Duct Leakage Report
15 Harbour Hill Run
Yarmouth
08/18/2021
Cape Cod HVAC
2018 IECC Energy Code
Test Mode
Pressurization
Test Pressure
25.0 Pascals
Testing Equipment
Minneapolis
Total CFM@25
76.00
Total Square Footage
2172.00
Maximum Allowable Leakage
86.88
or Total Duct Leakage Percentage
0.03
HVAC Duct Test
180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com
www.gocanvas.com 95E0FA67-A464-4BEB-A920-E29374FAE265
Location Sqft Served Ring CFM@25 Gauge Duct Leakage %
Unconditioned
Attic
1736 C 60 0.03
Unconditioned
Attic
436 C 16 0.04
180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com
www.gocanvas.com 95E0FA67-A464-4BEB-A920-E29374FAE265
All testing results recorded in this report
have been verified by:
Chris Mazzola
RTIN# - 8873503
ICC - 8344213
New Static TextAll testing was conducted in compliance with RESNET standards and protocols, the
780 CMR 51 Massachusetts Base Code, Stretch Code requirements and ASHRAE 62.2.