HomeMy WebLinkAbout2019 Nov 15 - J.M. O'Reilly & Assoc. FAST Field Inspection & Service Report J.M. O'Reilly & Associates, Inc. LETTER OF
Engineering&Land Surveying Services
1573 Main Street,2nd Floor,P.O.Box 1773 TRANSMITTAL
Brewster,MA 02631
(508)896-6601
Fax(508)896-6602
TO: DATE: JOB NUMBER:
Town of Yarmouth 11/15/2019 6878W
Board of Health
1146 Route 28 REGARDING:
South Yarmouth, MA 02664
LOCUS: 115 Merchant Ave,Yarmouthport
Shipping Method:
Ki=CKsJI='
Regular Mail n Federal Express ri
Certified Mail UPS NOV ? 0 2019
Priority Mail n Pick Up El HEALTH DEPT
Express Mail n Hand Deliver n
COPIES DATE DESCRIPTION
1 9/30/19 DEP Approved Inspection and O&M Form for Title 5 I/A Treatment and Disposal Systems
FAST Field Inspection& Service Report
Test Results
For review and comment: For approval: As Requested: For your use: '-
REMARKS:
cc: John M. O'Reilly, P.E., P.L.S.
Matthew Wrobel, E.I.T.
DEP
Client
From: MJW
If enclosures are not as noted,kindly notify us at once
FIELD INSPECTION & SERVICE REPORT
FAST® wastewater treatment systems
INSTALLATION AUTHORIZED SERVICE PROVIDER
Installation Address 115 Merchant Ave, Yarmouthport Namej.M. O'Reilly & Associates, Inc.
Owner Name Cheryl Burnham Street 1573 Main Street,Brewster,MA
Mail Address 115 Merchant Ave Mail Address P.O. Box 1773
City Yarmouthport State MA Zip 02631 City Brewster State MA Zip 02631
Phone 774-238-6165 Fax Phone 508-896-6601 Fax 508-896-6602
e-mail cherylb115@comcast.net e-mail mwrobel@jmoreiilyassoc.com
INSTALLATION INFORMATION
Model No. Serial No. Date of Installation Date of last pumpout
Microfast 0.5 12/20/2001 Unknown
MAINTENANCE PERFORMED
EQUIPMENT YES NO AND COMMENTS
Electrical Panel(s)
Visual Alarm Operating x
Audio Alarm Operating
X
(if present)
Blower(s)
Air Inlet Filter Clean x
Blower Hood Vents Clear x
Excessive Noise x
Excessive Vibration x
Treatment Unit(s)
Unusual Odor x
Pumpout Required:
Primary Settling Zone
Aerobic Treatment Zone x
EFFLUENT(options) LIMIT RESULT
Estimated Daily Flow
pH(Standard Units) 6-9 S.U. 7.41
Color Clear Brown
Temperature 66.6 F
Odor Slightly
Musty odor earthy DO=2.00 mg/I Turb=95.8 NTUs
(not septic)
OWNER SIGNATURE TECHNICIAN SIGNATURE SERVICE DATE
9/30/19
Massachusetts Department of Environmental Protection
Bureau of Resource Protection - Title 5
DEP Approved Inspection and O&M1
L
Form for Title 5 I/A
Treatment and Disposal Systems
A. Installation
Important:When Cheryl Burnham
filling out forms Owner
on the computer,
use only the tab 115 Merchant Ave
key to move your Facility Street Address
cursor-do not Yarmouthport 02675
use the return City Zip
key.
r�
Mailing address of owner, if different:
x. Street Address/PO Box:
reuse
i
City State Zip
(774)238-6165 ext.
Telephone Number
B. Authorized Service Provider
J. M. O'Reilly &Associates, Inc.
O&M Firm
1573 Main Street
Street Address
Brewster MA 02631
City State Zip
(508) 896-6601 ext.
Telephone Number
John O'Reilly 17746
Certified Operator Name Certification Number
C. Facility/System Information
ZN86 Bio-Microbics, Inc. Microfast.5
DEP ID Manufacturer ID Model Number
12/20/2001
Installation Date Start of Operation
Approval Type: ® General ❑ Provisional ❑ Piloting ❑ Remedial
Seasonal Residence—used less than 6 mo./year: ❑ Yes ® No
D. Operating Information
9/30/19 9/7/18
Inspection Date Previous Inspection Date
1"
Pumping Recommended ® Yes ❑ No
Sludge Depth(to be checked yearly)
t5aiom.doc•rev.04-11-13 Page 1 of 3
Massachusetts Department of Environmental Protection
ILIBureau of Resource Protection - Title 5
DEP Approved Inspection and O&M Form for Title 5 I/A
Treatment and Disposal Systems
E. Field Testing
Field Inspection:
Color: El gray ® brown ❑ clear ❑turbid
❑ Other(specify):
Odor: ❑ musty ® earthy ❑ moldy ❑ offensive ❑ turbid
Effluent Solids: ❑ no ® some
pH 7.41 SU DO 2.00 mg/L Turbidity 95.8 NTU
6 to 9 2 or greater 40 or less
Should a Remedial or General Use system fail the Field Testing, effluent samples shall be collected
per Standard Methods and analyzed for BOD and TSS.
F. Sampling Information
Samples Taken: ❑ Influent ® Effluent
Commercial systems or systems with a design flow of 2000 gpd and greater, and General Use
nitrogen reducing systems:
gpd
Parameters sampled: ❑ pH ❑ BOD ❑ CBOD ❑ TSS ❑TN ❑ Other(list below)
see attached lab results
Other 1 Other 2 Other 3
G. Inspection and Maintenance
Description of any maintenance performed since previous inspection &during this inspection:
See attached manufacturer's checklist
Notes and Comments:
TN and TSS have both slightly increased since the previous inspection. Will resample the systems
influent and effluent per the manufacturer's suggestion to evaluate system performance and the
breakdown of nitrogen. High TSS most likely due to minor solids carry over and heavy root intrusion
in the distribution box where samples are taken. Recommend Distribution box be pumped +cleaned.
t5aiom.doc•rev.04-11-13 Page 2 of 3
Massachusetts Department of Environmental Protection
Bureau of Resource Protection - Title 5
DEP Approved Inspection.)
1
L
and O&M Form for Title 5 IIA
Treatment and Disposal Systems
H. Certification
I certify: I have inspected the sewage treatment and disposal system at the address above, have
conducted the required Field Testing and/or sample collection in accordance with Standard Methods,
have completed this report and the attached technology operation and maintenance checklist, and
the information reported is true, accurate, and complete as of the time of the inspection. I am a
Massachusetts certified operator in accordance with 257 CMR 2.00.
11/15/19
Operator Si Date
System owner must submit this report, technology O&M checklist, and any required sampling results
to the local board of health as follows for each inspection performed:
Remedial Use—by January 31st of each year for the previous calendar year
Piloting Use-within 45 days of inspection date
Provisional Use—by March 31th of each year for the previous 12 months
General Use—by September 30th of each year for the previous 12 months
Send to:
Department of Environmental Protection
Attention: Title 5 Program
One Winter Street, 5th Floor
Boston, MA 02108
t5aiom.doc•rev.04-11-13 Page 3 of 3
ENVIROTECH LABORATORIES, INC.
MA CERT. NO.: M-MA 063
8 Jan Sebastian Drive
Sandwich,MA 02563
(508)888-6460 1-800-339-6460
FAX(508)888-6446
Friday,October 11,2019
J.M O'Reilly&Associates, Inc.
1573 Main St., PO Box 1773
Brewster, MA 02
ProjectName: Burnham-115 Merchant Ave, SY Comments:
Project Number: 6878W
Sampled By: Client
Lab Order Number: WW-192129
Date Received: 09/30/19
va ,
lr -f - orf w w
- _i 15 00 09/30/ 115 N erc11 ve :> 1 `s
Parameters Units Test Results Reportable Limits Date Analyzed Analyst Method
pH pH units 7.41 NA 09/30/19 LL SM 4500 H-B
BOD 5-Day mg/L 16 2.0 10/01/19 MC SM 5210 B
Kjeldhal Nitrogen mg/L 12 0.60 10/09/19 KB SM4500-Norg B-C
Nitrate-N mg/L 12.0 0.01 10/01/19 LL EPA 300.0
Nitrite-N mg/L 1.11 0.006 10/01/19 LL EPA 300.0
Total Nitrogen mg/L 25 NA 10/10/19 KB Calculation
Total Suspended Solids mg/L 170 1.5 10/07/19 KB SM 2540 D
Dissolved Oxygen mg/L 2.00 1.0 09/27/19 MC 4000-0 C
All samples were analyzed within the established guidelines of US EPA approved methods with all requirements met,unless otherwise noted at the
end of a given sample's analytical results.
We certify that the following results are true and accurate to the best of our knowledge.
BRL=below reportable limits
*see attached 4
By: i7►'
Ronal J.Saari
Laboratory Dir,c r Page 1 of 1
. ' c •
i3 11• 67 -13
c c h o 'a
m m O
as
- ..
O ''0
n
A.., a
....
CD
7 ai
R
Cn
a O
CO 0
:3 11
0 0 -1 a
cm ca
3 7)
E
E M (D
SN` '11 m = $.
S N m as c
cv M. C ,may, p
I GO
N < O
(CD. N - P 2
6.
cz \ a
CN,„ \\ .
- N C4 a :' c w - . m
0 0 0 _co = -&, z
Q
-® -0 .p oo
m O
N �' �' co o w m
rn >' o n
o I
0 o0r
v wwCU0 a 0q
cD n " CO
a> Z
o n
w m .0 3 m 3 > C)
3 A, # ' Q
N N rt@ s
-t {
-1 p -1 -¢ > 03 -A C..
Z O In qb CD -
® OD Q- 73 y E A 1
0 O O N a) (D r
xi ci3 r+
m 0 C 3'
m m Z ,P,. E Cl) l
<' c D .4. D
;0 N
a a O Q CO o
Z -.i 114
2'
ON w CD