2015 IECC R-406 RESNET
IIESNET
RESIDENTIAL ENERGY SERVICES NETVvORK
Registered Energy Rating Index
Report
Property Organ'Report
Energy Rating Index Information
Builder:Toni Smith Company:Home Energy Raters LLC RESNET Registered Rating
Address: Phone:508-833-3100 Rating No:733036350
75 Sisters Circle, Yarmouth Port,MA Rater:Andrew Popielarski Rater ID(RTIN):5363711
02675 Date Rated:2019-09-03
HERS Index Estimated Annual Energy Consumption*
mom Energy Rated Home Calculated Rated Home Cost($/yr)
Energy Use(MBtu)
150
Existing 140 Heating 34.5 $587
Homes 13o Cooling 0.3 $20
120 Water Heating 11.1 $183
110
Reference Lights &Appliances 16.7 $901
Home "`•i yo Photovoltaics 0.0 $0
eitaw
'Based on standard operating candhons
60
so '1 ERI with PV:55
This Home ERI without PV:55
30
20 Annual Estimates
Zero Energy 10 Electric(kWh):4,237.1 CO2 Emissions(Tons):5.5
Home 0
Natural Gas(Therms):481.1 Energy Savings($)**:N/A
1414 Emir/
01013 RESM Y 'Based on the 2015 IECC R406 ReleRroe design rome
Maximum Energy Rating Index:55 This Home's Energy Rating Index:55 PASS
This home MEETS the Energy Rating Index Score requirement of 2015 IECC R-406 for Climate Zone 5. It
MEETS all of the requirements verified by Ekotrope. Mandatory requirements are summarized on the 2nd page
of this report, some of which are not verified by Ekotrope.
Name: Andrew Popielarski Signature: Pepiela t4/n
Organization: Home Energy Raters LLC Digitally signed: 9/4/19 at 9:30 AM
Rati • Provider Data and Seal
4 h�r
Company:Energy Raters of Massachusetts ' ,•
Address:2 Woodlawn Street Amesbury,MA 01913
Phone#:978-270-3911 \ ""'°"'16 4
Fax#: .4°
C'ttarywtfO
To determine if a provider is properly accredited go to:www.rennet.us/professionaUprograms/search_directory
Home Energy Rating Certificate Rating Date: 2019-09-03
Final Report Registry ID: 733036350
p Ekotrope ID: YdxJXPZ2
HERS® Index Score: Annual Savings Home:
Your home's HERS score is a relative 75 Sisters Circle
performance score. The lower the number, $ 1 55 783 Yarmouth Port, MA 02675
the more energy efficient the home.To Builder:
learn more, visit www.hersindex.com *Relative to an average U.S.home Toni Smith
Your Home's Estimated Energy Use: This home meets or exceeds the
Use[MBtu] Annual Cost criteria of the following:
Heating 34.5 $587 2015 International Energy Conservation Code
Cooling 0.3 $20 ;,;
Hot Water 11.1 $183
Lights/Appliances 16.7 $901
Service Charges $0
Generation (e.g.Solar) 0.0 $0 •
Total: 62.6 S1,691
HERS Index Home Feature Summary: Rating Completed by: •
41111•4 Ner•w•a Home Type: Single family detached Energy Rater.AndrewPopielarski
sso Model: N/A RESNET I D:5363711
Existing 103 Community: N/A
s iso Conditioned Floor Area: 1,641 ft� Rating Gompany:l ome Energy Raters LLC
1120
„ Number of Bedrooms: 3 180 State Rd,Suite 2U Sagamore Beach MA 02562
Reference 508-833-3100
Home ion Primary Heating System: Fu rnace•Natural Gas•95 AFUE
90 Primary Cooling System: Air Conditioner•Electric•13 SEER Rating Provider:Energy Raters of Massachusetts or . ` '`°R
w PrimaryWater Heating Water Heater•Natural Gas•0.93 EnergyFactor 2 Wood lawn Street Amesbury,MA 01913 ;,- , °
,o 9 I 1
bo
House Tightness: 624 CFM50(2.51 ACH50) 978-2703911 v ypa
'o Ventilation: 74.0 CFM•13.2 Watts "'".•"°"
ao This Home
Duct Leakage to Outside: 55 CFM25(3.35/100 s.f.)
30
so Above Grade Walls: R-21 4/2/A
so Ceiling: Attic,R-37 ,?(,1a e,GUL POWLA&
Zero Energy 0
Home Window Type: U-Value:0.3,SHGC:0.3 Andrew Popielarski,Certified energy Rater
e„1/,1„e, `""""" Foundation Walls: WA Digitally signed 9/4/19at9:3(1AM .,
eicot ope, Ekotrope RATER-Version:3.1.0.2244
The Energy Rating Disclosure for this home is available from the Approved Rating Provider.
This report does not constitute any warranty or guarantee.
Building Specification Summary
Property Organization Inspection Status
75 Sisters Cirde Home Energy Raters LLC 2019-09-03
Yarmouth Port, MA 02675 508-833-3100 Rater ID(RTIN): 5363711
Andrew Popielarski RESNET Registered
Sisters Cirde 75-final (Confirmed)
Sisters Cir 75- YdxJXPZ2 Builder
Toni Smith
Building Information Rating
Conditioned Area(ft2] 1,641.00 HERS Index 55
Conditioned Volume[ft3j 14,931.00 HERS Index w/o PV 55
Thermal Boundary Area[ft2] 5,210.00
Number Of Bedrooms 3
Housing Type Single family detached
Building Shell
Ceiling w/Attic I R37,DPCE,10",10x16,G1 U-0.03 Windows(largest)I U-Value:0.3, SHGC:0.3
Vaulted Ceiling I None Window/Wall Ratio 10.12
Above Grade Walls I R21,FG,6x16,G1 U-0.05 Infiltration(624 CFM50(2.51 ACH50)
Found.Walls 1 None Duct Lkg to Outside 155 CFM25(3.35/100 s.f.)
Framed Floors I R30,FG,12x16,G1 R-30 Total Duct Leakage 155 CFM25(Rough-In,with Air Handler)
Slabs I None
Mechanical Systems
Heating Furnace •Natural Gas •95 AFUE
Cooing Air Conditioner•Electric • 13 SEER
Water Heating Water Heater• Natural Gas•0.93 Energy Factor
Programmable Thermostat Yes
Ventilation System 74.0 CFM • 13.2 Watts
Lights and Appliances
Percent Interior LED 100% Clothes Dryer Fuel Bectric
Percent Exterior LED 100% Clothes Dryer CEF 4.3
Refrigerator(kWh/yr) 633.0 Clothes Washer LER (kWh/yr) 82.0
Dishwasher Efficiency 269 kWh Clothes Washer Capacity 3.2
Ceiling Fan(CFM/Watt) 70.4 Range/Oven Fuel Natural Gas
Ekotrope RATER-Version 3.1.02244
N results are based on data entered by Ekotrope users.Ekotrope disclaims all fabiiy for the information shown on this report.
Air Leakage Report
Property Organization Inspection Status
75 Sisters Cirde Home Energy Raters LLC 2019-09-03
Yarmouth Port, MA 02675 508-833-3100 Rater ID(RTIN): 5363711
Andrew Popielarski RESNET Registered
Sisters Cirde 75-final (Confirmed)
Sisters Cir 75- YdxJXPZ2 Builder
Toni Smith
General Information
Conditioned Floor Area[sq.ft.] 1,641
Infiltration Volume[cu.ft.] 14,931
Number of Bedrooms 3
Air Leakage
Measured Infiltration 624 CFM50(2.51 ACH50)
ACH50(Calculated) 2.51
ELA[sq. in.] (Calculated) 34.32
ELA per 100 s.f. Shell Area(Calculated) 0.659
CFM50(Calculated) 624
CFM50/s.f. Shell Area(Calculated) 0.120
Duct Leakage
System 1
Leakage to Outdoors 55 CFM25 (3.35/100 s.f.)
Total Leakage Test Type Rough-In, with Air Handler
Total Leakage[CFM 0 25 Pa] 55.0
Total Leakage [CFM25/100 s.f.] 3.4
Total Leakage[CFM25/CFA] 0.034
Mechanical Ventilation
Rate[CFM] 74.0
Hours per day 19.4
Fan Watts 13.2
Recovery Efficiency% 0.0
Runs at least once every 3 hrs? true
Average Rate[CFM] 59.8
2010 ASHRAE 62.2 Req.Cont.Ventilation 46.4
2013 ASHRAE 62.2 Req.Cont.Ventilation 59.7
Ekotrope RATER-Version 3.1.02244
Al results are based on data entered by Ekotrope users.Ekotrope disclaims al lability for the information shown on this report.
RESNET HOME ENERGY
RATING Standard Disclosure
For home(s) located at: 75 Sisters Circle, Yarmouth Port, MA
Check the applicable disclosure(s) in accordance with the
instructions on the reverse of this page:
011. The Rater or the Rater's employer is receiving a fee for providing the rating on this home.
02. In addition to the rating, the Rater or the Rater's employer has also provided the following consulting
services for this home:
—A. Mechanical system design
D B. Moisture control or indoor air quality consulting
C. Performance testing and/or commissioning other than required for the rating itself
O D. Training for sales or construction personnel
E. Other(specify)
3. The Rater or the Rater's employer is:
LJA. The seller of this home or their agent
f[B. The mortgagor for some portion of the financed payments on this home
VC. An employee, contractor, or consultant of the electric and/or natural gas utility serving this home
j4. The Rater or Rater's employer is a supplier or installer of products, which may include:
Products Installed in this home by OR is in the business of
HVAC systems IIRater [ [Employer LIRater [—Employer
Thermal insulation systems jRater . Employer Rater Employer
Air sealing of envelope or duct systems FiRater Employer FiRater fEmpbyer
Energy efficient appliances [Rater 'Employer [Rater liEmpbyer
Construction (builder, developer,construction contractor, etc) ERater I [Employer [Rater Employer
Other(specify); r Rater j [Employer Rater l[Employer
Wit5. This home has been verified under the provisions of Chapter 6, Section 603 "Technical Requirements for
Sampling" of the Mortgage Industry National Home Energy Rating Standard as set forth by the Residential Energy
Services Network (RESNET). Rater Certification#: 5363711
To report any complaints regarding this Rater's service, please visit: http://www.energyratersma.com/Feedback_New.html
Name: Andrew Popielarski Signature: /i(r,, uat Pepielandd
Organization: Home Energy Raters LLC Digitally signed: 9/4/19 at 9:30 AM
I attest that the above information is true and correct to the best of my knowledge. As a Rater or Rating
Provider I abide by the rating quality control provisions of the Mortgage Industry NationalHome Energy
Rating Standard as set forth by the Residential Energy Services Network(RESNET). The national rating
quality control provisions of the rating standard are contained inChapter One 4.C.8. of the standard and are
posted at
http://resnet.us/standards/RESNET_Mortgage_Industry_National_H ERS_Standards.pdf
The Home Energy Rating Standard Disclosure for this home is available from the rating provider.
RESNET Form 03001-2 -Amended April 24, 2007
Mass Save RNC PFS Savings Report
Property Organization Inspection Status
75 Sisters Circle Home Energy Raters LLC 2019-09-03
Yarmouth Port,MA 02675 508-833-3100 Rater ID(RTIN):5363711
Andrew Popielarski RESNET Registered
Sisters Orde 75-final (Confirmed)
Sisters Or 75-YdXJXPZ2 Builder
Toni Smith
Annual End-Use Consumption Reference Home Rated Home Savings % Saved
Heating[Natural Gas Therms] 560.6 458.9 101.7 18.1%
Heating[Electric kWh] 170.3 141.2 29.1 17.1%
Cooling[Electric kWh] 194.0 200.9 -6.8 -3.5%
Hot Water[Natural Gas Therms] 138.4 110.7 27.7 20%
Lights&Appliances[Natural Gas Therms] 29.2 29.2 0.0 0%
Lights&Appliances[Electric kWh] 4,041.3 4,041.3 0.0 0%
Total[Natural Gas Therms] 728.2 598.8 129.4 17.8%
Total[Electric kWh] 4,405.6 4,383.3 22.3 0.5%
Electric Savings Incentive $7.79
Fuel Savings incentive $452.94
Percent Savings Incentive $444.58
Rater Incentive' $350.00
Participant Incentive $905.30
Percent Savings 14.82%
'Rater Incentive is distributed directly to Rater by Mass Save Program.
Ekotrope RATER-Version 3.1.02244
AM results are based on data entered by Ekotrope users.Ekotrope dsclaims all lability for the information shown on this report.
IECC 2015 Label
75 Sisters Circle
Ekotrope RATER -Version:3.1.0.2244
HERS® Index Score: 55
Ceiling: R-37
Above Grade Walls: R-21
Foundation Walls: N/A
Exposed Floor: R-30
Slab: null
Infiltration: 624 CFM50(2.51 ACH50)
Duct Insulation: R-6
Duct Lk• to Outdoors: 55 CFM25 3.3.5/100 s.f.
.
U-Value: 0.3, SHGC: 0.3
Door: R-7
Heating: Furnace • Natural Gas• 95 AFUE
Cooling:Air Conditioner • Electric • 13 SEER
Hot Water:Water Heater• Natural Gas •0.93
Ener.) Factor
(Confirmed and tested)
Climate Zone 5 Mandatory Requirements
Provision Number Topic Compliance Decision
2009 IECC Table Building thermal envelope minimum insulation levels and PASS
402.1.1 or 402.1.3 maximum fenestration U-factor and SHGC
R401.3 Post a permanent certificate listing the level of efficiencies Certificate required for CO
installed in the house
R402.4.1.2 Envelope ak leakage maximum leakage rate PASS
R402.4.1 /Table Comply with air sealing and insulation requirements in Table Checklist required for CO
R402.4.1.1 R402.4.1.1
R402.4.4 Rooms containing fuel-burning appliances PASS*
R402.5 Maximum fenestration U-factor and SHGC (U-Factor) PASS
(SHGC) PASS
R403.1.2 Heat pump controls PASS*
R406.2 Ducts outside of conditioned space to be insulated to a PASS*
minimum of R-6.
R403.3.2 Duct seeing on all ducts PASS*
R403.3.3 Duct testing for ducts in unconditioned space PASS*
R403.3.5 Building cavities not used as ducts. PASS*
R403.5.1 Heated water circulation and temperature maintenance PASS*
systems comply
R403.5.3 Hot water pipe insulated to R-3 FAIL
R403.6 Mechanical ventilation meeting the requirements of the IRC PASS*
or IMC. Outdoor air and exhaust dampers installed
R403.7 ACCA Manual J and S conducted for all heating and cooling ACCA forms required for
systems. permit
R403.8 Systems serving multiple dwelling units to meet the PASS*
mechanical requirements of IECC commercial code
R403.9 Snow melt and ice system controls installed where applicable PASS*
R403.10 Pools and permanent spa energy consumption meet PASS*
requirements for heaters,time docks and covers
R403.11 Portable spas meet the requirements of APSP-14. PASS*
R404.1 High efficacy lights installed in 75%of permanently instated PASS
fixtures.
These items have been field-verified by the Rater,Field Inspector, Code Inspector,or Builder.