H-10
�-----21"-�,
13"
5, 5" DIA. OUTLETS•
PLAN VIEW
2" WALLS
3"
13'!:"
sv=' J —j� 2"
SECTION VIEW
SPECIFICATIONS
- Concrete Minimum Strength: 4,000 P.S.I. ® 28 days
- Steel Reinforcement: AS -615-68, Grade 60
Design Loading: AASHTO - H10
- Weight: 250 lbs.
1
LEACHING DRYWELL 500 GALLONS H-10
PLAN VIEW
F" B
-------------------------
L -------------------------
A
-----------------
L-------------
FRONT VIEW
A
20" D
2
5 DIA. KNOCKOUTS
1�1 1�1
1�1 wl
wl �' 1�1 I�1 IMMM-1W
I�I1�1
I�I1.1
I�Ii�II�I I�IIIRI
ISI 1f1
Iw1 I.i 1�1 1-1 1lel
1M1 IEI
r 1 1ft1 1 ISI 1
FRONT VIEW
A
20" D
2
SIDE VIEW
SECTION A—A SECTION B—B
SPECIFICATIONS
• Concrete Minimum Strength: 4,000 P.S.I. ® 28 days
• Steel Reinforcement: AS -615 & A-185, Grade 60
• Design Loading: AASHO - H 10
• Weight: 3862 lbs.
l
ISISIw,-1
ism
SIDE VIEW
SECTION A—A SECTION B—B
SPECIFICATIONS
• Concrete Minimum Strength: 4,000 P.S.I. ® 28 days
• Steel Reinforcement: AS -615 & A-185, Grade 60
• Design Loading: AASHO - H 10
• Weight: 3862 lbs.
l