Loading...
HomeMy WebLinkAbout15 Harbour Hill Run Air Leakage Report180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 95E0FA67-A464-4BEB-A920-E29374FAE265 Duct Leakage Report 15 Harbour Hill Run Yarmouth 08/18/2021 Cape Cod HVAC 2018 IECC Energy Code Test Mode Pressurization Test Pressure 25.0 Pascals Testing Equipment Minneapolis Total CFM@25 76.00 Total Square Footage 2172.00 Maximum Allowable Leakage 86.88 or Total Duct Leakage Percentage 0.03 HVAC Duct Test 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 95E0FA67-A464-4BEB-A920-E29374FAE265 Location Sqft Served Ring CFM@25 Gauge Duct Leakage % Unconditioned Attic 1736 C 60 0.03 Unconditioned Attic 436 C 16 0.04 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 95E0FA67-A464-4BEB-A920-E29374FAE265 All testing results recorded in this report have been verified by: Chris Mazzola RTIN# - 8873503 ICC - 8344213 New Static TextAll testing was conducted in compliance with RESNET standards and protocols, the 780 CMR 51 Massachusetts Base Code, Stretch Code requirements and ASHRAE 62.2.