HomeMy WebLinkAbout29R Crest Cir Air Leakage Report180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com AA4A827B-DB45-4B5E-9CB8-03DEAFCBFC8D Air Leakage Report 29R crest cir West Yarmouth 06/01/2020 Lewis and Weldon 2015 IECC Energy Code Test Mode Depressurization Test Pressure 50.0 Pascals Test Equipment Minneapolis Total Air Leakage 184 Conditioned Volume 5040 or Air Changes Per Hour 2.19 Gauge This project meets the criteria for the following: 2009 International Energy Conservation Code 2012 International Energy Conservation Code 2015 International Energy Conservation Code 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com AA4A827B-DB45-4B5E-9CB8-03DEAFCBFC8D Ventilation Report Ventilation Tests Fan Location Fan CFM Fan Timer Run Time Fan CFM Bath 68 RH control 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com AA4A827B-DB45-4B5E-9CB8-03DEAFCBFC8D All testing results recorded in this report have been verified by: Chris Mazzola RTIN# - 8873503 ICC - 8344213 All testing was conducted in compliance with RESNET standards and protocols, the 780 CMR 51 Massachusetts Base Code, Stretch Code requirements and ASHRAE 62.2. In low infiltration homes, ventilation systems are vital to indoor air quality. Each newly constructed home must meet the 2013 ASHRAE 62.2 minimum ventilation specifications. Ventilation testing completed measures and ensures a healthy natural air exchange in the home. The fans installed in this home do not meet ASHRAE specifications and would require a programmable timer control to operate the fan independent of the on/off switch. Relative humidity levels in the home can have negative effects of the indoor quality. Testing contained in this report only verifies Fan Flow Rate, it is the Licensed CSL's Responsibility to ensure the required systems are installed.