„I PRECAST H-10
RISERS (TYP.)
2'0
PROVIDE MIN. 20" DIAM. WATERTIGHT
ACCESS COVERS TO WITHIN 6" OF FIN. GRADE
MINIMUM J5' OF COVER OVFR PRFCAST
U 10" **EXISTING 14"
TEE SEPTIC TANK TEE
GAS BAF
4' LIQ. LEVEL (ACME OR EOL
SYSTEM PROFILE
(NOT TO SCALE)
2" PEASTONE OR GEOTEXTILE
FILTER FABRIC OVER STONE
ALL SYSTEM COMPONENTS SHALL BE
MARKED WITH MAGNETIC TAPE OR
COMPARABLE MEANS FOR FUTURE LOCATION.
CONCRETE COVERS TO WITHIN 3" GRADE
2% SLOPE REQUIRED OVER SYSTEM 128.0
NOTE: 2" MIN. WALL
THICKNESS REQUIRED BLOCKS OR
PRECAST RISERS
4"OSCH40 PVC MORTAR ALL
6" MIN. SUMP PIPES LEVEL 1ST 2' COMPONENTS H-10
12" MIN. INT. DIM. � ENDS (rTMP') SIDES 25.03'
25.7'± '0000°°°°
*j2'
0 G.0°°°°° WATERTEST D'BOX ;00000000 ° ° ° ° ° ° ° ° ° °°°°°°°O°°° FOR LEVELNESS '0000°°°°100000000
00002 24.35' >°°°°°°°°
22.2'
1000°0
0 ° ° ° H-10 500 GAL. LEACHING CHAMBER BY ACME PRECAST OR EQUAL.
'9-°°°°' 3/4"-1-1/2" DOUBLE WASHED STONE 4' MIN. (4) UNITS REQUIRED
ALL AROUND PRECAST STRUCTURES
6" CRUSHED STONE OR MECHANICAL OVERALL DIMENSIONS TO OUTSIDE OF STONE: 42.00' X 12.83'
COMPACTION. (15.221 [2])
(4.5 % SLOPE)
FOUNDATION EXIST SEPTIC TANK 26' D' BOX
LEGEND-
EGEND99—
99-
EXISTING CONTOUR
X 99.
EXIST. SPOT ELEV.
--[99]--
PROPOSED CONTOUR
198.41
PROPOSED SPOT EL.
TH1
io
TEST HOLE
SLOPE OF GROUND
Z°
UTILITY POLE
Locus
FIRE HYDRANT
NOTE: NOT ALL SYMBOLS MAY APPEAR IN DRAWING
TEST HOLE LOGS
ENGINEER: CRAIG J. FERRARI, SE # 13871
WITNESS: PHIL RENAUD
DATE: 12/18/2019
PERC. RATE =_< 2 MW/INCH
CLASS I SOILS
4 ELEV.
i
0't 27.5'
A
LS
12" 1OYR 4/2
B
LS
36" 1OYR 5/8 24.5'
C
PERC
MS
1OYR 7/4
132" I 116.5'
NO GROUNDWATER ENCOUNTERED
DCE # 19-304
(—!—% SLOPE)
17'
*THE INSTALLER SHALL VERIFY THE LOCATIONS OF ALL
UTILITIES AND ALL BUILDING SEWER OUTLETS AND ELEVATIONS
PRIOR TO INSTALLING ANY PORTION OF SEPTIC SYSTEM
Permit valid for REPAIR OF SEPTIC SYSTEM
ONLY, due to State and Local septic variances.
Board of Health review and approval is reiiuired for
any future additions/renovations/alterations to
sewage facilities acid/or su uctures/dwelling.
N.nne
Yarmouth Ilcalth Departmeut
APPROVED
Scole:1 "= 20'
0 10 20 30 40 50 FEET
16.5' BOTTOM TH-1
NO GROUNDWATER FOUND
LEACHING
FACILITY
**INSTALLER SHALL CONFIRM MINIMUM SEPTIC
TANK SIZE AT 1500 GALLONS AND ITS SUITABILITY
FOR RE—USE. REPLACE WITH 1500 GALLON
SEPTIC TANK APPROPRIATE TO SITE CONDITIONS IF
NOT SUITABLE
NOTES
1. DATUM IS NAVD 88
2. MUNICIPAL WATER IS EXISTING
3. MINIMUM PIPE PITCH TO BE 1/8" PER FOOT.
4. DESIGN LOADING FOR ALL PROPOSED PRECAST
UNITS TO BE AASHO H-10
5. PIPE JOINTS TO BE MADE WATERTIGHT.
6. CONSTRUCTION DETAILS TO BE IN ACCORDANCE
WITH 310 CMR 15.000 (TITLE 5.)
7. THIS PLAN IS FOR PROPOSED WORK ONLY AND
NOT TO BE USED FOR LOT UNE STAKING OR ANY
OTHER PURPOSE.
8. PIPE FOR SEPTIC SYSTEM TO SCH. 40-4" PVC.
9. COMPONENTS NOT TO BE BACKFILLED OR
CONCEALED WITHOUT INSPECTION BY BOARD OF
HEALTH AND PERMISSION OBTAINED FROM BOARD
OF HEALTH.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR
CALLING DIGSAFE (1-888-344-7233) AND
VERIFYING THE LOCATION OF ALL UNDERGROUND &
OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF
WORK. LOCUS MAP
11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL SCALE 1-=2000'±
BE REMOVED BENEATH AND 5' AROUND THE
PROPOSED LEACHING FACILITY. ASSESSORS MAP 124 PARCEL 55
12. EXISTING LEACHING FACILITY SHALL BE PUMPED
AND REMOVED OR PUMPED AND FILLED WITH CLEAN LOCUS IS WITHIN FEMA FLOOD ZONE X
SAND. (AREA OF MINIMAL FLOOD HAZARD) AS
SHOWN ON COMMUNITY PANEL #25001CO578J
DATED 7/16/2014
SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED'
EXISTING 5 BEDROOM DWELLING
DESIGN FLOW: 5 BEDROOMS @ 110 GPD = 550 GPD
USE A 550 GPD DESIGN FLOW
-SEFTIC-TANK:- 550—GPD (2�-- '1100 --- —
PROPOSED—� **USE EXISTING 1500 GAL. SEPTIC TANK _
SEPTIC
— G ECEIVE
LEACHING:
12 - 1;>--k r-\
DATE
SIDES: 2 (42 + 12.83) 2_-(.74)
= 162 GPD
MAR U 3 202
e/ ede�e
¢moi
BOTTOM
42 x 12.83 (.74)
Csi
io
� �
�c
H
Z°
Locus
756 S.F.
560 GPD
NAVD88
c
T
USE (4)
500 GAL. LEACHING CHAMBERS (ACME OR EQUAL)
27,
0
r
STONE ALL AROUND
CALLING DIGSAFE (1-888-344-7233) AND
VERIFYING THE LOCATION OF ALL UNDERGROUND &
OVERHEAD UTILITIES PRIOR TO COMMENCEMENT OF
WORK. LOCUS MAP
11. ANY UNSUITABLE MATERIAL ENCOUNTERED SHALL SCALE 1-=2000'±
BE REMOVED BENEATH AND 5' AROUND THE
PROPOSED LEACHING FACILITY. ASSESSORS MAP 124 PARCEL 55
12. EXISTING LEACHING FACILITY SHALL BE PUMPED
AND REMOVED OR PUMPED AND FILLED WITH CLEAN LOCUS IS WITHIN FEMA FLOOD ZONE X
SAND. (AREA OF MINIMAL FLOOD HAZARD) AS
SHOWN ON COMMUNITY PANEL #25001CO578J
DATED 7/16/2014
SYSTEM DESIGN:
GARBAGE DISPOSER IS NOT ALLOWED'
EXISTING 5 BEDROOM DWELLING
DESIGN FLOW: 5 BEDROOMS @ 110 GPD = 550 GPD
USE A 550 GPD DESIGN FLOW
-SEFTIC-TANK:- 550—GPD (2�-- '1100 --- —
PROPOSED—� **USE EXISTING 1500 GAL. SEPTIC TANK _
SEPTIC
— G ECEIVE
LEACHING:
12 - 1;>--k r-\
DATE
APPROVED
DANIEL A. OJALA, P.E., P.L.S.
, MA
DATE BOARD OF HEALTH -
TITLE 5 SITE PLAN
OF
e
X48 OLD CHURCH STREET
YARMOUTH PORT, MA
PREPARED FOR
WILLIAM CROSTON, JR.
DATE: DECEMBER 30, 2019
off 508-362-4541
I fax 508-362-9880
downcape.com
40Wa CQ.PC�a j'ineeri/!g, iftC.
civil engineers
/and surveyors
939 Main Street ( R to 6A)
YARMOUTHPORT MA 02675
19-304 CROSTON.DWG
SIDES: 2 (42 + 12.83) 2_-(.74)
= 162 GPD
MAR U 3 202
BOTTOM
42 x 12.83 (.74)
= 398 GPD
HEALTH DEP
SARK:
BOUND
TOTAL:
756 S.F.
560 GPD
NAVD88
USE (4)
500 GAL. LEACHING CHAMBERS (ACME OR EQUAL)
27,
WITH 4'
STONE ALL AROUND
APPROVED
DANIEL A. OJALA, P.E., P.L.S.
, MA
DATE BOARD OF HEALTH -
TITLE 5 SITE PLAN
OF
e
X48 OLD CHURCH STREET
YARMOUTH PORT, MA
PREPARED FOR
WILLIAM CROSTON, JR.
DATE: DECEMBER 30, 2019
off 508-362-4541
I fax 508-362-9880
downcape.com
40Wa CQ.PC�a j'ineeri/!g, iftC.
civil engineers
/and surveyors
939 Main Street ( R to 6A)
YARMOUTHPORT MA 02675
19-304 CROSTON.DWG