DESIGN F OW• 4 BEDROOMS x 110 gal/dog
PER BEDROOM = 440 GALLONS PER DAY
SEPTIC TANK 440 GPD X 2 DAYS = 880 GALLONS
USE EXISTING 1000 GALLON SEPTIC TANK IF IN
SOUND STRUCTURAL CONDITION. IF NOT, INSTALL
NEW 1500 GALLON SEPTIC TANK.
DISTRIBUTION BOX, INSTALL 5 OUTLET D -BOX
THE LONG TERM ACCEPTANCE RATE FOR A CLASS ONE
SOIL WITH A PERCOLATION RATE BELOW 5 MINUTES
PER INCH = 0.74 GALLONS PER DAY PER SQUARE FOOT.
INSTALL 25 ADS ARC 36 BIODIFFUSER UNITS
25 UNITS x 5 ft / UNIT = 125 L.F. (LINEAR FEET)
125.0 L.F. x 4.8 S.F./L.F = 600 S.F. (SQUARE FEET)
600.0 S.F x .74 G.P.D. / S.F. = 444.0 gal/day
-INSTALL 25 ADS ARC 36 BIODIFFUSERS AS
CONFIGURED BELOW.
-FLOW CAPACITY = 444.0 gal/day WHICH EXCEEDS
THE 440 gal/day REQUIRED FOR FOUR BEDROOMS.
77
ELEVATION
24.43
PROPOSED SOIL
ABSORPTION
SYSTEM
-SEE DETAIL
ON BACK
FLOOR PLAN I
L
O
W
E
R
U
P
E
R
BED
AT 19.63
ROOM
BATHROOM
ZONE
/L A UNDR Y
BED
APRIL, 2019
ROOM
FA MIL Y
ADJUSTMENT
ROOM
BED A KITCHEN
ROOM T
17 H
BED
ROOM LIVING
ROOM
EXISTING SOIL ABSORPTION SYSTEMS ARE
TO BE REMOVED OR ABANDONED IN PLACE
LEGEND]
SEPTIC COMPONENTS
EXISTING
1000 GAL
SEPTIC TANK
INSTALL 1000
GALLON PUMP
CHAMBER
2 In SCH 80
PRESSURE PIPE
W/ I cu ft THRUST
BLOCK 0 BENDS
DISTRIBUTION BOX
TEST PIT
THIS IS A
CO, OR
PLAN
USE COLOR PLAN ONLY
FOR INSTALLATION
FULL DETAIL IS BEST
VIEWED IN
FULL COLOR
I YARMOUTH, MA
BAANSTABLE
MUNICIPAL
AIRPORT JI
Q
Q
�z
Q m
904", m
B
WASN►OTON
AVE
NOT
TO
SCALE
904,
LOCUS MAP
OBSERVED GW
AT 19.63
INDEX WELL
AIW-230
ZONE
D
READING DATE
APRIL, 2019
READING
19.97
ADJUSTMENT
0
ADJUSTED GW
AT 19.63
do 40
23 to aw
SOT 42
.00000 AREA = 15000 sf+—
� MILL POL Y
INSTALL 40 33983
�
LINER 63 64 o
—23 TOP EL = 24.35 t
�24 -BOTTOM EL = 20.35
SOIL
REMOVAL
AREA aRA��AY O
m4 DRIYEW
® o
27,5 ft
WALK
LK Ay
� 2 !� �� � K / 41 m uuu
®7
'r Z m
z
2� m
oy vi a
Ik I i✓
Mit valid for REPAIR OF SlrIIAeA�f i3
LY, due to State and Localestic va
ird of Health review and appro� s requ
ra
Page facilities and/or structures/dwell\r future ngt1
l Yarmouth Health Department
APPROVED
Nslae
22
�( l
pate
LAN
SCALE: 1 in = 20 ft
O 20 40
TFMM
O 10 20
PRINT ON 11 x 17 in
PAPER FOR PROPER SCALE
�P`ZN OF MASs9
DAVID �yGJ
�COUGHANOWR
No. 1093
cP��N OF Mgss9
o DAVID �tioJ
D
COUGHANOWR
No. 461
VARIANCE REQUESTED
310 CMR 15.212 — DEPTH TO GROUNDWATER.
FIVE FOOT SEPARATION REQUIRED —VARIANCE
TO A FOUR FOOT SEPARATION REQUESTED.
'Iii..... �.... goIw�
REVISED AUGUST 15, 2019
SOIL REMOVAL AREA — REMOVE ALL FILL
AND UNSUITABLE SOILS DOWN TO THE
C STRATUM AND REPLACE WITH CLEAN
MEDIUM SAND PER TITLE 5
(3)0 CMR 15.255(3)).
FOR SURVEYOR'S CERTIFICATION REFER TO 'PLOT PLAN'
DATED OCTOBER 26. 1977 SIGNED & STAMPED BY GEORGE
LOW JR. RLS ON FILE AT THE YARMOUTH BUILDING DEPARTMENT.
SEWAGE DISPOSAL
SYSTEM PLAN
CLAUDIO
A. NETTO
-
25 FILLMORE ROAD
155 Geo Ryder Rd S
YARMOUTH. MA
Chatham, MA 02633
DavidcouOHotmail.com
JUNE 27, 2019
508 364-0894
1/2 E ETE-4394 1.E1 E
SOIL TEST
LOG
'''
SOIL COLOR
(MUNSELL)
9
SOIL EVALUATOR: DAVID D. COUGHANOWR. ASE
#461
WITNESSED
BY: AMY VON HONE, HEALTH DEPT.
10 YR 2/2
TEST PIT
1
GROUNDWATER NCOUNTERED AT 80 in
E
MEDIUM SAND
IN/
MN
FRIABLE
14-18
ELEVATION
SANDY LOAM
10 YR 3/3
NONE
FRIABLE
18-32
B
LOAMY SAND
10 YR 4/3
NONE
LOOSE
32-52
26.30
MEDIUM SAND
10 YR 6/4
NONE
LOOSE
52-100
C2
'CEMENT' SAND
10 YR 2/1
BOG NOH
FIRM1000
ON
;CHECK
VALVE
OFF
19.63
17.97
TEST PIT
Z
GROUNDWATER ENCOUNTERED
AT 38 In
2 MINIINCH IN
C SOILS
ELEVATION
22.75
20.75
19.58
16.41
DEPTH
INCHES
GALLON PUMP CHAMBER
SOIL
HORIZON
USDA SOIL
TEXTURE
SOIL COLOR
(MUNSELL)
SOIL
MOTTLES
OTHER
0-8
O
WOOD LOAM
10 YR 2/2
NONE
FRIABLE
8-14
E
MEDIUM SAND
10 YR 5/1
NONE
FRIABLE
14-18
A
SANDY LOAM
10 YR 3/3
NONE
FRIABLE
18-32
B
LOAMY SAND
10 YR 4/3
NONE
LOOSE
32-52
Cl
MEDIUM SAND
10 YR 6/4
NONE
LOOSE
52-100
C2
'CEMENT' SAND
10 YR 2/1
BOG NOH
FIRM1000
DEPTH
IN<HES
SOIL
HORIZON
USDA SOIL
TEXTURE
SOIL COLOR
(MUNSELL)
SOIL
MOTTLES
OTHER
0-4
O
LOAMY SAND
10 YR 3/2
NONE
FRIABLE
4-10
E
LOAMY SAND
10 YR 4/2
NONE
LOOSE
10-14
A
SANDY LOAM
10 YR 2/1
NONE
FRIABLE
14-24
6
LOAMY SAND
10 YR 3/2
NONE
LOOSE
L-76
C
MEDIUM SAND
10 YR 6/3
NONE
LOOSE
DIMENSIONS AND DETAIL ELECTRICAL PERMIT NEEDED
FOR PUMP SYSTEM
NOT
CAL CS TA PER � SCALE
SEASONAL HIGH 1�
GROUNDWATER = 19.63 0 � c
BOTTOM OF --
PUMP CHAMBER = 18.20 �
�ro
DEPTH OF WATER
DISPLACED = 1.43 ft •��
EXTERIOR DIMENSIONS OF
UNIT = 8.5 ft x 4.83 ft
8.5x4.83x143=58.71 cu ft 8 ft -6 in A
58.71 cu ft x 7.48 = 439 go/
439 x 8 Ib/ go/ = 3513 # USE SHOREY PRECAST
PUMP CHAMBER WEIGHS 8240# ST -1000 H-1
0
PUMP CHAMBER WILL NOT FLOAT OR EQUIVALENT
TANK TO BE CERTIFIED WATERPROOF ALL ELECTRICAL CONNECTIONS
& WATERTIGHT BY MANUFACTURER TO BE MADE OUTSIDE CHAMBER
CONTROL PANEL TO CONSIST OF AUDIBLE AND VISUAL ALARM ON
INDEPENDANT CIRCUIT AND TO BE LOCATED OUTSIDE DWELLING.
USE BARNES SE411 PUMP 0.4 HP, 115 V, 1750 RPM
PASSING 1-I/2 in SOLIDS
PROVIDE 1/4 tPUMP
INSTALL QUICK COVER
WEEPHOLE DISCtin
TO
DRAIN PIPE ACOUGRADE
RUMP--C-YCL F INTO
TO
___w D -BOX
FROM GE = 1"�r
BUOYANCY
-►
WEEP
SEPTIC
M ON
HOLE
TANK
ON
;CHECK
VALVE
OFF
DOSING = 104 GAL/CYCLE = 4 CYCLES/DAY
STORAGE = 500 GALLONS � 440 GPD REQUIRED
CROSS SECTION VIEW
-INSTALLER TO OBTAIN DISPOSAL WORKS
PERMIT BEFORE STARTING WORK.
-ALL COMPONENTS INSTALLED SHALL MEET
THE MINIMUM REQUIREMENTS OF
MASSACHUSETTS TITLE 5 SEPTIC
CODE (310 CMR 15).
-INSTALLER TO VERIFY LOCATIONS OF ALL
UNDERGROUND UTILITIES BEFORE
EXCAVATING FOR SYSTEM.
-ECO-TECH RAPID RESPONSE RECOMMENDS
THE INSTALLATION OF LOW FLOW
FIXTURES & APPLIANCES. AND PERIODIC
PUMPING OF THE SEPTIC TANK.
-SYSTEM IS NOT DESIGNED TO WITHSTAND
VEHICULAR LOADING. DO NOT PARK OR
DRIVE VEHICLES OVER SEPTIC SYSTEM.
1000 GALLON SEpTOC TANKI in CO
EXISTING UNIT - DIMENSIONS & DETAIL
TANK TO BE PUMPED DRY AT TIME OF INSTALLATION
AND EXAMINED FOR STRUCTURAL INTEGRITY. INSTALL
NEW PVC OUTLET TEE EQUIPPED WITH A GAS BAFFLE.
REPLACE WITH A NEW
1500 GALLON TANK
TAPERCRACKED, ROTTED
OR OTHERWISE
COMPROMISED.
� c
0
o NOT
TO
� SCALE
8 ft 6
INLET INSTALL FILTER (ZABEL) OUTLET
COVER ON OUTLET TEE COVER
� �3 IN DROPFLOW LINE
FROM 10 in _ 14 TO
BUILDING ,,,
D -BOX
48 in
LIQUID GAS �
LEVEL BAFFLE
,STONE BASE IF NEW
SEPARATION BETWEEN INLET & OUTLET
TEES NO LESS THAN LIQUID DEPTH
CROSS SECTION VIEW
BUOYANCY CALCS
SEASONAL HIGH GROUNDWATER = 19.63
BOTTOM OF SEPTIC TANK = 18.50
DEPTH OF WATER DISPLACED = 1.13
EXTERIOR DIMENSIONS OF UNIT = 8.5 ft x 4.83 ft
8.5 x 4.83 x 1.13 = 46.4 cu ft x 7.48 = 347 GAL
347 GAL x 8 Ib/ 801 = 2777 #
SEPTIC TANK WEIGHS 8240#
SEPTIC TANK WILL NOT FLOAT
SOo§L QeSOoRp'r§OoN
S� YS -rEIF
M CONSTRUCTION DETAIL
USE ADS ARC 36 LP LOW PROFILE B/ODIFFUSERS
INSPECTION
PORT 25.0 ft
O
u�
M
O
25 UNITS TOTAL - 5.0 ft PER UNIT
CROSS SECTION VIEW
RESTORE VEGETATIVE COVER
BACKFILL WITH CLEAN PERC
SAND TO TOP OF CHAMBERS
3.8 in O -PRO 8 inch
F DEPTH UNITS TOTAL DEPTH
EFH
2.875' EXISTING
SUITABLE
EFFECTIVE WIDTH = 5 x 2.875' = 14.375' MATERIAL
REFER TO DEP APPROVAL LETTER TRANSMITTAL
# X264258 FOR CERTIFICATION OF INFILTRTATOR
SYSTEMS BIODIFFUSER UNITS.Q]�
ALL PIPE TO BE SCH. 40 PVC
AND TO PITCH AT 1/8 in/ft MIN'S VENT
RAISE COVERS TO WITHIN PIPE
F � _ 24.43 + - 6 i n O F FINAL GRADE
*PIPE FROM PUMP CHAMBER TO D -BOX SHALL BE 2 in
SCH. 80 PVC WITH 1 cu ft OF THRUST BLOCKING AT BENDS.
25.35 �l
'yq
D -BOX 12 in INSPECTION - -sl pP
TEE 24.35
MIN PORT F
EXISTING 24.30
yy�� w,' �y� REFER TO DETAIL BOX
rN=�: PROPOSED 24.13
22.75 6 in � +
SEPTIC TANK 1000 GALLON �p
REFER TO DETAIL BOX EXISTING PU11� CHAA�ER 22.45 BEE S0�� ABSORPTION
18.50 24.00 ������ -REFER TO o
6 In STONE BASE IF NEW '.9 •`. � � �' 18.20 DETAIL BOX
22.70 6 In'STONE BASE 96 ft 4-11 ft 23.G8 ADJUSTED SEASONAL T 4
EXISTING 5 ft HIGH GROUNDWATER 19.63
SEWAGE DISPOSAL SYSTEM PLAN 25 FILLMORE ROAD YARMOUTH, MA JUNE 27. 2019 ETE-4394 PG 2/2
-►
WEEP
SEPTIC
M ON
HOLE
TANK
ON
;CHECK
VALVE
OFF
DOSING = 104 GAL/CYCLE = 4 CYCLES/DAY
STORAGE = 500 GALLONS � 440 GPD REQUIRED
CROSS SECTION VIEW
-INSTALLER TO OBTAIN DISPOSAL WORKS
PERMIT BEFORE STARTING WORK.
-ALL COMPONENTS INSTALLED SHALL MEET
THE MINIMUM REQUIREMENTS OF
MASSACHUSETTS TITLE 5 SEPTIC
CODE (310 CMR 15).
-INSTALLER TO VERIFY LOCATIONS OF ALL
UNDERGROUND UTILITIES BEFORE
EXCAVATING FOR SYSTEM.
-ECO-TECH RAPID RESPONSE RECOMMENDS
THE INSTALLATION OF LOW FLOW
FIXTURES & APPLIANCES. AND PERIODIC
PUMPING OF THE SEPTIC TANK.
-SYSTEM IS NOT DESIGNED TO WITHSTAND
VEHICULAR LOADING. DO NOT PARK OR
DRIVE VEHICLES OVER SEPTIC SYSTEM.
1000 GALLON SEpTOC TANKI in CO
EXISTING UNIT - DIMENSIONS & DETAIL
TANK TO BE PUMPED DRY AT TIME OF INSTALLATION
AND EXAMINED FOR STRUCTURAL INTEGRITY. INSTALL
NEW PVC OUTLET TEE EQUIPPED WITH A GAS BAFFLE.
REPLACE WITH A NEW
1500 GALLON TANK
TAPERCRACKED, ROTTED
OR OTHERWISE
COMPROMISED.
� c
0
o NOT
TO
� SCALE
8 ft 6
INLET INSTALL FILTER (ZABEL) OUTLET
COVER ON OUTLET TEE COVER
� �3 IN DROPFLOW LINE
FROM 10 in _ 14 TO
BUILDING ,,,
D -BOX
48 in
LIQUID GAS �
LEVEL BAFFLE
,STONE BASE IF NEW
SEPARATION BETWEEN INLET & OUTLET
TEES NO LESS THAN LIQUID DEPTH
CROSS SECTION VIEW
BUOYANCY CALCS
SEASONAL HIGH GROUNDWATER = 19.63
BOTTOM OF SEPTIC TANK = 18.50
DEPTH OF WATER DISPLACED = 1.13
EXTERIOR DIMENSIONS OF UNIT = 8.5 ft x 4.83 ft
8.5 x 4.83 x 1.13 = 46.4 cu ft x 7.48 = 347 GAL
347 GAL x 8 Ib/ 801 = 2777 #
SEPTIC TANK WEIGHS 8240#
SEPTIC TANK WILL NOT FLOAT
SOo§L QeSOoRp'r§OoN
S� YS -rEIF
M CONSTRUCTION DETAIL
USE ADS ARC 36 LP LOW PROFILE B/ODIFFUSERS
INSPECTION
PORT 25.0 ft
O
u�
M
O
25 UNITS TOTAL - 5.0 ft PER UNIT
CROSS SECTION VIEW
RESTORE VEGETATIVE COVER
BACKFILL WITH CLEAN PERC
SAND TO TOP OF CHAMBERS
3.8 in O -PRO 8 inch
F DEPTH UNITS TOTAL DEPTH
EFH
2.875' EXISTING
SUITABLE
EFFECTIVE WIDTH = 5 x 2.875' = 14.375' MATERIAL
REFER TO DEP APPROVAL LETTER TRANSMITTAL
# X264258 FOR CERTIFICATION OF INFILTRTATOR
SYSTEMS BIODIFFUSER UNITS.Q]�
ALL PIPE TO BE SCH. 40 PVC
AND TO PITCH AT 1/8 in/ft MIN'S VENT
RAISE COVERS TO WITHIN PIPE
F � _ 24.43 + - 6 i n O F FINAL GRADE
*PIPE FROM PUMP CHAMBER TO D -BOX SHALL BE 2 in
SCH. 80 PVC WITH 1 cu ft OF THRUST BLOCKING AT BENDS.
25.35 �l
'yq
D -BOX 12 in INSPECTION - -sl pP
TEE 24.35
MIN PORT F
EXISTING 24.30
yy�� w,' �y� REFER TO DETAIL BOX
rN=�: PROPOSED 24.13
22.75 6 in � +
SEPTIC TANK 1000 GALLON �p
REFER TO DETAIL BOX EXISTING PU11� CHAA�ER 22.45 BEE S0�� ABSORPTION
18.50 24.00 ������ -REFER TO o
6 In STONE BASE IF NEW '.9 •`. � � �' 18.20 DETAIL BOX
22.70 6 In'STONE BASE 96 ft 4-11 ft 23.G8 ADJUSTED SEASONAL T 4
EXISTING 5 ft HIGH GROUNDWATER 19.63
SEWAGE DISPOSAL SYSTEM PLAN 25 FILLMORE ROAD YARMOUTH, MA JUNE 27. 2019 ETE-4394 PG 2/2