HomeMy WebLinkAboutBldsm-20-004060 (2) TARGET INSPECTIONS
SUMMARY OF TOTAL DUCT LEAKAGE TESTING
RESULTS FOR:
Rick Toma
Project Located at:
70 Breezy Point Road
South Yarmouth, MA
Project Number: 3084
Report Version: 1.0
QLbSre\ _ . O - Ob1kO(,0
Target Inspections
Steven Grevelis
P.O. Box 444
West Dennis, MA 02670
Phone: 508-737-4289
Email: steve@targetinspections.com
www.targetinspections.com
Certified HERS Rater(RIN—4958795),
&Certified Microbial Professional
Enclosures:
- Summary of Results
- Retrotec Reports
- Calibration Data
PASS
Based on testing of the total duct systems,the observed total duct leakage at the time of
testing of the system was at or below the allowable limits(4 cfm per 100 sq ft)as set forth in
IECC 2015 with tested results of 3.9 cfm per 100 sq ft.
Target Inspections Summary of Testing Results Copyright 2010/2011
Page 1 of 5
TARGET INSPECTIONS
Testing Conditions
February 13th, 2020
Wind — NE 5 mph
Weather—Cloudy
Outdoor Temperature—42° F
Outdoor Relative Humidity- 89%
Barometric Pressure— 29.54"
Target Inspections Summary of Testing Results Copyright 2010/2011
Page 2 of 5
a
TARGET INSPECTIONS
Total Duct Leakage Test—Summary of Results
Test Date: 02/13/2020 Technician:Steven Grevelis
Test File: 3084_Rick Toma_70 Breezey Point Rd_S Yarmouth_Duct
Building Address: 70 Breezey Point Rd
South Yarmouth, MA
Equipment Used
Retrotec—DU-200 Duct Blaster w/ DM32 Manometer
Serial Numbers: FT9010674/404468
DM32 Factory Calibration Date: 11-05-2015
DM32 Next Factory Calibration Date by: 10-15-2020
Field Calibration of DU-220 Performed: 02-12-2019
Tubing Integrity Testing Performed and Passed On-Site
The home has 1 systems outside of conditioned space that were tested:
Test Results
In accordance with IECC 2015 the maximum allowable total duct leakage is 4 cfm per 100 sq ft
at+/-25 pa in the rough or final stage.
Whole house square footage of conditioned space is 829 square feet:
- Maximum allowable leakage of 4 cfm per 100 sq ft=33.16 cfm: (4 cfm x 829 sq ft/100
sgft= 33.16cfm)
System#1—Servicing the 1st Floor
- Tested total duct leakage was 33 cfm @-25 pa
cfm=cubic feet per minute pa=pascals sq ft=square feet
Target Inspections Summary of Testing Results Copyright 2010/2011
Page 3 of 5
■
TARGET INSPECTIONS
Conclusion
Based on testing of the total duct systems,the observed total duct leakage at the time of
testing the system were at or below the allowable limits(4 cfm per 100 sq ft)as set forth in
IECC 2015 with tested results of 3.9 cfm per 100 sq ft.
The systems as installed meets the recommended guidelines and no further sealing is required.
Note:Square footage provided by Rick Toma.
I
All . .
A1 1 i!� :a -25.1
pun 32.63
x- ♦ .,or
y
i11 ._e o
PHOTO SUMMARY PHOTO SUMMARY
Setup of 1 st floor tested system. Manometer reading of 1st floor tested system.
Target Inspections Summary of Testing Results Copyright 2010/2011
Page 4 of 5
TARGET INSPECTIONS
This inspection report is solely based on the conditions within the defined area at the time of inspection
only and makes no express or implied warrant or guarantee as to future changes in condition or
conditions outside of the described job scope.
Sincerely,
Steven Grevelis
Certified HERS Rater(RIN—4958795),
&Certified Microbial Professional
Target Inspections Summary of Testing Results Copyright 2010/2011
Page 5 of 5
, .. Test Date: 2020-02-13
Duct Leakage
Test Report
Client Tester
Building Description Single Family Company Target Inspections
Building Address 70 Breezey Point Road Address 24 School Street,Unit 6
South Yarmouth,MA West Dennis,MA 02670
Contact Rick Toma Technician Steven Grevelis
Phone Phone (888)280-2108
Test Type Total Duct Leakage Gauge S/N 404468
Test Equipment Retrotec DU200 Fan S/N FT9010674
Building and Duct Details
Conditioned Floor Area 829.0 sq ft
Supply Return
Average Duct Operating Pressure 25.0 Pa 25.0 Pa
Leakage Split 50% 50%
Leakage Penalty 100% 50%
Leakage Data
Baseline Pressure
Depressurization
Duct Test Pressure 25.0 Pa
Duct Leakage 33 CFM
Leakage Area 6.1 sq in
Leakage constant, C
Leakage Exponent
Leakage Results
Total Duct Leakage 33 CFM at 25 Pa
Leakage/Conditioned Floor Area 0.039 CFMIsq ft at 25 Pa
3.9 CFM/100 sq ft at 25 Pa
39 CFM/1,000 sq ft at 25 Pa
,,f,.0.: t r a,,„fiii:,:::,::.:,......4
Gauge Calibration
Verification Report
Calibrated Equipment Calibration Facility
Serial Number 404377 Company Retrotec,Inc.
Firmware Version 2.3 Build 62 Address 1060 E Pole Rd
Gauge Type DM32
Manufacturer Retrotec,Inc. City Everson
Calibration Date 2015-11-13 State WA
AutoVerification Version 1.1.2 Zip Code 98247
Master Gauge Reference FC0550 SN0704353 Country USA
Phone (360)738-9835
Technician Mike Shtunyuk
Pressure calibration verification data
The accuracy of this dual channel(DM32)pressure gauge was calibrated against one of two NIST traceable Fumess 550(master gauge)pressure
calibrators.0704353 and 0907002,whose pressure accuracies are t 0.15%of its reading. A 32 point verification check was performed after
calibration to verify pressure readings are accurate when used with Door Fans.
Master gauge Calibrated gauge Calibrated gauge
Channel A Channel B
Pressure Pressure Error Pressure Error
(Pa) (Pa) (%) (Pa) (%)
400.0 400.0 0.0% 400.1 0.0%
300.0 300.1 0.0% 300.3 0.10/0
200.0 200.5 0.2% 200.3 0.2%
150.0 150.7 0.5% 150.7 0.5%
100.0 100.3 0.3% 100.9 0.9%
75.0 75.4 0.5% 75.3 0.4%
50.0 50.1 0.2% 50.4 0.8%
25.0 25.2 0.8% 25.1 0.4%
-25.0 -24.8 0.8% -25.1 0.4%
-50.0 -50.0 0.0% -49.7 0.6%
-75.0 -75.2 0.3% -75.0 0.0%
-100.0 -100.4 0.4% -99.9 0.1%
-150.0 -150.2 0.1% -150.4 0.3%
-200.0 -200.5 0.2% -200.5 0.2%
-300.0 -301.0 0.3% -300.6 0.2%
-400.0 -401.3 0.3% -401.1 0.3%
Digital pressure gauges should be checked for calibration every five years.
Calibration for the gauge should be checked before: 2020-09-30
This gauge meets the accuracy requirements of the following Standards:
NFPA 2001 EN13829 ATTMA:TS1 ASTM E779-10 CGSB I6014520 EN15004 RESNET
t1Pa 12Pa t2Pa 35%or0.25Pa t1Pa t1Pa 11Pa 31%or0.5Pa
t(10 to 50)Pa (up to 160 Pa) (up to t100 Pa) whichever is greater (up to 350 Pa) (up to 360 Pa) (up to 1100 Pa) whichever is greater
tl
TARGET INSPECTIONS
Most Recent Field Calibration Record for Retrotec Duct Blast Fan
Serial Number: FT9010674 Part Number: FN253
Date of Technician CFM @ Pressurized Comments
Verification 25 Pa on =P
Mid Depressurized
Range =D
97-106 is a Pass.
Steven 98.84= Field calibration
1/7/2020 Grevelis Pass D plate used (p/n:
DU-159)
r
-25.7
1r!
240
4 98.84
1 Mhd F M la II
L! ! hb0P4
fNkmp V01 a 8.0 Pa
Photo of manometer during field calibration of Duct Blast.