HomeMy WebLinkAbout01-5100-Construction-Indoor-Air-Quality_Rev_1Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
1 of 7
SECTION 01 51 00 - CONSTRUCTION INDOOR AIR QUALITY
PART 1- GENERAL
1.1 RELATED DOCUMENTS
A. Section 018113 Sustainable Design Requirements
1.2 REQUIREMENTS INCLUDED IN THIS SECTION
A. Indoor Air Quality Management Goals
B. Indoor Air Quality Management Plan
C. Indoor Air Quality Management Plan Implementation
1.3 INDOOR AIR QUALITY MANAGEMENT GOALS
A. The Owner has established that this Project shall prevent indoor air quality problems
resulting from the construction process, to sustain long-term installer and occupant health
and comfort.
B. Protect the ventilation system components during construction and cleanup of
contaminated components after construction is complete.
C. Control sources of potential Indoor Air Quality (IAQ) pollutants by controlling selection of
materials and processes used in project construction.
D. With regard to these goals the Contractor shall develop, for Owner and Architect’s
review, an IAQ Management Plan for this Project
PART 2 – PRODUCTS
2.1 SUBMITTALS:
A. Construction IAQ Management Plan highlighting the five requirements of the Sheet Metal
and Air Conditioning National Contractors Association (SMACNA) IAQ Guidelines for
Occupied Buildings under Construction, 2nd edition, 2007, ANSI/SMACNA 008–2008,
Chapter 3, including a no-smoking policy.
B. Photographs documenting construction IAQ management measures implemented during
construction of each of the five SMACNA requirements.
C. Cut sheets of filtration media used during construction and installed immediately prior to
occupancy with MERV values highlighted.
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
2 of 7
D. Submit a letter from the Contractor describing building flush-out procedures including
actual dates of building flush-out, hours of ventilation, ventilation rates, and indoor
temperature and humidity levels.
2.2 IAQ MANAGEMENT PLAN
A. Develop a Draft Indoor Air Quality (IAQ) Management Plan for the construction and pre-
occupancy phases of the building as follows: (1) during construction meet or exceed the
minimum requirements of the Sheet Metal and Air Conditioning National Contractors
Association (SMACNA) IAQ Guidelines for Occupied Buildings under Construction, 2nd
edition, 2007, ANSI/SMACNA 008–2008, Chapter 3, (2) Protect stored on-site or installed
absorptive materials from moisture damage, and (3) conduct a building flush-out after
construction ends and prior to occupancy.
1. The SMACNA IAQ Guidelines for Occupied Buildings under Construction provides an
overview of air pollution associated with construction, control measures, construction
process management, quality control, communicating with occupants, and case
studies. These guidelines can be accessed at www.smacna.org. Chapter 3 of the
SMACNA Guidelines recommends Control Measures in five areas: HVAC protection,
source control, pathway interruption, housekeeping, and scheduling. Review the
applicability of each Control Measure and include those that apply in the Draft IAQ
Management Plan.
a. HVAC Protection: Shut down the return side of the HVAC system whenever
possible during heavy construction. If the system must remain operational during
construction include the following strategies that apply:
i. If conditioning is required during construction, use supplementary HVAC
units instead of permanently installed equipment if possible.
ii. Seal all ductwork, registers, diffusers, and returns with plastic when
stored on site or not in service. Seal unfinished runs of ductwork at the
end of each day
iii. Fit the return side of the HVAC system with temporary filters.
iv. Isolate the return side of the HVAC system from the surrounding
environment as much as possible (e.g., place all tiles for the ceiling
plenum, repair all ducts and air handler leaks).
v. Damper off the return system in the heaviest work areas and seal the
return system openings with plastic.
vi. Upgrade the filter efficiency where major loading is expected to affect
operating HVAC system.
vii. Clean permanent return air ductwork per National Air Duct Cleaning
Association standards upon completion of all construction and finish
installation work.
viii. If permanently installed air handlers are used during construction,
filtration media with a Minimum Efficiency Reporting Value (MERV) of 8
shall be used at each return air grille during construction, as determined
by ASHRAE 52.2-1999.
ix. Install new clean media just prior to substantial completion and
occupancy that has a Minimum Efficiency Reporting Value (MERV) of 13.
b. Source Control: Keep sources of contaminants out of the building and have a
plan to eliminate any that are introduced:
i. Use low-toxicity and low-VOC materials to the greatest extent possible.
ii. Develop protocols for the use of any high-toxicity materials. Isolate areas
where high-toxicity materials are being installed and use temporary
ventilation for that area.
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
3 of 7
iii. Prevent exhaust fumes (from idling vehicles, equipment, and fossil-
fueled tools) from entering the building.
iv. Enforce the no-smoking job site policy.
v. Protect stored materials from moisture because absorbent materials
exposed to moisture during construction can mold and degenerate long
after installation. Store materials in dry conditions indoors, under cover,
and off the ground or floor.
vi. If materials are improperly exposed to moisture, replace the material and
consider testing air quality before occupancy to make sure no mold
contamination has occurred.
c. Pathway Interruption: Prevent contamination of clean spaces. Include the
following strategies that apply:
i. Use 100% outside air ventilation (when outside temperatures are
between 55 degrees F and 85 degrees F and humidity is between 30%
and 60%) with air exhausted directly to the outside during installation of
finishes and other VOC emitting materials.
ii. Isolate areas of work to prevent contamination of other spaces, whether
they are finished or not. Seal doorways, windows, or tent off areas as
needed using temporary barriers, such as plastic separations. Provide
walk-off mats at entryways to reduce introduced dirt and pollutants.
iii. Use dust guards and collectors on saws and other tools.
iv. Depressurize the work area to allow a differential between construction
areas and clean areas. Exhaust to the outdoors using 100% outdoor air,
if possible
d. Housekeeping: Reduce construction contamination in the building prior to
occupancy through HVAC and regular space cleaning activities.
i. Maintain good job site housekeeping on a daily basis. Use vacuum
cleaners with high-efficiency particulate filters and use sweeping
compounds or wetting agents for dust control when sweeping
ii. Store building materials in a weather tight, clean area prior to unpacking
for installation.
iii. Check for possible damage to the HVAC system and Building
assemblies from high humidity.
iv. Clean all coils, air filters, and fans before testing and balancing
procedures are performed.
e. Scheduling: Specify construction sequencing to reduce absorption of VOC’s by
materials that act as sinks or contaminant sources. Complete application of wet
and odor-emitting materials such as paints, sealants, and coatings before
installing sink materials such as ceiling tiles, carpets, insulation, gypsum
products, and fabric-covered furnishings are installed.
i. Consider after-hours or weekend work if practical.
2. Protect stored on-site or installed absorptive materials from exposure to moisture
through precipitation, plumbing leaks, or condensation from the HVAC system to
prevent microbial contamination.
PART 3 – EXECUTION
3.1 FLUSH-OUT
As part of Indoor air quality management, the following requirements have to be met:
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
4 of 7
FLUSH OUT: Provide a summary data log sheet indicating outside air cfm provided
on an hourly basis during flush out. Provide cut sheets of filters use during flush out
and verify replacement air filters after flush out. Refer to Section 018113 for LEED
requirements.
Or
AIR TESTING: Provide an IAQ Testing report that includes a narrative describing
procedures and how locations were determined, and date/results of each test.
A. Building Flush Out: Select one of the following two options (prior to occupancy or during
occupancy), to be implemented after construction ends and the building been completely
cleaned. All interior finishes, such as millwork, doors, paint, carpet, acoustic tiles, and
movable furnishing, must be installed, and major VOC punch list items must be finished.
a. Prior to Building Occupancy: Prime Trade Contractor shall install new filtration media
and perform a building flush-out by supplying a total air volume of 14,000 cubic feet f
outdoor air per square foot of gross floor area while maintaining an internal
temperature of at least 60ºF (15ºC) and no higher than 80ºF (27ºC) and relative
humidity no higher than 60%. The duration of the flush-out must be calculated as
follows:
Cubic feet of outdoor air needed prior to occupancy = Area (ft2) X 14,000 cfm
Duration (Days) = Cubic Feet needed/(air handler capacity/1440 minutes/day)
i. Replace all outside air filtration media prior to occupancy. Filtration media
shall have a MERV of 13 as determined by ASHRAE 52.2.
b. During Occupancy: if occupancy is desired before the flush-out is completed, the
space may be occupied only after delivery of a minimum of 3,500 cubic feet of
outdoor air per square foot of gross floor area while maintaining an internal
temperature of at least 60ºF (15ºC) and no higher than 80ºF (27ºC) and relative
humidity no higher than 60%.
Once the space is occupied, it must be ventilated at a minimum rate of 0.30 cubic
foot per minute (CFM) per square foot of outdoor air or the design minimum outdoor
air rate determined by the ASHRAE 62.1-2010 calculations determined in IEQ
Prerequisite Minimum indoor Air Quality performance, whichever is greater. During
each day of the flush-out period, ventilation must begin at least three hours before
occupancy and continue during occupancy. These conditions must be maintained
until a total of 14,000 cubic feet per square foot of outdoor air has been delivered to
the space. The duration of the flush-out must be calculated as follows:
Cubic feet of outdoor air needed prior to occupancy = Area (ft2) X 3,500 cfm
Cubic feet of outdoor air needed during occupancy = Area (ft2) X 10,500 cfm
Duration (Days) = (Area (ft2) X 14,00 cfm)/(air handler capacity/1440 minutes/day)
B. IAQ Testing: After construction ends and before occupancy, but under ventilation
conditions typical for occupancy, conduct IAQ testing using protocols consistent with the
methods in the table below for all occupied spaces.
C. Use current versions of ASTM standard methods, EPA compendium methods, or ISO
methods, as indicated.
D. Conduct all measurements before occupancy during normal occupied hours, with the
building ventilation system started at the normal daily start time and operated at the
minimum outdoor airflow rate for the occupied mode throughout the test. F
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
5 of 7
E. or each sampling point where the concentrations exceed the limit, take corrective
action and retest for the noncompliant contaminants ate the same sample points.
Repeat until all requirements are met.
Test for the particulate matter (PM) and inorganic gases listed in Table 1, using an allowed test
method, and demonstrate the contaminants do not exceed the concentration limits listed in the
table.
Table 1.
Contaminant (CAS#) Concentration Limit (µg/m3) Allowed Test Methods
Carbon monoxide (CO) 9 ppm; no more than 2 ppm
above outdoor levels
ISO 4224
EPA Compendium Method IP-3
GB/T 18883-2002 for projects in
China
Direct calibrated electrochemical
instrument with
accuracy of (+/- 2% ppm <50 ppm
minimum accuracy).
PM 10 ISO 14644-1:2015,
cleanroom class of 8 or lower 50 μg/m3 Healthcare only: 20 μg/m3
Particulate monitoring device with
accuracy greater of 5
micrograms/m3 or 20% of reading
and resolution (5 min
average data) +/- 5 µg/m
3
PM 2.5 12 μg/m3 or 35 µg/m3**
Ozone 0.07 ppm Monitoring device with accuracy
greater of 5 ppb or 20%
of reading and resolution (5 min
average data) +/- 5 ppb
ISO 13964
ASTM D5149 -– 02
EPA designated methods for Ozone
Perform a screening test for Total Volatile Organic Compounds (TVOC). Use ISO 16000-6, EPA
TO-17,or EPA TO-15 to collect and analyze the air sample. Calculate the TVOC value per EN
16516:2017, CDPH Standard Method v1.2 2017 section 3.9.4, or alternative calculation method
as long as full method description is included in test report. If the TVOC levels exceed 500 µg/m3,
investigate for potential issues by comparing the individual VOC levels from the GC/MS results to
associated cognizant authority health-basedlimits. Correct any identified issues and re-test if
necessary.
Additionally, test for the individual volatile organic compounds listed in Table 2 using an allowed
test method and demonstrate the contaminants do not exceed the concentration limits listed in
the table.
Table 2.
Contaminant (CAS#) Concentration Limit (µg/m3) Allowed Test Methods
Formaldehyde 50-00-0 20 µg/m3 (16 ppb) ISO 16000-3, 4;
EPA TO-11a, Acetaldehyde 75-07-0 140 µg/m3
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
6 of 7
EPA comp. IP-6A
ASTM D5197-16
Benzene 71-43-2 3 µg/m3 ISO 16000-6
EPA IP-1,
EPA TO-17,
EPA TO-15
ISO 16017-1, 2;
ASTM D6196-15
Hexane (n-) 110-54-3 7000 µg/m3
Naphthalene 91-20-3 9 µg/m3
Phenol 108-95-2 200 µg/m3
Styrene 100-42-5 900 µg/m3
Tetrachloroethylene 127-18-4 35 µg/m3
Toluene 108-88-3 300 µg/m3
Vinyl acetate 108-05-4 200 µg/m3
Dichlorobenzene (1,4-) 106-46-
7
800 µg/m3
Xylenes-total 108-38-3, 95-47-
6, and 106-42-3
700 µg/m3
F. Draft IAQ Management Plan Review Meeting: Once the Owner and Architect have
reviewed the Draft IAQ Management Plan and prior to construction at the site, schedule
and conduct a meeting to review the Draft IAQ Management Plan and discuss
procedures, schedules and specific requirements for IAQ during the construction and pre-
construction phases of the building. Discuss coordination and interface between the
Contractor and other construction activities. Identify and resolve problems with
compliance to the requirements. Record minutes of the meeting, identify all conclusions
reached and matters requiring further resolution.
1. Attendees: The Contractor and related Contractor personnel associated with the work
of this section, including personnel to be in charge of the IAQ management program,
Architect, Owner and such additional personnel as the Architect or Owner deems
appropriate.
G. Final IAQ Management Plan: Make any revisions to the Draft IAQ Management Plan
agreed upon during the meeting identified in item (B) above and incorporate resolutions
agreed to be made subsequent to the meeting. Submit the revised plan to the Owner
and Architect for approval within 10 calendar days of the meeting.
3.2 IMPLEMENTATION OF IAQ MANAGEMENT PLAN
A. Manager: The Contractor shall designate an on-site party (or parties) responsible for
instructing workers and overseeing and the IAQ Management Plan for the Project.
B. Progress Meetings: Construction related IAQ procedures shall be included in the pre-
construction and construction progress meeting agendas.
C. Distribution: The Contractor shall distribute copies of the IAQ Management Plan to the
Job Site Foreman, each Subcontractor, the Owner, and the Architect.
Dennis Yarmouth Intermediate Middle School January 19, 2021
Dennis Yarmouth Regional School District 100% Construction Documents
Perkins Eastman DPC, project #71011
01 5100 Construction Indoor Air Quality
7 of 7
D. Instruction: The Contractor shall provide on-site instruction of the IAQ procedures and
ensure that all participants in the construction process understand the importance of the
goals of the IAQ Management Plan.
END OF SECTION 01 51 00
(THIS PAGE IS BLANK)