HomeMy WebLinkAboutEngineered Plan - 2019GENERAL NOTES:
A.) NEITHER DRIVEWAYS NOR PARKING AREAS ARE ALLOWED OVER SEPTIC SYSTEM
UNLESS H-20 COMPONENTS ARE -USED.
B.) THE DESIGNER WILL NOT BE RESPONSIBLE FOR THE SYSTEM AS DESIGNED UN-
LESS CONSTRUCTED AS SHOWN. ANY CHANGES SHALL BE APPROVED IN WRITING.
C.) CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION OF ALL
UNDERGROUND AND OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF WORK.
CONSTRUCTION NOTES:
1.) ALL CONSTRUCTION SHALL CONFORM TO THE STATE ENVIRONMENTAL CODE,
TITLE 5, AND THE REQUIREMENTS OF THE LOCAL BOARD OF HEALTH.
2.) SEPTIC TANK(S), GREASE TRAP(5), DOSING CHAM15ER(5) AND DISTRIBUTION
BOX(E5) SHALL BE SET ON A LEVEL STABLE BASE WHICH HAS BEEN MECHANICALLY
COMPACTED, OR ON A G INCH CRUSHED STONE BASE.
3.) SEPTIC TANKS) SHALL MEET ASTM STANDARD C 1 127-93 AND SHALL HAVE
AT LEAST THREE 20" DIAMETER MANHOLES. THE MINIMUM DEPTH FROM THE BOT-
TOM OF THE SEPTIC TANK TO THE FLOW LINE SHALL BE 48". j
4.) SCHEDULE 40 PVC INLET AND OUTLET TEES SHALL EXTEND A MINIMUM OF G"
ABOVE THE FLOW LINE OF THE SEPTIC TANK AND SHALL BE INSTALLED ON THE
CENTERLINE OF THE TANK DIRECTLY UNDER THE CLEANOUT MANHOLE.
5.) RAISE COVERS OF THE SEPTIC TANK AND DISTRIBUTION BOX WITH PRECAST
CONCRETE WATER TIGHT RISERS OVER INLET AND OUTLET TEES TO WITHIN G" OF
FINISH GRADE, OR AS APPROVED BY THE LOCAL BOARD OF HEALTH AGENT.
G.) PIPING SHALL CONSIST OF 4" SCHEDULE 40 PVC OR EQUIVALENT. PIPE SHALL
BE LAID ON A MINIMUM CONTINUOUS GRADE OF NOT LESS THAN I %.
7.) DISTRIBUTION LINES FOR SOIL ABSORPTION SYSTEM (AS REQUIRED) St
4" DIAMETER SCHEDULE 40 PVC LAID AT 0.005 FT/FT. LINE SHALL BE CAPI
AT END OR AS NOTED.
8.) OUTLET PIPES FROM DISTRIBUTION BOX SHALL REMAIN LEVEL FOR AT L
2' BEFORE PITCHING TO SOIL ABSORPTION SYSTEM. WATER TEST D15TRIB
BOX TO ASSURE EVEN DISTRIBUTION.
9.) DISTRIBUTION BOX SHALL HAVE A MINIMUM SUMP OF G" MEASURED BI
THE OUTLET INVERT.
10.) BASE AGGREGATE FOR THE LEACHING FACILITY SHALL CONSIST OF 3L
1-1 /2" DOUBLE WASHED STONE FREE OF IRON, FINES AND DUST AND SHAI
INSTALLED BELOW THE CROWN OF THE DISTRIBUTION LINE TO THE BOTTON
501L ABSORPTION SYSTEM. BASE AGGREGATE SHALL BE COVERED WITH /
LAYER OF 1/8" TO 1/2" DOUBLE WASHED STONE FREE OF IRON, FINES AND
1 1.) VENT SOIL ABSORPTION SYSTEM WHEN DISTRIBUTION LINES EXCEED
WHEN LOCATED EITHER IN WHOLE OR IN PART UNDER DRIVEWAYS, PARKING
TURNING AREAS OR OTHER IMPERVIOUS MATERIAL; OR WHEN PRESSURE D
12.) 501L ABSORPTION SYSTEM SHALL BE COVERED WITH A MINIMUM OF
CLEAN MEDIUM SAND (EXCLUDING TOPSOIL).
13.) FINISH GRADE SHALL BE A MAXIMUM OF 3G" OVER THE TOP OF ALL 5'
COMPONENTS, INCLUDING THE SEPTIC TANK, DISTRIBUTION BOX, D051NG
AND SOIL ABSORPTION SYSTEM. SEPTIC TANKS SHALL HAVE A MINIMUM
OF 9"• .
'14:) FROM THE. DATE OF INSTAM i iGN'0ff THE SOIL ABSORPTION SYSTEM
RECEIPT OF A CERTIFICATE OF COMPLIANCE, THE PERIMETER OF THE SOIL h�A_/',, -_
TION SYSTEM SHALL BE STAKED AND FLAGGED TO PREVENT THE USE OF SUCH
AREA FOR ALL ACTIVITIES THAT MIGHT DAMAGE THE SYSTEM.
15.) THE BOARD OF HEALTH SHALL REQUIRE INSPECTION OF ALL CONSTRUCTION I
BY AN AGENT OF THE BOARD OF HEALTH (OR THE DESIGNER IF THIS SYSTEM RE- I
QUIRES A VARIANCE) AND MAY REQUIRE SUCH PERSON TO CERTIFY IN WRITING
THAT ALL WORK HAS BEEN COMPLETED IN ACCORDANCE WITH THE TERMS OF THE i
PERMIT AND APPROVED PLANS. 48 HOURS ADVANCE NOTICE IS REQUESTED.
G.) INSTALLER SHALL VERIFY INVERT ELEVATIONS PRIOR TO INSTALLATION OF i
ANY SEPTIC SYSTEM COMPONENTS.
17.) EXISTING CESSPOOL # I TO BE PUMPED DRY, FILLED WITH CLEAN SAND,
AND ABANDONED IN PLACE.
18.) EXISTING WASTELINE(S): INSTALLER TO CONFIRM WASTELINE(S) BY WATER TESTING
WITHIN THE DWELLING PRIOR TO SETTING ANY SYSTEM COMPONENTS.
19.) INSTALLER TO CONFIRM LOCATION OF ALL UNDERGROUND AND OVERHEAD
UTILITIES PRIOR TO START OF CONSTRUCTION.
20.) EXISTING CESSPOOL #2 TO BE REMOVED. ANY CONTAMINATED 501L WITHIN 50
THE PROPOSED SOIL ABSORPTION SYSTEM SHALL BE REMOVED AND REPLACED WITH
. CLEAN SAND. AREA TO BE COMPACTED TO MINIMIZE SETTLING.
501L TEST LOGS:
TEST HOLE 1: EL=34.4±
DEPTH FROM
SURFACE
(INCHES)
501L
HORIZON
SOIL
TEXTURE
(USDA)
501L
COLOR
(MUN5ELL)
SOIL OTHER
MOTTLING
0-10
A
FINE LOAMY SAND
I OYR 412
NONE
10-30
B
FINE LOAMY SAND
I OYR 5/G
NONE
30-177
C
FINE -MEDIUM SAND
10YR G14
NONE PERC P, 59"• <2M1r IN
TEST HOLE 2: EL=34.7±
DEPTH FROM
SURFACE
(INCHES)
SOIL
HORIZON
SOIL
TEXTURE
(USDA)
SOIL
COLOR
(MUN5ELL)
SOIL OTHER
MOTTLING
LEGEND
0-15
A
FINE LOAMY SAND
10YR 4/2
NONE
EL=35.8±
1 5-5 1
B
FINE LOAMY SAND
I OYR 5/G
NONE PERC 43"' <2MIP4N
51-139
C
FINE -MEDIUM SAND
I OYR G/4
NONE NO G.W. ENCOUNTEkED
DATE OF TESTING: 8/21/19
PERCOLATION RATE: LESS THAN 2 MIN/INCH IN "B" � "C" LAYERS.
WITNESSED BY: MATTHEW J. WROBEL, EIT, J.M. O'REILLY � ASSOCIATES, INC.
PHIL RENAUD, AGENT, YARMOUTH HEALTH DEPARTMENT
NO WATER ENCOUNTERED
USE A LOADING RATE OF 0.74 GPD/SF FOR SIZING OF SOIL ABSORPTION SYSTEM.
PLAN VIEW
SCALE: I " = 10' BENCHMARK:
Top of Concrete Bound
�p EL=34.2± (NNVD 1 988)
FLOW PROFILE:
NOT TO SCALE
DEED BOOK 27031 PAGE 97
ASSESSORS' MAP 70 PARCEL 2G
FOUR (4) 24" DIAMETER CONCRETE
LEGEND
EXISTING CONTOUR
RAISED TO WITHIN G" OF FINISH
TOP OF FOUNDATION
GRADE (OR AS NOTED)
X 12.34 EXISTING SPOT GRADE
EL=35.8±
(SEE NOTE #5)
- W- WATER SERVICE LINE
Proposed EL= 35.0±
-o- OVERHEAD UTILITY SERVICE
-u- UNDERGROUND UTILITY SERVICE
_G_ GAS SERVICE LINE
_e TEST HOLE / BORING LOCATION
SST SEPTIC TANK
DB DISTRIBUTION BOX
SAS 501L ABSORPTION SYSTEM
Reserve RESERVED FOR FUTURE
EXISTING
32.50
10" 14"
C.C. CONCRETE CURB
'NOTE
P.F. PICKET FENCE
C.S. COVERED SLAB
3 T
Cob UTILITY POLE
4'0"
FIRE HYDRANT
GAS BAFFLE
17' ±_1 1 500 GALLON
SEPTIC TANK
`NOTE: SEPTIC TANK INLET INVERT ELEVATION WAS ESTABLISHED
BASED ON EXISTING CESSPOOL INLET INVERT EL=32.7±.
32_00/ 31.8
2" DRO
DB -3
D -"BOX
H-20
5Y5TEM DE51GN CALCULATIONS:
SEWAGE DE51GN FLOW:
BEDROOM DWELLING @ 110 GPD = 330 GPD
LEACHING CAPACITY REQUIRED:
3 BEDROOMS (MAX.) @ I 10 GPD = 330 GPD REQUIRED
SEPTIC TANK CAPACITY REQUIRED:
DAILY FLOW = 330 GPD @ 200% = GGO GAL. REQUIRED
SEPTIC TANK CAPACITY PROVIDED:
1 500 GALLON SEPTIC TANK (MIN. ALLOWED)
LEACHING CAPACITY PROVIDED:
ONE (1) 25.0'X 12.53' X 2.0' LEACHING CHAMBER CAN LEACH:
Vt=((25.0 X 12.53) + (25.0 X 2.0)2 + (12.83 X 2.0)2] X 0.74 GPD/5F=349.3 GPD
349 GPD>330 GPD REQUIRED
NOTE: A GARBAGE DISPOSAL IS NOT PERMITTED WITH THIS DESIGN.
INSTALL:
ONE (1) - 1500 GALLON SEPTIC TANK
ONE (1) - 3 OUTLET DISTRIBUTION BOX (H-20 Rated)
TWO (2) - 500 GALLON LEACH CHAMBERS WITH 4' OF STONE ALL AROUND
i
4
X '�4,9
�I
X 34.9
23S,X
35.3 x
N
7
4 PARCEL 2G rye. 5.1
\'Area=0.49 AC±
34,7 35.5 x
�4
Y
=_ .. 33.6 / 34.6 -
lP
34.5 G3.31±
x 343
4.5
S�•'o
de Fenc ryry
e
Existing Cesspool # I /,9/ 4.6
TO BE ABANDONED
(SEE NOTE # 17)
INSPECTION NOTE:
PRIOR TO FINAL INSPECTION BY THE ENGINEER, SYSTEM
NEEDS TO BE COMPLETE INCLUDING BUILDUP FOR COVERS.
EL=34.5± r -Proposed EL=34.5±
Existing Cesspool #2
TO BE REMOVED
34.7 /(SEE NOTE #20)
X 34.6
YARMOUTH,
MA
LOCUS
�Q% z
1 \ooA Charles St.
ry x 34,6
v
c0 5,0 34.7
Fdye
OcO f of Cjea 34.4
'� '"tz .. rip13 34-
P. FND lc 34.0
r.
34.6
347 ;` �r ;11\\ w�„ j;""::'.'•;;'.': 34.0
ooh j W"":.•`,:."Oram,. ,: w
34.5
qj
t 3
.9
t �O tl w\ O. 0
t SA www �a vV 0�
34.4 G4.5 34,5
40
c �_Z�
4.7 " �: 35.3 _Q�
s, J
PLAN
SCALE 1 "=30'
TH 15 AREA 15 SERVED
BY TOWN WATER.
25" Proposed
32.4± (9" Min - 3G" Max)
2" LAYER OF 1/8"- 1 /2" STONE
3 I .GO 3/4" - 1-1 /2" STONE
3 N N
P
29.60 r
USE TWO (2) SHOREY PRECAST
500 GALLON LEACH CHAMBERS 9.9'±
Longest Run WITH 4' OF STONE AROUND
14'± (END VIEW)
LEACHING CHAMBER EL= 19.7± BorroM of TP#i
25.0'x 1 2.83'x 2.0'
G:\AAJobs\The
NOT TO SCALE \
DEED BOOK 27031 PAGE 97
ASSESSORS' MAP 70 PARCEL 2G
LEGEND
EXISTING CONTOUR
32 PROPOSED CONTOUR
X 12.34 EXISTING SPOT GRADE
24X5 PROPOSED SPOT GRADE
- W- WATER SERVICE LINE
-o- OVERHEAD UTILITY SERVICE
-u- UNDERGROUND UTILITY SERVICE
_G_ GAS SERVICE LINE
_e TEST HOLE / BORING LOCATION
SST SEPTIC TANK
DB DISTRIBUTION BOX
SAS 501L ABSORPTION SYSTEM
Reserve RESERVED FOR FUTURE
5 STEP
C.C. CONCRETE CURB
P.F. PICKET FENCE
C.S. COVERED SLAB
Cob UTILITY POLE
® CATCH BASIN
FIRE HYDRANT
-
® DRAINAGE MANHOLE
■ CONCRETE BOUND, FOUND
O IRON PIPE, FOUND
>�x LIGHTP05T
- W - TOP OF BANK
-X-X- LIMIT OF WORK
FENCE
EDGE OF CLEARING
WV
�Q WATERGATE
Permit valid for REPAIR OF SEPTIC SYSTEM
ONLY, dae to State and Local septic variances.
Board of llealth review and approval is reeeired for
any future additions/renovations/alterations to ,
sewage facilities and/or structures/dwelling.
Yarmouth ilea€thDepartr*a.;rt
APPROVED
1 1 ✓?
I i
i
I
i
OF S�Jt9 I
The Davenport Compan1e5
ill-iiM. �' 20 North Main Street, South Yarmouth_ , MA 02GG4
Ji! �� ; �
9`�'"''( SITE SEWAGE DISPOSAL SYSTEM DESIGN
Ei BLLI �` PCO. 36200 �
7Q 105 North Main 5tre(!�t, Yarmouth, MA 02GG4
J.M. OTEILLY & ASSOCIATES, INC.
Professional Engineering & Land Surveying Services
1573 Main Street - Route 6A
0 30 GO 90
P.O. Bog 1773
(508)896-6601 Office Brewster, MA 02631 (508)896-6602 Fax
SCALE I "=30' DATE: SCALE: BY: CHECK: JOB NUMBER:
08/27/19 A5 Noted MJW JMO JMO-8777
Companie5\8777 - 105 North Main St. Yarmouth\DWG\8777.SD5 PLAN