HomeMy WebLinkAboutClark Reder 2020-08-03 Structural Inspection Letter Yarmouth Drive-in Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester, OH 45069-3873 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 8/3/2020 Innovation Arts and Entertainment 111 N Wabash Avenue Chicago, IL 60602 Attn: Joe Kosin Project Name: Cape Cod Drive-In CRE Project No. 20.901.19 Dear Joe: Clark Reder Engineering Inc. has completed its on-site structural observation of the following structures installed for the Cape Cod Drive-In located at the Yarmouth Drive-In in Yarmouth, MA on 07/29/2020 · Container mounted video wall Having performed the required observations, I hereby attest that to the best of my knowledge, belief and professional judgement, the systems listed above have been built in accordance with the stamped structural drawings and details dated 07/02/2020 by Clark Reder Engineering. Any deviations or changes have been discussed on site with the appropriate parties and/or the Engineer of Record for the structures in question. A summary of said deviations or changes is listed on page 3 of this document. The evaluations performed for these observations are based on the visible evidence observed at the time of our visit to the site and our application of generally accepted principles of structural engineering. We performed a visual examination only. No material testing, subsurface investigation, or design work has been performed as a part of this submittal. The conclusions and recommendations of this submittal represent our opinion of the existing conditions reviewed in this submittal, and there is no claim, either stated or implied, that all conditions were observed. Clark Reder Engineering, Inc. is not responsible for the conclusions, opinions, or recommendations made by others based on the information included in this submittal or for future changes in conditions. This report is not to be considered a guarantee of condition and no warranty is implied. Project Name: Cape Cod Drive-In 8/3/2020 CRE Project No: 20.901.19 Page 2 Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester, OH 45069-3873 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com We trust this information is suitable for your needs at this time. If you have any questions, please do not hesitate to contact our office. Regards, Clark-Reder Engineering, Inc. Tommy Wagar Jeffrey M. Reder, P.E. 08/03/2020 Project Name: Cape Cod Drive-In 8/3/2020 CRE Project No: 20.901.19 Page 3 Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester, OH 45069-3873 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 1. Half couplers were stood off from the container with approximately 1-2” of washers and M10 bolts. a. It was noted that some bolts were tightened at an angle other than 90 degrees relative to the container wall. For these locations, it is recommended that the coupler is slid up or down on the truss chord to resolve this angle such that the bolt is perpendicular to the container wall and truss chord. 2. Half couplers were connected to pipes which were then cheeseboroughed to truss chords rather than the half coupler directly attaching to the truss chord. 3. Base header utilized as W8x21 rather than the specified channel. The steel was cut every 10’ for maneuvering. a. W8x21 was beam clamped to half cheeseborough on both sides of the flange. The half cheeseboroughs were then connected to the truss chords. 4. 8’ spans of 20.5” box truss was placed between each vertical. a. The extra spacing resulted in the edge vertical truss legs overhanging approximately 6” from the edge of the container. 5. Horizontal truss legs extend approximately 6” from the downstage edge of container. 6. Wood padding was located on the upstage rung of the bottom truss and upright positions. Upstage padding was not tap screwed to container roof a. Downstage padding was tap screwed to container roof 7. The horizontal pipe on the upstage was not evenly spaced out every 2’ however a 3 pipe per container ratio was maintained. a. Additionally, the amount of connections was doubled to 2 per horizontal 8. Stage left and stage right horizontal pipes were double braced and cantilevered to accommodate vertical truss overhang. 9. Video wall extended above the vertical truss legs approximately 2’ a. 1.5” schedule 40 pipe was cheeseboroughed to truss and cantilevered up to reach video wall attachment point. b. Several of the above-mentioned cantilever supports are absent from some uprights. 10. Screen is tilting slightly back into the container. 11. Containers are located on a bed of crushed 4”-6” rock and leveled. a. Some container corners are elevated above, and not contacting, rock bed. It is recommended to place additional crushed rock in the corner container area such that the entire container base is supported. 12. Some cheeseboroughs are unattached or loose. It is recommended that these cheeseboroughs are attached or tightened. Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com Structure Overview Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 1. Half coupler with bolts and washers 2. Half coupler to pipe to cheeseborough to truss chord Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 3. Base header - W8X21 4. 8' Horizontal truss spans Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 4a. Overhung edge Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 5. Truss leg overhang 6a. Tap screwed downstage wood padding Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 6. Non-tap screwed upstage wood padding Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 7. 3-Per-Container horizontal pipe Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 8. Double braced and cantilevered horizontal Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 9. Video wall extended above truss 9a. 1.5" Sch 40 cantilevered pipe 9b. Missing 1.5" Sch 40 cantilevered pipe Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 10. Video wall slightly tilted towards container Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 11. Container sitting on bed of crushed rock 11a. Elevated container corner Clark Reder Engineering, Inc. ● 10091 Mosteller Lane, West Chester OH 45069 ● Phone (513) 851-1223 ● Fax (513) 217-9388 ● www.clarkreder.com 12. Unattached cheeseborough