Loading...
HomeMy WebLinkAboutbuilding Air Tightness RECEIVED rSEP26 2019 Building Air-Tightness Test Form BUILDING DEPARTMENT By. Customer Information: Building&Test Conditions: Name: MJ Nardone Building & Remodeling Address: 299 White's Path City: South Yarmouth Date: 9/24/2019 State/Zip: MA/02664 Phone: (508)771-9927 Time: 4:30 P.M. Email: Mike@mjnardone.com Building Address: (if different from above) Street: 25 Powers Lane Floor Area (ft2): 3150 s.f. City/State: West Yarmouth, MA Comments: Permit #: BLD-19-001459 Issued: 09/24/2019 Standard Level Accuracy Mechanical Ventilation: Aprilaire Heat Recovery Ventilator Model 8100 65 CFM = Minimum Continuous Run-Time Rate in Accordance with ASHRAE62.2(2013) Test#1 Depress: V Press: Test#2 Depress: V Press: Pre-test Baseline Pressure: -0.4 (Pa) Pre-test Baseline Pressure: -0.5 (Pa) Bldg Press. Flow Ring Fan Press Flow Bldg Press. Flow Ring Fan Press Flow (Pa) Installed (Pa) (cfm) (Pa) Installed (Pa) (cfm) -50.4 B -50.8 1207 -50.4 B -50.9 1210 -50.5 B -50.9 1208 -50.7 B -51.2 1202 -50.7 B -51.0 1202 -50.7 B -51.2 1206 -50.5 B -50.9 1214 -50.6 B -51.1 1208 -50.1 B -50.5 1211 -50.2 B -50.7 1217 Post-test Baseline Pressure: -0.1 (Pa) Post-test Baseline Pressure: -0.3 (Pa) Fan Model/SN: Minn BD 130927 Fan Model/SN: Minn BD 130927 Results: Results: CFM50: 1208.4 CFM50: 1208.6 ACH50: 2.9 ACH50: 2.9 HERS Rater Name and Cert.#: Chris Picariello Cert.#: 6397177 HERS Rater Signature and Date:CA: 9/24/2019 Developed by Advanced Building Analysis,LLC