Building Air-Tightness Test Form
BUILDING DEPARTMENT
By.
Customer Information: Building&Test Conditions:
Name: MJ Nardone Building & Remodeling
Address: 299 White's Path
City:
South Yarmouth Date: 9/24/2019
State/Zip: MA/02664
Phone: (508)771-9927
Time: 4:30 P.M.
Email: Mike@mjnardone.com
Building Address: (if different from above)
Street: 25 Powers Lane Floor Area (ft2): 3150 s.f.
City/State: West Yarmouth, MA
Comments: Permit #: BLD-19-001459 Issued: 09/24/2019
Standard Level Accuracy
Mechanical Ventilation: Aprilaire Heat Recovery Ventilator Model 8100
65 CFM = Minimum Continuous Run-Time Rate in Accordance with ASHRAE62.2(2013)
Test#1 Depress: V Press: Test#2 Depress: V Press:
Pre-test Baseline Pressure: -0.4 (Pa) Pre-test Baseline Pressure: -0.5 (Pa)
Bldg Press. Flow Ring Fan Press Flow Bldg Press. Flow Ring Fan Press Flow
(Pa) Installed (Pa) (cfm) (Pa) Installed (Pa) (cfm)
-50.4 B -50.8 1207 -50.4 B -50.9 1210
-50.5 B -50.9 1208 -50.7 B -51.2 1202
-50.7 B -51.0 1202 -50.7 B -51.2 1206
-50.5 B -50.9 1214 -50.6 B -51.1 1208
-50.1 B -50.5 1211 -50.2 B -50.7 1217
Post-test Baseline Pressure: -0.1 (Pa) Post-test Baseline Pressure: -0.3 (Pa)
Fan Model/SN: Minn BD 130927 Fan Model/SN: Minn BD 130927
Results: Results:
CFM50: 1208.4 CFM50: 1208.6
ACH50: 2.9 ACH50: 2.9
HERS Rater Name and Cert.#: Chris Picariello Cert.#: 6397177
HERS Rater Signature and Date:CA: 9/24/2019
Developed by Advanced Building Analysis,LLC