Air Leakage Report
237 Main Street Test Mode
Yarmouth Depressurization
05/28/2019 Test Pressure
Lohr Construction 50.0 Pascals
Test Equipment
2009 IECC Energy Code Retrotec
RECEIVEf
BUILDING DEPARTMEN"T
By J
Total Air Leakage Or Air Changes Per Hour Gauge
864 2.59
Conditioned Volume
20000
This project meets the criteria for the following:
2009 International Energy Conservation Code
2012 International Energy Conservation Code
2015 International Energy Conservation Code
180 STATE ROAD SUITE 2U SAGAMORE BEACH,MA 02562-(508)833-3100-ENERGYCODEHELP.COM-INFO@ENERGYCODEHELP.COM
powered bycgocanvos www.gocanvas.com �_. >_3
•• HOME ENERGY RATERS L LC
BUILDING PERFORMANCE TESTING
Duct Leakage Report
237 Main Street Test Mode
Yarmouth Depressurization
05/28/2019 Test Pressure
Lohr Construction 25.0 Pascals
Testing Equipment
2009 IECC Energy Code Minneapolis
111
Total CFM@25 or Total Duct Leakage Percentage
72.00 0.03
Total Square Footage
2300.00
Maximum Allowable Leakage
92.00
HVAC Duct Test
Mechanical Room 2300 B 72 0.03
180 STATE ROAD SUITE 2U SAGAMORE BEACH,MA 02562-(508)833-3100-ENERGYCODEHELP.COM-INFO@ENERGYCODEHELP.COM
powered by gocanvos www.gocanvas.com ,• -�
._ •
HOME ENERGY RATERS L LC
BUILDING PERFORMANCE TESTING
Ventilation Report
Ventilation Tests
1st floor bath 75 6 hrs
- coNflG
tons
2nd floor bath 73 6 hrs
ME AVG
UNITS caries
u.,..
n.,.
180 STATE ROAD SUITE 2U SAGAMORE BEACH,MA 02562-(508)833-3100-ENERGYCODEHELP.COM-INFO@ENERGYCODEHELP.COM
powered bycgocanvas www.qocanvas.com - -
•• HOME ENERGY RATERS L LC
BUILDING PERFORMANCE TESTING
Compliance Option t1:
Follow these steps to determine compliance for the fan Airflow.
1) Determine the floor area of the conditioned space of the home=(A )
2) Determine number of Bedrooms.al&.f)
3) Insert these number in the formula Below:
Fan airflow(CFM)=0.01Anoor+7.5(Na+1)
Fan Airflow for Homes with Average Air Leakage
Floor Area(ft2) No.Of Bedrooms
0-1 2-3 4-5 6-7 >7
<1500 30 45 60 75 90
1501-3000 45 60 75 90 105
3001-4500 60 75 90 105 120
4501-6000 75 90 105 120 135
6001-7500 90 105 120 135 150
>7500 105 120 135 150 165
Fan airflow is CFM.