HomeMy WebLinkAboutERV
to remove the filter
bracket and remove the
filter from the bracket.
Both filters should be
vacuumed with a soft
brush attachment.
Exchange Capillary Core
Panasonic technology is at the core
of WhisperComfort’s efficiency.
This unique core is made from a
plastic-like material and should never
be washed or submerged in water.
To clean, vacuum with a soft brush
attachment.
VF070278SS
Bringing fresh-air ventilation into your home
• Spot balanced ventilation fan with low-rate
continuous run
• Easy ceiling mount installation
• Provides fresh air from outside while
exhausting stale air and filtering out dust and
indoor air pollutants
• Exchange capillary core recovers heat energy
and moisture
• Balances air pressure inside the house
• Ideal for new air tight homes built to meet
energy efficiency standards
Headquarters
Panasonic Home & Environment Company
One Panasonic Way
Secaucus, NJ 07094
www.panasonic.com/building
ventfans@us.panasonic.com
Customer Service
Panasonic Home & Environment Company
1707 North Randall Road, 1D-12
Elgin, IL 60123
For Order Information:
PHONE: 866-292-7299; FAX: 888-553-0723
For Customer Call Center:
PHONE: 866-292-7292
Panasonic Home & Environment Company Unit of Panasonic Consumer Electronics Company
Design and specifications subject to change without notice.
Panasonic WhisperComfort Spot
Energy Recovery Ventilator (ERV)
offers a revolutionary way to provide
balanced ventilation with a ceiling insert
ERV. Affordable and easy to install,
WhisperComfort is energy efficient
and provides fresh ventilated air while
maintaining indoor air quality.
ADDITIONAL BENEFITS
• Totally enclosed motor for long life
–rated for continuous run
• Rust-proof paint treatment on galvanized housing
• Mechanical supply air damper employed
• Dual setting air volume for 40/20 or 20/10 CFM
• Supply and exhausted air filters employed
• One motor operates two fan wheels
• Uses two 4-inch ducts
INSTALLATION
Mounting
WhisperComfort measures 14 inches wide and fits between
joists 16" on center. Brackets and screws are provided to
secure the unit to the joists on 4 corners.
Wiring
Power consumption is 23 Watts at 40 CFM with a power
rating of 120/60 V/Hz. Bring house power to the unit junction
box and use 3 wire to connect the 2 switches.
Duct
Insulated 4" duct is recommended. For cold climates,
insulated duct running through a cold attic will help avoid
condensation build up. And for warm climates, insulated duct
running through a hot attic will help reduce heat transfer to
supply air.
In all cases, in order to reduce unnecessary airflow resistance,
duct should be stretched straight and braced to avoid
sagging. Assure that all duct connections are completely
secured with zip ties or duct straps and sealed with duct tape
and/or duct mastic material.
Elbows
Rule number one is to avoid elbows and bends whenever
possible. However, the fact is that many installations may
require at least one elbow. There are two precautions to take
when installing elbows to achieve optimum performance.
First, allow a 2 – 3 foot straight run out of the unit before the
first elbow. This allows for air flow momentum before passing
through the first elbow. An installation that has a 90-degree
elbow immediately after the exhaust port will cause air to
back flow into the unit. This will reduce fan performance and
may increase noise.
Second, use a long radius angle (not a tight short radius) to
help ensure optimum airflow and minimum airflow noise.
Termination/Supply Device
The exhaust termination device (roof cap or wall hood) may
have a back draft damper. The supply device will need to
have the back draft damper removed and replaced with a
screen to prevent insects and small animals from nesting.
The termination and supply devices should be placed a
minimum of 3 feet apart. If placed closer than 3-feet, then the
angle of each device should be mounted at 45-degrees in
opposite directions.
MAINTENANCE (Cleaning)
Maintenance instructions can
be found in the Operating Manual.
Grille
The grille can be washed with light
dish soap. Follow the Operating
Manual and remove the grille
from the unit. Next, remove the filter from the inside louver of
the grille. Never use gasoline, benzene, thinner or any other
chemicals when cleaning the grille or ERV unit. Do not wash in
dishwasher, which may be too hot and cause grille to deform.
Use light dish soap in the sink.
Filters
WhisperComfort has two air filters. One filter is located on
the inside louver of the grille. The second filter is located
in the unit held by a bracket with a handle. Pull the handle
3' (920 mm)
SUPPLY hood
with bird screen,
no backdraft flap(s)
EXHAUST hood
with backdraft flap(s)
Grille
Exchange
Capillary Core
Supply Air Filter Exhaust Air
Filter
N/A=not applicable
w.g.=water gauge
S.P.=static pressure
WhisperComfort (40/20 or 20/10 setting)
FV-04VE1
40 CFM 20 CFM 10 CFM
Characteristics
Static pressure in inches w. g. 0.1 0.1 0.1
Air Volume Exhaust (CFM) 40 20 10
Air Volume Supply (CFM) 30 20 10
Noise (sones) 0.8 <0.3 N/A
Power Consumption (Watts) 23 21 17
Speed (RPM)1479 1292 1095
Current 0.15 0.10 0.09
Power Rating (V/Hz)120/60
Specifications
Motor Type Condenser
Type of Motor Bearing Ball
Thermal Fuse Protection Yes
Blower Wheel Type 2 x Sirocco
Apparent Sensible
Effectiveness Heating (%) 32 °F (0°C)66% at 30 CFM
Total Recovery Efficiency Cooling (%) 95 °F (35°C)36% at 29 CFM
• New high efficiency energy recovery core
• Contemporary designed removable grille
• Suitable for renovation
• Easy installation (and no drain line required)
• Thermal fuse protection
• Meets Washington State Ventilation and Indoor Air
Quality code and ASHRAE 62.2-2007
Note: CFM and sones are tested and certified in accordance with HVI testing standards.
Energy efficiency is tested in accordance with CSA-C439 standard.
Printed with soy ink on 10% post-consumer recycled paper.
Frost Prevention Mode
WhisperComfort incorporates built-in frost prevention
technology to prevent exchange core freeze-up.
• Above 32ºF both exhaust and supply are fully functional
• From 32ºF to 20ºF the mechanical damper on the supply
air closes for 30 minutes, then opens 1 hour at the set high/
low mode. The cycle repeats itself to avoid core freeze-up.
(Exhaust-only 30 minutes per 90-minute cycle)
• Below 20ºF the mechanical damper on the supply air
remains closed for 1 hour and opens 10 minutes at low
mode. After 10 minutes the cycle will repeat or change if
the temperature has risen above 20ºF. (Exhaust only 60
minutes per 80-minute cycle)
Settings
WhisperComfort has two 2-speed CFM settings
High Low __________________________________________________
Setting 1. 20 CFM 10 CFM
Setting 2. 40 CFM 20 CFM factory preset
The factory setting is 40/20 CFM. To change to optional
20/10 CFM setting, move the plug connector located in the
junction box to the 20 CFM side of receptacle. This step must
be completed prior to installation.
Switches
WhisperComfort operates in an on/off and high/low mode.
When switch is turned off, the unit does not operate. When
switch is turned on the unit will operate at the high or low
mode. A duplex switch, designed for a single gang box. may
be selected for switch operation. Switch labels are provided
for convenience to attach to the selected switches.
32ºF Open 1 hr.
Close 30 m.
Open 1 hr.
Open 10 m.40 CFM20 CFMClose 1 hr.
Open 10 m.
19ºF
-13ºF
As a further reference and to consider dry versus humid
climates, refer to the climate zone map adopted by ASHRAE,
EPA and DOE. The map is located on the websites of all 3
agencies. (See ASHRAE link:
www.ashrae.org/technology/page/1330)
SIZING
Panasonic’s recommended zone map is based on average
temperature readings over 10 years from 60 major cities in
North America. Actual performance may vary depending on
annual temperature differences and varying altitudes.
Need to choose 10/20 CFM mode when installing.
Ventilation Capacity Requirements (CSA-F326)
10 CFM Single Bedroom Living room Family room
20 CFM Master Bedroom Large Basement room
Spot Ventilation
Need to choose 20/40 CFM mode when installing.
ASHRAE 62.2 2007
1 Bedroom 2 Bedrooms 3 Bedrooms
20 CFM 500 sq ft.N/A N/A
40 CFM 2500 sq ft. 1750 sq ft. 1000 sq ft.
Whole House Ventilation (IAQ)
Balanced Ventilation With Spot ERV
WINTER
SUMMER
Outside Inside
single room. The unit provides a low rate of continuous air
exchange. Fresh air is supplied while maintaining balanced air
pressure. This is an affordable way to add ERV to a specific
room or a new addition.
Ideal for: Home office / Game rooms / Family rooms
Whole House ERV
WhisperComfort may also be suitable to meet whole house
ventilations requirements under ASHRAE 62.2. The sizing
charts on the next page provide a guideline for number of
bedrooms and square feet. Additionally, two or even three
WhisperComfort ERV’s may be installed, often at a cost lower
than a traditional whole house ERV.
Ideal for: Condominiums / Housing Authority properties /
Hotels / Studio Apartments
ASHRAE 62.2 2007 Standard
The American Society of Heating, Refrigerating and Air
Conditioning Engineers (ASHRAE) set a standard for whole
house ventilation, requiring that continuous mechanical
ventilation be 7.5 CFM per bedroom (master bedroom
X 2) plus 1 CFM per 100 square feet, with sone level not to
exceed 1.0. Panasonic WhisperComfort ERV is an
affordable, efficient way to meet this ventilation standard.
Spot ERV Ceiling Insert Ventilator
FV-04VE1 4" x 2 Ducts
FEATURES
Balanced Ventilation
Tightly built homes and buildings minimize passive air leaks.
An exhaust-only fan may create negative pressure. Whisper-
Comfort solves this by supplying air to replace exhausted air,
helping to balance air pressure within the home.
Panasonic WhisperComfort spot ERV uses two 4 inch ducts
– one to exhaust stale air and the other to supply fresh air
from outdoors. Its low rate, continuous run ensures chemi-
cals such as volatile organic compounds (VOC’s) and other
pollutants from cleaning fluids and building materials are
vented out and replaced with fresh air.
Exchange Capillary Core
Indoor and outdoor air passes through Panasonic’s
capillary core technology designed to transfer heat energy
and moisture. This process tempers supply air while transfer-
ring moisture.
Motor Technology
Panasonic uses a single AC condenser motor to run
two highly efficient blower wheels. The motor is totally
enclosed to ensure long-life and continuous
quiet operation.
Filters
Two filters clean exhaust and supply air before passing
through the ERV core, extending the life of the core.
Grille Design
The contemporary, low profile grille design incorporates
spring clips for easy removal.
Spot ERV
WhisperComfort is a ceiling insert spot ERV ideal for a
Tight Home Air Pressure
Without ERV With Spot ERV
Spot ERV Technology
OUTSIDECool
Cool
INSIDE
WarmWarmHeat & Moisture Transfer
OPERATION
Sizing example 1 (based on ASHRAE 62.2):
TWO BEDROOMS at 1600 SQ. FT.
Master Bedroom (7.5 CFM x 2) = 15 CFM
Second Bedroom = 7.5 CFM
1600 SQ. FT. x .01 = 16 CFM_________________________________________________
Total 38.5 CFM
Use WhisperComfort set at 40 CFM
Sizing example 2 (based on ASHRAE 62.2):
FOUR BEDROOMS at 2200 SQ. FT.
Master Bedroom (7.5 CFM x 2) = 15 CFM
Other 3 Bedrooms (7.5 CFM each) = 22.5 CFM
2200 SQ. FT. x .01 = 22 CFM________________________________________________
Total 59.5 CFM
Use 2 WhisperComfort or 1 WhisperComfort and
1 WhisperGreen*
ON OFF
HI LO
* WhisperGreen is a line of exhaust fans with variable speed DC motor and
built-in controls, ideal for both bathroom intermittent ventilation and whole house
continuous run ventilation.
Switch is not supplied.