HomeMy WebLinkAboutEngineered Plan - Rev. 2004TOP OF FOUNDATION ELEV. = 100.00 - ___' (ASSUMED) 4" SCHEDULE 40 PVC PIPE CLEAN SAND 20 FT. MINIMUM FROM CELLAR MIN. PITCH 1/8" PER FT.--\ INSPECTION PORT 10 FT. MINIMUM FROM SLAB OR CRAWL SPACE 2" LAYER OF 10 FT. MINIMUM 1/8' TO 1/2" 2" PRESSURE PIPE 150 PSI MINIMUM ELEV. WASHED STONE VENT CONCRETE 6" MAX. COVERS CMOVERHOANLE 7 SOIL TEST DATE OF SOIL TEST 7 SOIL TEST DONE BY WITNESSED BY 2 OBSERVATION HOLE 1 ELEV.= PERCOLATION RATE Ml N./INCH AT INCHES DEPTH HORIZ TEXTURE COLOR MOTT. OTHER U�.Elo ILL. (TO BE PLACED ON FIRM BASE) 4 FEET 14 INCHES MYERS SRM 4 --t 5 FEET 19 INCHES 0.4 HIP (MAX.) WATER ENCOUNTERED AT ELEV. 6 FEET 24 INCHES /1500 GALLON 1000 6A (OR EQUAL) USGS PROBABLE WATER TABLE ELEV. = 7 FEET 29 INCHES p OBSERVED WATER TABLE ELEV. = -7 ,8 FEET 34 INCHES SEPTIC TANK PUMP CONCRETE BOTTOfl OF TEST HOLE ELEV. = z CONCRETE CHAMBER DESIGN CALCULATIONS 0 ,7700 PUMP CHAMBER CALCULATIONS: NUMBER OF BEDROOMS ELEV. AT INVERT INLET ------ GARBAGE DISPOSAL ELEV. AT ALARM ON 9 y UNIT ELEV. AT PUMP ON 67 REQUIRED FLOW PER CYCLE .,5 X GAL./CYCLE 03 TOTAL ESTIMATED FLOW SEWAGE DISPOSAL SYSTEM PROFILE VOLUME LE CAL/CYCLE /7.48 CA 110 GAL./BR./DAY X BR.) GAL./DAY PER CYC L./CU FT. CU. FT./CYCLE NOT TO SCALE ELEV. AT PUMP OFF _ff_2K_ BOTTOM OF INSIDE PUMP CHAMBER VOLUME OF WATER IN PIPE 3.14 X 0.00694 X -L> F SEPTAC TANK -- FT. CU. FT. REQUIRED SEPTIC TANK CAPACITY GAL. CAPACITY OBOTTOM OF OUTSIDE PUMP CHAMBER j37 TOTAL MINIMU A VOLUME PER CYCLE CU. FT, ACTUAL SIZE OF SEPTIC TANK GAL. CU. 34.67 CU.FT.7FT, = -Ja-33-- FT. (1000 G.S.T.) Z SOIL CLASSIFICATION 5X1 OX(5.33 ------ )X7.48 GALLONS STORAGE CAPACITY GAL./DAY /7.48 CAL./CU.FT,/3,;.67 CU.FT./FT. FT. DESIGN PERCOLATION RATE 5 MIN./IN. REQUIRED l,_=P-R,'CVIDED EFFLUENT LOADING RATE _Q .2-4 CAL./DAY/S.F. -1 LEACHING AREA '247 SQ. FT. LEACHING CAPACITY (AREA X RATE) GAL./DAY "J RESERVE LEACHING CAPACITY GALJDAY NOTES: 1. ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO D.E.P. TITLE 5 AND THE TOWN RULES AND REGULATIONS FOR. THE SUBSURFACE DISPOSAL OF SEWAGE. 2. ALL COVERS TO SANITARY UNITS SHALL' BE BROUGHT TO )Qrm tl WITHIN 6* OF FINISHED GRADE. 3. ALL COMPONENTS OF THE SANITARY SYSTEM SHALL BE CAPABLE OF lqf WITHSTANDING H-10 LOADING UNLESS THEY ARE UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS. H-20 LOADING SHALL BE USED UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS. .ANY MASONRY UNITS USED TO BRING COVERS TO GRADE SHALL 94 LEGEND: EXISTING SPOT ELEVATION x0_0 EXISTING CONTOUR ----00---- FINAL SPOT ELEVATION FINAL CONTOUR SOIL TEST LOCATION UTILITY POLE TOWN WATER —W W� CATCH BASIN GAS LINEG CESSPOOL 5'p - CLEANOUT -'_'C. C.O. 9.26.6 97.6 97.7 8.5 97.3 71D U 73 C__ 98.7 96.2 k3 98.1: 6.9 96.1 96.0 --BE-MORTARED IN -P -L -A -CE.- ---- PROPOSED SEPTIC W R_ EE FOR -c AUG 1 9 2004 5. NO DETERMINATION HAS BEEN MADE AS TO COMPLIANCE WITH DEEDED OR ZONING REGULATIONS. OWNER / APPLICANT IS TO PROJ: VJ OBTAIN SUCH DETERMINATION FROM APPROPRIATE AUTHORITY. 6. UTILITIES SHOWN ARE APPROXIMATE ONLY, EXCAVATION CONTRACTOR v IS TO CALL "DIG -SAFE" AT 1-888-344-7233 AT LEAST 72 HOURS 4" CAST IRON PIPE (OR EQUAL) MINIMUM 6 MAX- 6 MA _1 T ALE 1 it I 20 22 0 0 W 10 - REVISED _RE� IS TO BE BROUGHT TO THE ATTENTION OF THE DESIGN ENGINEER IMMEDIATELY. PITCH 1/4- PER FT. 8. PARCEL IS IN FLOOD ZONE LOCATION MAP I 9. LOT IS SHOWN ON ASSESSORS MAP --13-0 AS PARCEL 25 L VEL c' % /4; BEL A1800 FILTEREL V 6" SUMP ELEV.=��_l � V. ELEV. FLOW LINE o" APPROVED. BOARD OF HEALTH __DrSTRIBUTION ELEV.,, ELEV. i MIN. --I �'i' -, 1 3/8- DRILL BOX 4 HIGH CAPACITY INFILTRATORS WITH STONE IN AN GAS BAF.F�.'E H OLE TO BE WATER TESTED *x ox �!D TRENCH FORMATION f4 I 4. WELL rl�% �\,' ELEV. ELEV. (TO BE PLACED ON FIRM BASE) 1/2- SOIL ABSORPTION ZONE INDEX LIQUID OUTLET 2 .4�1> v CHECK 3/4- TO 1 VALVE WASHED STONE SYSTEM (SAS) ADJUST SOIL TEST DATE OF SOIL TEST 7 SOIL TEST DONE BY WITNESSED BY 2 OBSERVATION HOLE 1 ELEV.= PERCOLATION RATE Ml N./INCH AT INCHES DEPTH HORIZ TEXTURE COLOR MOTT. OTHER U�.Elo ILL. (TO BE PLACED ON FIRM BASE) 4 FEET 14 INCHES MYERS SRM 4 --t 5 FEET 19 INCHES 0.4 HIP (MAX.) WATER ENCOUNTERED AT ELEV. 6 FEET 24 INCHES /1500 GALLON 1000 6A (OR EQUAL) USGS PROBABLE WATER TABLE ELEV. = 7 FEET 29 INCHES p OBSERVED WATER TABLE ELEV. = -7 ,8 FEET 34 INCHES SEPTIC TANK PUMP CONCRETE BOTTOfl OF TEST HOLE ELEV. = z CONCRETE CHAMBER DESIGN CALCULATIONS 0 ,7700 PUMP CHAMBER CALCULATIONS: NUMBER OF BEDROOMS ELEV. AT INVERT INLET ------ GARBAGE DISPOSAL ELEV. AT ALARM ON 9 y UNIT ELEV. AT PUMP ON 67 REQUIRED FLOW PER CYCLE .,5 X GAL./CYCLE 03 TOTAL ESTIMATED FLOW SEWAGE DISPOSAL SYSTEM PROFILE VOLUME LE CAL/CYCLE /7.48 CA 110 GAL./BR./DAY X BR.) GAL./DAY PER CYC L./CU FT. CU. FT./CYCLE NOT TO SCALE ELEV. AT PUMP OFF _ff_2K_ BOTTOM OF INSIDE PUMP CHAMBER VOLUME OF WATER IN PIPE 3.14 X 0.00694 X -L> F SEPTAC TANK -- FT. CU. FT. REQUIRED SEPTIC TANK CAPACITY GAL. CAPACITY OBOTTOM OF OUTSIDE PUMP CHAMBER j37 TOTAL MINIMU A VOLUME PER CYCLE CU. FT, ACTUAL SIZE OF SEPTIC TANK GAL. CU. 34.67 CU.FT.7FT, = -Ja-33-- FT. (1000 G.S.T.) Z SOIL CLASSIFICATION 5X1 OX(5.33 ------ )X7.48 GALLONS STORAGE CAPACITY GAL./DAY /7.48 CAL./CU.FT,/3,;.67 CU.FT./FT. FT. DESIGN PERCOLATION RATE 5 MIN./IN. REQUIRED l,_=P-R,'CVIDED EFFLUENT LOADING RATE _Q .2-4 CAL./DAY/S.F. -1 LEACHING AREA '247 SQ. FT. LEACHING CAPACITY (AREA X RATE) GAL./DAY "J RESERVE LEACHING CAPACITY GALJDAY NOTES: 1. ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO D.E.P. TITLE 5 AND THE TOWN RULES AND REGULATIONS FOR. THE SUBSURFACE DISPOSAL OF SEWAGE. 2. ALL COVERS TO SANITARY UNITS SHALL' BE BROUGHT TO )Qrm tl WITHIN 6* OF FINISHED GRADE. 3. ALL COMPONENTS OF THE SANITARY SYSTEM SHALL BE CAPABLE OF lqf WITHSTANDING H-10 LOADING UNLESS THEY ARE UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS. H-20 LOADING SHALL BE USED UNDER OR WITHIN 10 FT. OF DRIVES OR PARKING AREAS. .ANY MASONRY UNITS USED TO BRING COVERS TO GRADE SHALL 94 LEGEND: EXISTING SPOT ELEVATION x0_0 EXISTING CONTOUR ----00---- FINAL SPOT ELEVATION FINAL CONTOUR SOIL TEST LOCATION UTILITY POLE TOWN WATER —W W� CATCH BASIN GAS LINEG CESSPOOL 5'p - CLEANOUT -'_'C. C.O. 9.26.6 97.6 97.7 8.5 97.3 71D U 73 C__ 98.7 96.2 k3 98.1: 6.9 96.1 96.0 C.' '�-00,dwg\-scs'.D WG 0 T.A. DUM�ASj --BE-MORTARED IN -P -L -A -CE.- ---- PROPOSED SEPTIC W R_ EE FOR -c AUG 1 9 2004 5. NO DETERMINATION HAS BEEN MADE AS TO COMPLIANCE WITH DEEDED OR ZONING REGULATIONS. OWNER / APPLICANT IS TO PROJ: VJ OBTAIN SUCH DETERMINATION FROM APPROPRIATE AUTHORITY. 6. UTILITIES SHOWN ARE APPROXIMATE ONLY, EXCAVATION CONTRACTOR IS TO CALL "DIG -SAFE" AT 1-888-344-7233 AT LEAST 72 HOURS PRIOR TO COMMENCING WORK ON SITE. ! ALE 1 it I 20 7. -CONTRACTOR IS TO VERIFY GRADES AND ELEVATIONS AS WELL AS SITE CONDITIONS PRIOR TO COMMENCING WORK ON SITE. ANY VARIA11ON REVISED _RE� IS TO BE BROUGHT TO THE ATTENTION OF THE DESIGN ENGINEER IMMEDIATELY. 8. PARCEL IS IN FLOOD ZONE LOCATION MAP I 9. LOT IS SHOWN ON ASSESSORS MAP --13-0 AS PARCEL 25 SHEET 1 OF % /4; APPROVED. BOARD OF HEALTH DATE AGENT C.' '�-00,dwg\-scs'.D WG 0 T.A. DUM�ASj WEST YARMOUTH,M rcg LOCU Nt 14 73 1� ul m Z3 -> o c' '�I' rz wk sk, PROPOSED SEPTIC W R_ EE FOR -c AUG 1 9 2004 PROJ: VJ TADCO ENVIRONMENTAL CONSULTANTS 26 COMPASS LANE, DENNIS, MA 02638 (508) 385-2425 DATE ALE 1 it I 20 REVISED _RE� JOB NO. LOCATION MAP I I REVISED � j SHEET 1 OF C.' '�-00,dwg\-scs'.D WG 0 T.A. DUM�ASj