HomeMy WebLinkAbout2021.09.03 YarmouthPD_Electrical Permit StampedGENERAL NOTES 1.PERFORM WORK AND PROVIDE MATERIALS AND EQUIPMENT TO MAKE INSTALLATION COMPLETE IN EVERY DETAIL UNDER THIS CONTRACT WHETHER OR NOT SPECIFICALLY SHOWN ON DRAWINGS. 2.ALL CONDUIT, WIRING AND ELECTRICAL EQUIPMENT SHALL BE INSTALLED AND GROUNDED IN ACCORDANCE WITH THE LATEST STANDARDS OF THE NATIONAL & STATE ELECTRICAL CODES AND ANY APPLICABLE LOCAL REGULATIONS. 3.ALL FLOOR, MASONRY WALLS AND STRUCTURAL CEILING PENETRATIONS SHALL BE SLEEVED. 4.PROVIDE FIRE/MOISTURE SEAL FOR WALL, FLOOR OR CEILING PENETRATIONS. 5.DO NOT LAY CABLES OR RACEWAY ON, OR SUPPORT FROM SUSPENDED CEILING OR PIPING AND DUCTWORK. 6.NO CONDUIT SMALLER THAN 3/4 INCH ELECTRICAL TRADE SIZE SHALL BE USED, UNLESS SPECIFICALLY CALLED FOR ON THE DRAWINGS. 7.ALL WIRING WITHIN UTILITY CLOSETS MAY BE IN SURFACE MOUNTED CONDUIT. EMT MAY BE UTILIZED. 8.FLEXIBLE CONDUIT CONNECTIONS SHALL BE A MAXIMUM OF 6'-0". 9.MC TYPE CONDUCTOR WITH INTEGRAL GROUND WIRE MAY BE UTILIZED FOR POWER AND LIGHTING CIRCUITS. MC CABLE SHALL BE UTILIZED ONLY WHERE COMPLETELY CONCEALED AND INSTALLED IN ACCORDANCE WITH CODE. 10. STEEL OR FIRE-RATED ELECTRICAL BOXES (SWITCHES, OUTLETS, JUNCTION BOXES, ETC.) SHALL BE PROVIDED AND INSTALLED IN ALL FIRE RATED ASSEMBLIES AS IN ACCORDANCE WITH BUILDING AND ELECTRICAL CODES. UL LISTED MOLDABLE PUTTY PADS OR FIREBLOCK/SPRAY FOAM INSULATE SHALL BE USED TO SEAL ALL ANNULAR SPACES/PENETRATIONS AROUND OUTLET BOXES. FIRE RATED ASSEMBLIES INCLUDE EXTERIOR WALLS, FIRE-RATED WALLS, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIES. 11. ALL EQUIPMENT AND WIRING SHOWN ON DWGS IS DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. ALL CONDUIT RUNS SHALL BE RIGIDLY SUPPORTED. LIGHTING NOTES 1.ALL CONDUIT, FIXTURES AND OUTLETS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. 2.ALL LIGHTING FIXTURE SPACING DIMENSIONS AND MOUNTING HEIGHTS ARE RECOMMENDED LOCATIONS. SLIGHT VARIATIONS WHERE NECESSARY TO AVOID INTERFERENCE SHALL BE DETERMINED IN THE FIELD. 3.WHERE REQUIRED, ADDITIONAL SUPPORT STEEL FOR THE LIGHTING INSTALLATION SHALL BE FURNISHED AND INSTALLED BY ELECTRICAL CONTRACTOR. SEISMIC RESTRAINTS SHALL BE INCLUDED AS PER STATE BUILDING CODE. 4.PROVIDE SEPARATE UN-SWITCHED NEUTRAL TO ALL EXIT SIGNS, EMERGENCY BATTERY UNITS AND EMERGENCY LIGHT FIXTURES CONTAINING EMERGENCY BALLASTS. 5. FIRE-RATED BOXES/ENCLOSURES FOR RECESSED LIGHTING FIXTURES SHALL BE PROVIDED AND INSTALLED IN FIRE-RATED ASSEMBLIES AS IN ACCORDANCE WITH BUILDING AND ELECTRICAL CODES. FIRE-RATED ASSEMBLIES INCLUDE; FIRE-RATED WALLS, FLOOR/CEILING ASSEMBLIES AND ROOF/CEILING ASSEMBLIES. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE-RATED ASSEMBLIES. POWER NOTES 1.ALL CONDUITS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION AND METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD, EXCEPT WHERE SPECIFIC DIMENSIONS AND DETAILS ARE SHOWN. ALL CONDUIT RUNS SHALL BE RIGIDLY SUPPORTED. 2. CONDUCTORS AND CABLE SHALL BE MINIMUM #12 AWG, 600 VOLT, COPPER WITH TYPE THHN/THWN INSULATION. PROVIDE SEPARATE GREEN GROUND IN ALL FEEDERS. WIRE SIZE #8 AWG AND LARGER SHALL BE STRANDED, #10 AWG AND SMALLER SHALL BE SOLID. COLOR CODE CONDUCTORS BLACK, RED, BLUE, WITH WHITE NEUTRAL AND GREEN GROUND EXCEPT AS NOTED FOR 120 VOLT. DEMOLITION NOTES 1.DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT IDENTIFIED FOR REMOVAL ON THE HVAC PLANS. 2. THE ELECTRICAL DEMOLITION PLANS AND DETAILS INDICATE THE GENERAL INTENT AND ARE NOT INTENDED TO SHOW ALL ITEMS TO BE REMOVED OR RETAINED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO THE SUBMISSION OF BIDS TO BECOME FAMILIAR WITH THE ACTUAL CONDITIONS AND EXTENT OF WORK. DEVICES AND EQUIPMENT LOCATED ON WALLS AND/OR CEILINGS TO BE REMOVED SHALL BE DISCONNECTED AND MADE SAFE. THE ELECTRICAL CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY UNANTICIPATED HIDDEN CONDITIONS ENCOUNTERED DURING DEMOLITION. 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ALL SYSTEMS OR BUILDING COMPONENTS DAMAGED DURING THE EXECUTION OF THE WORK. DAMAGE SHALL INCLUDE BUT NOT BE LIMITED TO DESTRUCTION OR DISPOSAL OF ITEMS INTENDED TO REMAIN OR TO BE SALVAGED. 4. THE ELECTRICAL CONTRACTOR SHALL CIRCUIT TRACE AND LABEL ALL EXISTING BRANCH CIRCUITS AND FEEDERS WITHIN THE AREA OF DEMOLITION SCOPE PRIOR TO DE-ENERGIZING AND DISCONNECTION. ALL CIRCUITS WITHIN PANELBOARDS IDENTIFIED FOR REMOVAL SHALL BE TRACED AND LABELED TO ENSURE THAT NO AREA OUTSIDE THE DEMOLITION SCOPE LIMIT IS AFFECTED. 5. THE ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL BRANCH CIRCUITS, FEEDERS AND SYSTEM COMPONENTS, WHICH ARE TO REMAIN WITHIN THE AREA OF DEMOLITION SCOPE. THERE SHALL BE NO INTERRUPTION OF SERVICE TO ANY AREA OUTSIDE THE SCOPE LIMITS WITHOUT APPROVAL FROM THE OWNER'S REPRESENTATIVE. EXISTING EQUIPMENT TO REMAIN SHALL BE LEFT IN A CODE COMPLIANT MANNER. 6. THE ELECTRICAL CONTRACTOR SHALL DE-ENERGIZE AND REMOVE ALL CONDUCTORS AND RACEWAYS TO THEIR POINTS OF ORIGIN WITHIN THE AREA OF DEMOLITION SCOPE. ITEMS IDENTIFIED FOR DEMOLITION SHALL NOT BE ABANDONED IN PLACE. RACEWAYS THAT ENTER MASONRY WALLS AND FLOORS SHALL BE CUT FLUSH AT THE SURFACE FOR PATCHING BY OTHERS. ALL CIRCUIT BREAKERS ASSOCIATED WITH THE DEMOLITION SCOPE SHALL BE DE-ENERGIZED AND LABELED SPARE. 7.ALL REMOVED ITEMS SHALL BE LEGALLY DISPOSED OF UNLESS IDENTIFIED FOR REUSE. THE OWNER'S REPRESENTATIVE SHALL INSPECT ALL RETAINED ITEMS PRIOR TO PLACEMENT IN THE IDENTIFIED STORAGE LOCATION BY THE ELECTRICAL CONTRACTOR. 8. THE EXISTING FIRE ALARM SYSTEM SHALL REMAIN FULLY FUNCTIONAL DURING THE ENTIRE DEMOLITION AND CONSTRUCTION PERIOD. REUSE OF EXISTING FIRE ALARM SYSTEM RACEWAYS SHALL NOT BE ALLOWED. ALL REQUIRED SYSTEM SHUTDOWNS SHALL BE COORDINATED WITH AND APPROVED BY THE OWNER'S REPRESENTATIVE AND THE AUTHORITY HAVING JURISDICTION. DEMOLITION OF THE EXISTING SYSTEM SHALL NOT COMMENCE UNTIL THE NEW SYSTEM HAS BEEN COMPLETELY INSTALLED, TESTED AND APPROVED BY THE AUTHORITY HAVING JURISDICTION. 9. REMOVED FLUORESCENT AND HID LAMPS AND BATTERIES SHALL BE RECYCLED BY A FACILITY APPROVED BY THE OWNER'S REPRESENTATIVE. A UNIFORM HAZARDOUS WASTE MANIFEST SHALL BE PREPARED FOR ALL DISPOSALS AND RETURNED WITH ALL APPLICABLE SIGN OFF'S PRIOR TO APPLICATION FOR FINAL PAYMENT. ABBREVIATIONS A/AMP AMPERE IMC INTERMEDIATE METALLIC CONDUIT AC ALTERNATING CURRENT JB JUNCTION BOX AF AMPERE FRAME KVA KILOVOLT-AMPERE AFF ABOVE FINISHED FLOOR KW KILOWATT AFG ABOVE FINISHED GRADE LTG LIGHTING AIC AMPERE INTERRUPTING CAPACITY MCB MAIN CIRCUIT BREAKER AL ALUMINUM MCC MOTOR CONTROL CENTER AT AMPERE TRIP MEC MASSACHUSETTS ELECTRICAL CODE ATS AUTOMATIC TRANSFER SWITCH MLO MAIN LUGS ONLY AWG AMERICAN WIRE GAUGE MTD MOUNTED C CONDUIT MTG MOUNTING CB CIRCUIT BREAKER NEC NATIONAL ELECTRICAL CODE CKT CIRCUIT No., #NUMBER CL CENTERLINE NS NON-SYSTEM CU COPPER NTS NOT TO SCALE DC DIRECT CURRENT PC PLUMBING CONTRACTOR DE DUAL ELEMENT PWR POWER DWG DRAWING RGS RIGID STEEL CONDUIT EC ELECTRICAL CONTRACTOR RMS ROOT MEAN SQUARE VALUE EMH ELECTRICAL MANHOLE RPM REVOLUTIONS PER MINUTE EMT ELECTRIC METALLIC CONDUIT SF SQUARE FOOT EWC ELECTRIC WATER COOLER SN SOLID NEUTRAL FLMT FLEXIBLE LIQUID TIGHT METALLIC TUBING ST SHUT TRIP CIRCUIT BREAKER GC GENERAL CONTRACTOR SWBD SWITCHBOARD GF GROUND FAULT CIRCUIT BREAKER TYP TYPICAL GFI GROUND FAULT INTERRUPTING V VOLTS GND GROUND VA VOLT-AMPERE HP HORSEPOWER VFD VARIABLE FREQUENCY DRIVE HVAC HEATING, VENTILATION AND AIR CONDITIONING WP WEATHERPROOF BRANCH CIRCUIT AND FEEDER SYMBOLS HOMERUN TO PANELBOARD "PP1", CIRCUIT NUMBER "2 REFER TO PANEL SCHEDULE FOR BREAKER SIZE AND NUMBER OF POLES CONCEALED UNLESS OTHERWISE NOTED NUMBER OF ARROWS INDICATES NUMBER OF INDIVIDUAL HOMERUNS "2", "4", AND "6" UNLESS NOTED OTHERWISE, WIRING FOR EACH CIRCUIT SHALL BE: 20A/1P - 2#12,#12G-34"C 20A/2P - 3#12,#12G-34"C 20A/3P - 4#12,#12G-34"C WIRING FOR MULTIPLE HOMERUNS MAY BE COMBINED IN CONDUIT IN ACCORDANCE WITH NEC REQUIREMENTS 4#1,#6G-112"C HOMERUN FEEDER / BRANCH CIRCUIT CALLOUT: INDICATES (3) #1 AWG (PHASE), (1) #1 AWG (NEUTRAL), (1) #6 GROUND IN A 1-12" CONDUIT FLEXIBLE CONNECTION TO MOTOR OR EQUIPMENT PP1-2,4,6 PP1-2 EXISTING EQUIPMENT DESIGNATIONS X EXISTING TO BE REMOVED, REMOVE ALL ASSOCIATE CONDUIT AND CONDUCTORS XM EXISTING TO REMAIN XN EXISTING EQUIPMENT TO BE REPLACED WITH NEW, CONNECT TO NEW EQUIPMENT CIRCUIT XR EXISTING EQUIPMENT TO BE RELOCATED, JUNCTION AND EXTEND EXISTING CONDUIT AND CONDUCTORS XC EXISTING EQUIPMENT TO REMAIN, PROVIDE NEW BRANCH CIRCUITRY XL NEW LOCATION OF EXISTING EQUIPMENT, JUNCTION AND EXTEND CONDUIT AND CONDUCTORS AS REQUIRED LIGHTING AND CONTROLS FIXTURE SYMBOLS SHOWN BELOW ARE REPRESENTATIVE. NOT ALL SYMBOLS FROM THE PLANS HAVE BEEN SHOWN ON THIS LEGEND. FIXTURE TAG AND CIRCUIT NUMBER LOCATIONS ARE ALSO REPRESENTATIVE. ACTUAL TAG AND CIRCUIT NUMBER LOCATIONS MAY VARY ON PLANS. LIGHTING FIXTURE (SEE LIGHTING FIXTURE SCHEDULE) "A" INDICATES LIGHTING FIXTURE TYPE "#" INDICATES CIRCUIT NUMBER "a" INDICATES SWITCH CONTROL "NL" INDICATES NIGHT LIGHT (UNSWITCHED) CIRCUIT SHADING INDICATES EMERGENCY FIXTURE; FIXTURE CONNECTED TO EMERGENCY GENERATOR RELAY INSTALLED ABOVE CEILING, ADJACENT TO FIXTURE; ALLOWING FIXTURE TO BE TURNED OFF, BUT SHALL ILLUMINATE IF NORMAL POWER IS LOST. FIXTURE TO BE CONNECTED TO EMERGENCY LIGHTING CIRCUITRY, EQUAL TO NINE 24, INC. CATALOG NO. BLTC R CI 120 (OR277); OR BODINE CATALOG NO. GTD20A EXIT SIGN, SHADING INDICATES FACE, ARROW INDICATES DIRECTION OF CHEVRON S a S 3a S 4a S Da SINGLE POLE SWITCH, RATED 20A, 120/277V, MOUNTING HEIGHT 48" TO CENTERLINE OF TOGGLE SWITCH IN "ON" POSITION "a" INDICATES FIXTURE SWITCH CONTROL "3" INDICATES 3-WAY SWITCH CONTROL "4" INDICATES 4-WAY SWITCH CONTROL "D" INDICATES DIMMING CONTROL TYPICAL SENSOR ANNOTATION: "a" INDICATES FIXTURE SWITCH CONTROL "3" INDICATES 3-WAY SWITCH CONTROL "4" INDICATES 4-WAY SWITCH CONTROL "D" INDICATED DIMMING CONTROL WALL OCCUPANCY SENSOR, MULTI-TECHNOLOGY, 180°, 300SF OF COVERAGE CEILING MOUNTED OCCUPANCY SENSOR, LOW VOLTAGE, 360° TWO-SIDED, 2000SF COVERAGE # aA A # a A a # R 3 RECEPTACLES AND DEVICES TYPICAL RECEPTACLE ANNOTATION: "5" INDICATES CIRCUIT NUMBER "WP" INDICATES WEATHERPROOF IN-USE COVER "FB#" INDICATES FLOOR BOX CONFIGURATION, REFER TO FLOOR BOX SCHEDULE / DETAILS FOR ADDITIONAL INFORMATION REFER TO SPECIFICATIONS FOR ADDITIONAL RECEPTACLE AND DEVICE DETAILS DUPLEX GROUND FAULT CIRCUIT INTERRUPTING RECEPTACLE OUTLET JUNCTION BOX, COORDINATE MOUNTING HEIGHT WITH ARCHITECT, "HT" INDICATES HEAT TRACEJ MOTORS AND CONTROLS MOTOR, NUMERAL INDICATES HORSEPOWER SM MANUAL MOTOR STARTED, RATED 20A, 250V, COORDINATE MOUNTING HEIGHT IN FIELD, MOUNTING HEIGHT SHALL NO EXCEED 6'-7" AFF DISCONNECT SWITCH RATED 30A, 3-POLE, IN NEMA TYPE 1 ENCLOSURE, UNLESS OTHERWISE NOTED "3R" INDICATES NEMA TYPE 3R ENCLOSURE "2P" INDICATES 2-POLE, SINGLE PHASE DISCONNECT "60A" INDICATES 60A SWITCH FUSED DISCONNECT SWITCH RATED 30A, 3-POLE, IN NEMA TYPE 1 ENCLOSURE, UNLESS OTHERWISE NOTED "3R" INDICATES NEMA TYPE 3R ENCLOSURE "2P" INDICATES 2-POLE, SINGLE PHASE DISCONNECT "60AF" INDICATES 60A FUSE SIZE "40AT" INDICATES 40A TRIP RATING MAGNETIC MOTOR STARTER, IN NEMA TYPE 1 ENCLOSURE, UNLESS OTHERWISE NOTED "0" INDICATES NEMA STARTER SIZE "4X" INDICATES NEMA TYPE ENCLOSURE 12 3R 60A 3R 60AF 40AT 0 4X PANELBOARD AND TERMINAL CABINET 120/208V PANEL, SURFACE MOUNTED, REFER TO PANEL SCHEDULES 120/208V PANEL, RECESSED MOUNTED, REFER TO PANEL SCHEDULES 277/480V PANEL, SURFACE MOUNTED, REFER TO PANEL SCHEDULES 277/480V PANEL, RECESSED MOUNTED, REFER TO PANEL SCHEDULES TELEPHONE TERMINAL, 4'x8' 34" PLYWOOD BACKBOARD, PAINTED BLACK ANNOTATIONS MECHANICAL EQUIPMENT TAG, REFER TO MECHANICAL EQUIPMENT COORDINATION SCHEDULE FOR ELECTRICAL REQUIREMENTS FEEDER TAG, NUMBER INDICATES AMPERE RATING OF FEEDER AND NUMBER OF WIRES, REFER TO FEEDER SCHEDULE FOR ADDITIONAL INFORMATION EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION SHEET NOTE TAG "#" INDICATES CALL OUT TO CORRESPONDING SHEET NOTE REVISION TAG DETAIL CALLOUT "#" INDICATES THE DETAIL REFERENCE NUMBER "E101" INDICATES THE DRAWING ON WHICH THE DETAIL CAN BE FOUND SECTION "A-A", REFER TO DUCTBANK OR CONDUIT SECTION DETAIL ECH 1 200/4 112.1 # 1 # E101 A A 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E0.1 ELECTRICAL LEGEND LIGHTING FIXTURE SCHEDULE FIXTURE TYPE DESCRIPTION MANUFACTURER AND CATALOG NUMBER LIGHT SOURCE VOLTAGELUMENSTEMPNo.WATTAGE TYPE 4 A LED RECESSED 2'X4'DAYBRITE #2FGG38L-835-4-DS-UNV 3800 3500 -33 LED 277 4 A1 LED RECESSED 2'X4'DAYBRITE #2FGG38L-835-4-DS-UNV-DIM 3800 3500 -33 LED 277 4 B LED EDGELIT PANEL 2'X4'TGS #882440-35-L-F-80CRI 5000 3500 -40 LED 277 4 C LED RECESSED 2'X2'DAYBRITE #2FGG30L-835-2-DS-UNV-DIM 3000 3500 -33 LED 277 4 C1 LED EDGELITE PANEL 2'X2'TGS #88223035L-F-8CRI 3750 3500 -30 LED 277 4 D 6" ROUND APERTURE DOWNLIGHTING LIGHTOLIER #6RN/Z6RDL15835WOCDE1 1500 3500 -30 LED 277 4 D1 6" ROUND APERTURE DOWNLIGHTING LIGHTOLIER #6RN/Z6RDL15835WOCDE1 1500 3500 -30 LED 277 4 E 4' SURFACE MOUNTED LINEAR LED LEDALITE #2911LBEQN047DEW 3000 3500 -33 LED 277 4 E1 4' WALL MOUNTED LINEAR LED LEDALITE #2921LBEWN047DEW 3000 3500 -33 LED 277 4 E2 LOW PROFILE LINEAR LED DAYBRITE #LPLS4L38-35K-UNV-F1 2800 3500 -38 LED 277 4 F 4' LED LINEAR STRIP DAYBRITE #FSSEZ440L835-UNV-DIM 4000 3500 -33 LED 277 4 G 4' LED CORNER MOUNTED LIGHT AEL #BAL-4-35-SL-CP25-156P-B14-M-W 4650 3500 -33 LED 277 4 G1 LED RECESSED 1'X4'AEL #BAA14-35-SL-B14-B14-156P-SY-M 4650 3500 -33 LED 277 4 J DECORATIVE PENDANT SOLERA #ORB-14-PAR-DA-70W-8000L-35K-UNV/P48-PAR-D-DM-XX 8000 3500 -70 LED 277 4 K 4' WALL MOUNTED ROUND LED DAYOLITE #ADL-R06-DI-WRA-35-LO-4-WM-W-TCW 5058 3500 -42 LED 277 4 K-ALT 4' WALL MOUNTED LED DAYOLITE #PRFL-44-DI-FL-FL-35-LO-4-WM-W-TCW 7160 3500 -64 LED 277 4 L 6" LED WALL WASHER DOWNLIGHT LITHONIA LDN6-35-10-LO6AR-LSS-MVOLT-EZ10 1000 3500 -10.4 LED 277 4 M 4' GARAGE VAPOR PROOF LED DAY-BRITE DWAE35L840-4-UNV 3500 4000 -32 LED 277 4 U2 2' LED STRIP FIXTURE METALUX 2SLSTP2040DD-UNV 2510 3500 -23 LED 277 4 Z LED PENDANT WESPORT #JAN-A-36"-3532L-SM-AA-RM 3532 3500 -36 LED 120 4 SINGLE FACE EDGELIT EXIT SIGN, REFER TO FLOOR PLANS FOR DIRECTIONAL ARROWS AND MOUNTING TYPES (WALL/CEILING) EXITRONIX # S902-WB-SR-RC-BA --1 4 LED 120 4 DOUBLE FACE EDGELIT EXIT SIGN, REFER TO FLOOR PLANS FOR DIRECTIONAL ARROWS AND MOUNTING TYPES (WALL/CEILING) EXITRONIX # S903-WB-SR-RM-BA --1 4 LED 120 LIGHTING FIXTURE NOTES: 1. ALL RECESSED FIXTURE TRIMS TO BE PAINTED TO MATCH CEILING. 2. PROVIDE A COMPLETE AND OPERABLE SYSTEM INCLUDING ALL NECESSARY MOUNTING HARDWARE, POWER FEEDS, WIRING CONNECTIONS, DRIVERS, AND CONTROL INTERFACES. 3. PAINT ALL FLANGES INSTALLED IN DRYWALL TO MATCH ADJACENT CEILING FINISH. FLANGES SHALL BE REMOVED FROM CEILING PRIOR TO PAINTING, OR RAZOR CUT AFTER PAINTING TO ALLOW FOR REMOVAL OF THE TRIM FROM THE CEILING. 4. OR EQUAL MANUFACTURES INCLUDING LITHONIA, LIGHTOLIER, AND DAYBRITE. * ELECTRICAL CONTRACTOR SHALL PROVIDE DIMMABLE LED REPLACEMENT LAMPS, LAMP COLOR TEMPERATURE 2700K, AS INDICATED ON THE LIGHTING FIXTURE SCHEDULE. ** ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY COMPONENTS FOR A COMPLETE AND OPERATIONAL SYSTEM. X1 X2 BASEMENT FIRST FLOOR PARTIAL POWER RISER DIAGRAM N.T.S. DISTRIBUTION PANEL NDHP PANEL LPG2 TRANSFORMER T75 XM NOTES: 1.ELECTRICAL CONTRACTOR SHALL GROUND IN ACCORDANCE WITH NEC ARTICLE 250 AS AMENDED BY MASSACHUSETTS ELECTRICAL CODE. 2.CIRCUIT BREAKER SHALL BE COMPATIBLE WITH EXISTING SQUARE D DISTRIBUTION PANEL. 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E0.2 ELECTRICAL RISER & SCHEDULES 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E0.3 ELECTRICAL PANEL SCHEDULES MEN'S LOCKER ROOM ENTRY MEN'S BATHROOM FITNESS ROOM STORAGE TRAINING STORAGE WEAPONS STORAGE BOILER ROOM ELECTRICAL ROOM EMERGENCY ELECTRICAL WEIGHT ROOM ELEVATOR MACHINE ROOM ELEVATOR JANITOR'S CLOSET CORRIDOR RADIO / TELEPHONE ROOM RECOVERED PROPERTY STORAGE WOMEN'S RESTROOM WOMEN'S LOCKER ROOM SHOWER ANTENNA /RADIO STAIR 2 CORRIDOR CORRIDOR CORRIDOR ENTRY Y.P.R.A STORAGE SHOWER STORAGE STAIR STAIR UP UP UP SPRINKLER ROOM TRAINING ROOM TRAINING ROOM RECORD STORAGE SCALE:1/8"=1'-0"1 Basement Floor Plan XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL S S S S SXR/XL XR/XL XR/XLXR/XL LPG NHDPATSATS-EQ EHDP ELDP LPG XM XM XM XM XM XM ATS15KVA T15 XM XM XM ATS-LS HLSP LSP XM112.5KVAT112XM SQUARE D - 112.5KVA STEP-DOWN TRANSFORMER SQUARE D PANELBOARD (DOUBLE TUB) 225A, 120/208V, 3PH, 4W SQUARE D DISTRIBUTION BOARD 400A, 120/208V, 3PH, 4W SQUARE D DISTRIBUTION BOARD 300A, 277/480V, 3PH, 4W SQUARE D DISTRIBUTION BOARD 800A, 277/480V, 3PH, 4W SQUARE D - 15KVA STEP-DOWN TRANSFORMER SQUARE D DISTRIBUTION BOARD 60A, 277/480V, 3PH, 4W SQUARE D PANEL BOARD 60A, 120/208V, 3PH, 4W2 2 (E)UH (E)P 1 (E)P - (E)FC 3 (E)UH213 (E)B(E)B (E)B - (E)BP - (E)BP - (E)BP 6 7 TYP. 8 TYP. S3 a S3 a a a b c S cS bS S S aaa S S3aS3bS3 aS3b S S S cS bc S ab b b b a a a SS S S S S S a9 TYP. XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL 7 TYP. 7 TYP. NOTES: 1. ELECTRICAL CONTRACTOR SHALL DE-ENERGIZED AND REMOVE COMPLETELY INCLUDING BRANCH CIRCUITRY BACK TO THEIR SOURCE (EXISTING PANELBOARDS) WITHIN THE BASE BID SCOPE OF WORK SHOWN, UNLESS NOTED OTHERWISE. REFER TO DRAWING E0.1 FOR DEMOLITION SUBSCRIPTS. 2.EXACT QUANTITY OF ELECTRICAL ITEMS MAY DIFFER IN FIELD. THIS PLAN IS TO INDICATE SCOPE OF DEMOLITION AND GENERAL AMOUNT OF ITEM TO BE REMOVED. 3.ALL ITEMS TO BE REMOVED SHALL BE DISPOSED OFF SITE IN A LEGAL MANNER. 4.FOR ALL ITEMS TO BE REUSED/RELOCATED, REFER TO NEW WORK PLANS FOR NEW LOCATIONS. 5. ELECTRICAL CONTRACTOR SHALL DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH MECHANICAL EQUIPMENT TO BE REMOVED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT (INCLUDING DISCONNECTS, STARTERS, JUNCTION BOXES, WIREWAYS, WIRING AND APPURTENANCES) ASSOCIATED WITH HVAC EQUIPMENT INDICATED FOR REMOVAL. REFER TO MECHANICAL PLANS FOR DETAILS. 6.ALTERNATE #1 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF THE ELECTRICAL ITEMS ASSOCIATED WITH THE THIRD BOILER/BOILER PUMP. 7. BASE BID SCOPE OF WORK: EXISTING CEILING SHALL BE REMOVED BY OTHERS. FOR AREAS WITHIN THE DASHED LINES THE ELECTRICAL CONTRACTOR SHALL REMOVE AND STORE EXISTING LIGHT FIXTURES TO BE RE-INSTALLED ONCE HVAC WORK HAS BEEN COMPLETED. 8.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHT FIXTURES SHOWN ON DRAWINGS. 9.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 ED1.0 ELECTRICAL DEMOLITION PLAN CELL CORRIDOR ALCOVE A/V EQUIPMENT MEN'S RESTROOM INTERVIEW INTERVIEW ROOMSTORAGE CORRIDOR ELEVATOR LOBBY ELEVATOR ENTRY WOMEN'S RESTROOM LOBBY TRAINING ROOM SHOWER VESTIBULE STAIR RECORDS FILING/WORK OFFICE RECORDS OFFICER RECORDS OFFICE PROSECUTOR STATION OFFICER CORRIDOR COMMUNICATIONS MUSTER DISPATCH BREAK ROOM DISPATCH RESTROOMELECTRICAL ROOM SHOWER CORRIDOR WOMEN'S RESTROOM CORRIDOR EVIDENCE PREP LAB MEN'S RESTROOM VESTIBULE STAIR REPORT WRITING LUNCH ROOM/ KITCHENETTE MOTORCYCLE / BICYCLE ELEC. ROOM JANITORS CLOSET CORRIDOR MALE CELL MALE CELL CELL CORRIDOR MALE CELL MALE CELL MALE CELL SHOWER MALE CELL CELL CORRIDOR INTAKE BOOKING ATTORNEY INTERVIEW BOOKING TOILET JUVENILE CELL JUVENILE CELL DETENTION SHOWERCELL CORRIDOR MATRON FEMALE CELL FEMALE CELL FEMALE CELL STAIR SECURE GARAGE BAY STORAGE SALLYPORT GARAGE DOOR GUNS EVIDENCE DRUGS SERGANTS MTS/COMPUTERS MALE CELL MALE CELL UP DN UP DN DN GARAGE DOORSCALE:1/8"=1'-0"1 First Floor Plan XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XLXR/XLXR/XLXR/XLXM XM XM XM XM XM XM XM XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XM XM XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XLXR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL S S XR/XL XR/XL HP1 XM XM LP1A LPC XM SQUARE D PANELBOARD 100A,120/208V, 3PH, 4W SQUARE D PANELBOARD 225A,120/208V, 3PH, 4W SQUARE D PANELBOARD 250A,277/480V, 3PH, 4W LP1B XM SQUARE D PANELBOARD 225A,120/208V, 3PH, 4W 1 2 3 1 2 (E)DAC (E)DAC (E)DAC (E)EF (E)EF - HP 4 1 1 1 1 1 1 1 2 (E)CUH (E)UH (E)UH (E)UH (E)UH (E)CH (E)UH(E)UH (E)UH(E)UH 1 1 1 1 (E)CH (E)CH (E)C (E)C 1 - (E)HP 1 (E)ACC 1 (E)HP (E)DHP 2 - (E)GEF - (E)GEF - (E)GEF 2 (E)ACC XM XM XM XM XM 7 TYP. 8 TYP. S b S S S S3vv S3 v S aS bS cS dS eS f S g S hS j S k S l S mS nS p SrS a S a a S S S3 S3 S b S3dS3dd d eee S S3 aS3a a aS3b S3bb b S S S S S S S dS cS bS aS y S w w a bS3eS3cS3 c b Sac c 9 TYP. XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL NOTES: 1. ELECTRICAL CONTRACTOR SHALL DE-ENERGIZED AND REMOVE COMPLETELY INCLUDING BRANCH CIRCUITRY BACK TO THEIR SOURCE (EXISTING PANELBOARDS) WITHIN THE BASE BID SCOPE OF WORK SHOWN, UNLESS NOTED OTHERWISE. REFER TO DRAWING E0.1 FOR DEMOLITION SUBSCRIPTS. 2.EXACT QUANTITY OF ELECTRICAL ITEMS MAY DIFFER IN FIELD. THIS PLAN IS TO INDICATE SCOPE OF DEMOLITION AND GENERAL AMOUNT OF ITEM TO BE REMOVED. 3.ALL ITEMS TO BE REMOVED SHALL BE DISPOSED OFF SITE IN A LEGAL MANNER. 4.FOR ALL ITEMS TO BE REUSED/RELOCATED, REFER TO NEW WORK PLANS FOR NEW LOCATIONS. 5. ELECTRICAL CONTRACTOR SHALL DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH MECHANICAL EQUIPMENT TO BE REMOVED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT (INCLUDING DISCONNECTS, STARTERS, JUNCTION BOXES, WIREWAYS, WIRING AND APPURTENANCES) ASSOCIATED WITH HVAC EQUIPMENT INDICATED FOR REMOVAL. REFER TO MECHANICAL PLANS FOR DETAILS. 6.ALTERNATE #1 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF THE ELECTRICAL ITEMS ASSOCIATED WITH THE THIRD BOILER/BOILER PUMP. 7. BASE BID SCOPE OF WORK: EXISTING CEILING SHALL BE REMOVED BY OTHERS. FOR AREAS WITHIN THE DASHED LINES THE ELECTRICAL CONTRACTOR SHALL REMOVE AND STORE EXISTING LIGHT FIXTURES TO BE RE-INSTALLED ONCE HVAC WORK HAS BEEN COMPLETED. 8.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHT FIXTURES SHOWN ON DRAWINGS. 9.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 ED1.1 ELECTRICAL DEMOLITION PLAN DN CRIME PREVENTION DOMESTIC VIOLENCE SERGANT DETECTIVE DETECTIVE CONFERENCE DETECTIVE OFFICE D.A.R.E LIEUTENANT DETECTIVE STORAGE CORRIDOR DETECTIVE INTERVIEW DETECTIVE FILE STORAGE STAIRCORRIDOR PATROL LIEUTENANT FAN ROOM LIEUTENANT ADMINISTRATION MEN'S RESTROOM ELEVATOR LOBBY ELEVATOR UPPER LOBBY ADMINISTRATIVE SERVICES GUNS WOMEN'S RESTROOM CONFERENCE E.O.C STAIR CORRIDOR DEPUTY CHIEF'S OFFICE CHIEF'S OFFICE CHIEF'S TOILET DETECTIVE INTERVIEW ELECTRICAL ROOM JANITORS CLOSET DN SCALE:1/8"=1'-0"1 Second Floor Plan XR/XL XR/XL XR/XLXR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XLXR/XLXR/XL XR/XL XR/XL XR/XL XR/XLXR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL HP2 XM SQUARE D PANELBOARD 100A,277/480V, 3PH, 4W LP2A XM SQUARE D PANELBOARD 225A,120/208V, 3PH, 4W 3 1 2 (E)EF (E)AC (E)AC 1 1 (E)C (E)C XM XM 7 TYP. 8 TYP. a a b b b S a S S S S aS bS S S S S dS c c 9 TYP. XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL XR/XL NOTES: 1. ELECTRICAL CONTRACTOR SHALL DE-ENERGIZED AND REMOVE COMPLETELY INCLUDING BRANCH CIRCUITRY BACK TO THEIR SOURCE (EXISTING PANELBOARDS) WITHIN THE BASE BID SCOPE OF WORK SHOWN, UNLESS NOTED OTHERWISE. REFER TO DRAWING E0.1 FOR DEMOLITION SUBSCRIPTS. 2.EXACT QUANTITY OF ELECTRICAL ITEMS MAY DIFFER IN FIELD. THIS PLAN IS TO INDICATE SCOPE OF DEMOLITION AND GENERAL AMOUNT OF ITEM TO BE REMOVED. 3.ALL ITEMS TO BE REMOVED SHALL BE DISPOSED OFF SITE IN A LEGAL MANNER. 4.FOR ALL ITEMS TO BE REUSED/RELOCATED, REFER TO NEW WORK PLANS FOR NEW LOCATIONS. 5. ELECTRICAL CONTRACTOR SHALL DISCONNECT AND MAKE SAFE ALL ELECTRICAL EQUIPMENT ASSOCIATED WITH MECHANICAL EQUIPMENT TO BE REMOVED BY MECHANICAL CONTRACTOR. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL EQUIPMENT (INCLUDING DISCONNECTS, STARTERS, JUNCTION BOXES, WIREWAYS, WIRING AND APPURTENANCES) ASSOCIATED WITH HVAC EQUIPMENT INDICATED FOR REMOVAL. REFER TO MECHANICAL PLANS FOR DETAILS. 6.ALTERNATE #1 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF THE ELECTRICAL ITEMS ASSOCIATED WITH THE THIRD BOILER/BOILER PUMP. 7. BASE BID SCOPE OF WORK: EXISTING CEILING SHALL BE REMOVED BY OTHERS. FOR AREAS WITHIN THE DASHED LINES THE ELECTRICAL CONTRACTOR SHALL REMOVE AND STORE EXISTING LIGHT FIXTURES TO BE RE-INSTALLED ONCE HVAC WORK HAS BEEN COMPLETED. 8.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHT FIXTURES SHOWN ON DRAWINGS. 9.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REMOVAL OF ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 ED1.2 ELECTRICAL DEMOLITION PLAN MEN'S LOCKER ROOM ENTRY MEN'S BATHROOM FITNESS ROOM STORAGE TRAINING STORAGE WEAPONS STORAGE BOILER ROOM ELECTRICAL ROOM EMERGENCY ELECTRICAL WEIGHT ROOM ELEVATOR MACHINE ROOM ELEVATOR JANITOR'S CLOSET CORRIDOR RADIO / TELEPHONE ROOM RECOVERED PROPERTY STORAGE WOMEN'S RESTROOM WOMEN'S LOCKER ROOM SHOWER ANTENNA /RADIO STAIR 2 CORRIDOR CORRIDOR CORRIDOR ENTRY Y.P.R.A STORAGE SHOWER STORAGE STAIR STAIR UP UP UP SPRINKLER ROOM TRAINING ROOM TRAINING ROOM RECORD STORAGE SCALE:1/8"=1'-0"1 Basement Floor Plan E1 HLSP-7 E HLSP-5 C1 NL HLSP-13 C1 b 7 C1 b 7 C1 NL HLSP-13 C1 b 7 C1 b 7 C1 NL HLSP-13 C1 b 7 C1 NL HLSP-13 C1 b 7 C1 a 8 C1 NL HLSP-11 C1 a 8 C1 a 8 C1 NL HLSP-11 C1 a 8 C1 a 8 C1 NL HLSP-11 C1 HLSP-5C1 HLSP-11 C1 b HLSP-11 C1 b HLSP-11 C1 a 8 C1 a HLSP-11 C1 b HLSP-2 C1 b HLSP-11 B a 8 B a HLSP-11 B a 8 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B HLSP-11 B a HLSP-11 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B a HLSP-11 B a 8 B a 8 B NL HLSP-11 B a 8 B a 8 B a 8 B a 8 B a 8 B 8 B 8 B HLSP-11 A 8 A 8 B 8 B 8 B 8 D NL HLSP-11 D1 c HLSP-11 D1 c HLSP-11 D1 c HLSP-11 D1 c HLSP-11 D1 c HLSP-11 F 8 F 8 F 8 F 8 F 8 F 8F HLSP-13 F HLSP-13 F HLSP-13 F 7 F 7 F 7 F 7 F 7 F HLSP-13 F HLSP-13 F 7 F HLSP-13 F 7 F HLSP-13 F 7 F 7 F HLSP-13 F 7 F 7 F HLSP-13 F 7 F 7 F 8 F 8 F HLSP-13F HLSP-13 S3 a S3 a a a S aa b c S cS bS D b 7 S S aaaE1 HLSP-7 E HLSP-5 F HLSP-13 F 7 S S3aS3bS3 aS3b S S S cS bb c S abb b b b a a a SS S S S S F 7 F HLSP-13 R HLSP-4EHDP-7 R HLSP-4EHDP-7 R HLSP-4EHDP-7 HLSP-13 EHDP-7 HLSP-5HLSP-7 HLSP-11 EHDP-8 HLSP-11 HLSP-11 HLSP-11 HLSP-11 HLSP-11 HLSP-11 HLSP-2 HLSP-11 HLSP-11 HLSP-11 HLSP-13 HLSP-13 HLSP-13 R HLSP-13EHDP-7 R HLSP-11EHDP-8 R HLSP-11EHDP-8 R HLSP-11EHDP-8 1 TYP. 1 TYP. 2TYP. 2TYP. NOTES: 1.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REPLACEMENT OF ALL LIGHT FIXTURES. REFER TO FLOOR PLANS FOR EXACT TYPE AND QUANTITY OF FIXTURES. 2.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPERATE BREAK OUT COST FOR ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E1.0 ELECTRICAL LIGHTING FLOOR PLAN CELL CORRIDOR ALCOVE A/V EQUIPMENT MEN'S RESTROOM INTERVIEW INTERVIEW ROOMSTORAGE CORRIDOR ELEVATOR LOBBY ELEVATOR ENTRY WOMEN'S RESTROOM LOBBY TRAINING ROOM SHOWER VESTIBULE STAIR RECORDS FILING/WORK OFFICE RECORDS OFFICER RECORDS OFFICE PROSECUTOR STATION OFFICER CORRIDOR COMMUNICATIONS MUSTER DISPATCH BREAK ROOM DISPATCH RESTROOMELECTRICAL ROOM SHOWER CORRIDOR WOMEN'S RESTROOM CORRIDOR EVIDENCE PREP LAB MEN'S RESTROOM VESTIBULE STAIR REPORT WRITING LUNCH ROOM/ KITCHENETTE MOTORCYCLE / BICYCLE ELEC. ROOM JANITORS CLOSET CORRIDOR MALE CELL MALE CELL CELL CORRIDOR MALE CELL MALE CELL MALE CELL SHOWER MALE CELL CELL CORRIDOR INTAKE BOOKING ATTORNEY INTERVIEW BOOKING TOILET JUVENILE CELL JUVENILE CELL DETENTION SHOWERCELL CORRIDOR MATRON FEMALE CELL FEMALE CELL FEMALE CELL STAIR SECURE GARAGE BAY STORAGE SALLYPORT GARAGE DOOR GUNS EVIDENCE DRUGS SERGANTS MTS/COMPUTERS MALE CELL MALE CELL UP DN UP DN DN GARAGE DOORSCALE:1/8"=1'-0"1 First Floor Plan L d 24 L d 24 L d 24 L d 24 L d 24 L d 24 D a HLSP-8 D a 24 D a HLSP-8 D a 24 D a HLSP-8 D a 24 D 24 D HLSP-8 D 24 D a HLSP-8 D a 24 D HLSP-8 D 24Da HLSP-8 D a 5 D a HLSP-8 D a 5 D a HLSP-8 D a 24 D a 24 D a HLSP-8 D a 24 D a HLSP-8 XM XM XM XM XM XM XM XM D a HLSP-8 D a 24 D a HLSP-8 D a 24 D a HLSP-8 D a 24 D 24 D HLSP-8 D 1 D b 24 D b HLSP-8 D b 24 D NL HLSP-8 D b 26 D NL HLSP-8 D b 26 D NL HLSP-8 D b 26 D NL HLSP-8 D b 26 D NL HLSP-8 D NL HLSP-8 XM XM XM XM K b,c 24 B HLSP-8 B 24 B 24 B 24 B 24 A HLSP-8 A 24 A 24 A HLSP-8 A a 24 A a 24 A a 24 A a 24 A a 24 A a HLSP-8 A a 24 A a 24 A a HLSP-8 A a 24 A a 24 A a 24 A 22 A HLSP-6 A 22 A 22 A 22 A 22 A HLSP-6 A 22 A 26 A HLSP-8 A 26 A 26 A 26 A 26 A 26 A HLSP-8 A 26 A 26 A 26 A 26 A 26 A 26 A 26 A 26 A 26 A 24 A 24 B 24 XM XM C a HLSP-8 C a 26 C a 26 C a 26 C a 26 C a 26 C a 26 C a HLSP-8 C a HLSP-8 C a 26 C a 26 C a 26 C a 26 C a 26 C a 26 C a HLSP-8 C a 26 C a HLSP-8 C a 26 C NL HLSP-6 C d 22 C NL HLSP-6 C d 22 C1 e 22 C d 22 C NL HLSP-6 C c 26 C NL HLSP-8 C c 26 C NL HLSP-8 C c 26 C NL HLSP-8 C1 NL HLSP-8 C 20 C 20 C HLSP-6 C 20 C 20 C 20 C HLSP-6 C 20 C 20 C 20 C 20 C 20 C 20 C 20 C HLSP-6 C1 NL HLSP-6 C1 e 22 C1 e 22 C1 NL HLSP-6 C1 e 22 C1 HLSP-5 C1 HLSP-7 C1 HLSP-5 C1 HLSP-7 C1 q HLSP-6 C1 q 20 C1 q 20 B HLSP-8 C NL HLSP-6 E 22 E 22 E 22 E 22 E 22 E 22 E HLSP-8 E 3 E 22 M a 22 M a 22 M a HLSP-6 M a 22 M b 22 M b HLSP-6 M b 22 M b 22 M b HLSP-6 G n 20 G m 20 G1 HLSP-6 G1 v 20 G1 v HLSP-6 G1 v 20 G1 v 20 G1 v HLSP-6 G1 v 20 G1 v 20 G1 v HLSP-6 G1 v 20 G1 v HLSP-6 E2 a 20 E2 a HLSP-6 E2 a 20 E2 a 20 E2 a 20 E2 a 20 E2 a 20 E2 a 20 E2 a 20 E2 a 20 E2 a HLSP-6 E2 a 20 G1 w 20 G1 w HLSP-6 G1 w 20 G d 20 G c 20 G b 20 G a 20 B HLSP-8 B HLSP-8 B HLSP-8 E1 HLSP-7 E1 HLPS-5 E HLPS-7 E1 HLPS-5 D b D b F 22 F 22 F 22 F 22 F 22 F HLSP-8 F HLSP-8 F 22 F 22 F 24 U2 22 G k 20 G r HLSP-6 G j 20 G1 HLSP-6 G j 20 G1 HLSP-6Gp HLSP-6 G h 20 G g 20 G y HLSP-6 G f 20 G e 20 G1 z 20 G1 z HLSP-6 E HLSP-8 E HLSP-8 E HLSP-8 E HLSP-8 D HLSP-8 D 24 S b S S S S3vv S3 v S aS bS cS dS eS f S g S hS j S k S l S mS nS p q SrS a S S aa a S S S3 S3 S b S3dS3dd d eee S S3 aS3a a aS3b S3bb b S S S S S S S dS cS bS aHLSP-5 HLSP-6 zS y S w w a b HLSP-6 S3eS3eK b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 K b,c 24 S3cS3 c HP1-20 HP1-26 HP1-22 HLSP-8 HP1-24 HLSP-6 HLSP-6 HLSP-6 HLSP-6 HLSP-6HLSP-8HLSP-8 HLSP-8 HLSP-8 HLSP-8 HLSP-7 HLSP-8 HLSP-8 b HLSP-8 HLSP-8 HLSP-8 HLSP-8 HLSP-8 HLSP-8 HLSP-8 HLSP-8 R HLSP-6HP1-22 R HLSP-2HP1-20 R HLSP-6HP1-20 R R HLSP-6HP1-20 R HLSP-6HP1-22 R HLSP-8HP1-22 R HLSP-8HP1-24 R HLSP-8HP1-26 R HLSP-8HP1-24 R HLSP-8HP1-24 R HLSP-8HP1-24 R HLSP-8HP1-24 R HLSP-8HP1-26 R HLSP-6HP1-20 R HLSP-6HP1-20 R HLSP-6HP1-4 R HLSP-6HP1-22 Sac c HLSP-2HP1-20 R HLSP-8HP1-24 1 TYP. 1 TYP. 2 TYP. 2TYP. NOTES: 1.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REPLACEMENT OF ALL LIGHT FIXTURES. REFER TO FLOOR PLANS FOR EXACT TYPE AND QUANTITY OF FIXTURES. 2.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPERATE BREAK OUT COST FOR ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E1.1 ELECTRICAL LIGHTING FLOOR PLAN DN CRIME PREVENTION DOMESTIC VIOLENCE SERGANT DETECTIVE DETECTIVE CONFERENCE DETECTIVE OFFICE D.A.R.E LIEUTENANT DETECTIVE STORAGE CORRIDOR DETECTIVE INTERVIEW DETECTIVE FILE STORAGE STAIRCORRIDOR PATROL LIEUTENANT FAN ROOM LIEUTENANT ADMINISTRATION MEN'S RESTROOM ELEVATOR LOBBY ELEVATOR UPPER LOBBY ADMINISTRATIVE SERVICES GUNS WOMEN'S RESTROOM CONFERENCE E.O.C STAIR CORRIDOR DEPUTY CHIEF'S OFFICE CHIEF'S OFFICE CHIEF'S TOILET DETECTIVE INTERVIEW ELECTRICAL ROOM JANITORS CLOSET DN SCALE:1/8"=1'-0"1 Second Floor Plan C HLSP-5 C HLSP-7 C HLSP-5 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C 30 C c HLSP-9 C c 30 C c 30 C c 30 C c 30 C c 30 C c 30 C c HLSP-9 C NL HLSP-9 C a 28 C NL HLSP-9 C a 28 C C1 HLSP-5 C1 HLSP-7 C1 HLSP-5 C1 HLSP-7 D a HLSP-9 D a 30 D a HLSP-9 D a 30 D a HLSP-9 D a 30 D a 30 D a HLSP-9 D a 30 D a HLSP-9 D a 30 D b 30 D NL HLSP-9 D b 30 D b 30 D b 30 D NL HLSP-9 D d 30 D d 30DNL HLSP-9 D b 30 D NL HLSP-9 Z NL HLSP-9 D2 NL HLSP-9 D2 NL HLSP-9 D NL HLSP-9 D b 30 D2 NL HLSP-9 B HLSP-9 B HLSP-9 A 30 A 30 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A 28 A A 28 A 28 A 28 A 28 A 28 AA 28 A 28 A A 28 A 28 A 28 A 28 A 28 A 28 A 28 F 28 F 28 F HLSP-9 F 28 F 28 F 28 F 28 F 28 F HLSP-9 F HLSP-9 F 28 F C HLSP-9 C B HLSP-9 B HLSP-9 C b 30 C b 30 C b 30 D a HLSP-9 D NL HLSP-9 D b 30 Z NL HLSP-9 a a b b b S a S S HLSP-9 HLSP-9 HLSP-9 HLSP-9 HLSP-9 HLSP-9S aS bS S S S S S dS c c HP1-28 R HLSP-9HP1-7 R HLSP-9HP1-30 R HLSP-9HP1-30 R HLSP-9HP1-7 HP1-30 2 TYP. 1 TYP. NOTES: 1.ALTERNATE # 2 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR THE REPLACEMENT OF ALL LIGHT FIXTURES. REFER TO FLOOR PLANS FOR EXACT TYPE AND QUANTITY OF FIXTURES. 2.ALTERNATE # 3: ELECTRICAL CONTRACTOR SHALL PROVIDE SEPERATE BREAK OUT COST FOR ALL LIGHTING CONTROL DEVICES SHOWN ON DRAWINGS. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E1.2 ELECTRICAL LIGHTING FLOOR PLAN MEN'S LOCKER ROOM ENTRY MEN'S BATHROOM FITNESS ROOM STORAGE TRAINING STORAGE WEAPONS STORAGE BOILER ROOM ELECTRICAL ROOM EMERGENCY ELECTRICAL WEIGHT ROOM ELEVATOR MACHINE ROOM ELEVATOR JANITOR'S CLOSET CORRIDOR RADIO / TELEPHONE ROOM RECOVERED PROPERTY STORAGE WOMEN'S RESTROOM WOMEN'S LOCKER ROOM SHOWER ANTENNA /RADIO STAIR 2 CORRIDOR CORRIDOR CORRIDOR ENTRY Y.P.R.A STORAGE SHOWER STORAGE STAIR STAIR UP UP UP SPRINKLER ROOM TRAINING ROOM TRAINING ROOM RECORD STORAGE SCALE:1/8"=1'-0"1 Basement Floor Plan FC 1 FC 3 FC 2 FC 4 B 1 B 2 B 3 BP 1 BP 2 BP 3 P 1 P 2 UH 1 LPG2-5 EF 1 AC 1 BC 1 FC 5 FC 9 FC 8 FC 10 FC 7 AC 2 FC 6 LPG NHDPATSATS-EQ EHDP ELDP LPG ATS15KVA T15 ATS-LS HLSP LSP 112.5KVAT112PUMP VFD'S XM 75KVAT75LPG2 1 NOTES: 1.ALTERNATE # 1 : ELECTRICAL CONTRACTOR SHALL PROVIDE SEPARATE BREAK OUT COST FOR WORK ASSOCIATED WITH THE THIRD BOILER/BOILER PUMP. # 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E2.0 ELECTRICAL POWER FLOOR PLAN CELL CORRIDOR ALCOVE A/V EQUIPMENT MEN'S RESTROOM INTERVIEW INTERVIEW ROOMSTORAGE CORRIDOR ELEVATOR LOBBY ELEVATOR ENTRY WOMEN'S RESTROOM LOBBY TRAINING ROOM SHOWER VESTIBULE STAIR RECORDS FILING/WORK OFFICE RECORDS OFFICER RECORDS OFFICE PROSECUTOR STATION OFFICER CORRIDOR COMMUNICATIONS MUSTER DISPATCH BREAK ROOM DISPATCH RESTROOMELECTRICAL ROOM SHOWER CORRIDOR WOMEN'S RESTROOM CORRIDOR EVIDENCE PREP LAB MEN'S RESTROOM VESTIBULE STAIR REPORT WRITING LUNCH ROOM/ KITCHENETTE MOTORCYCLE / BICYCLE ELEC. ROOM JANITORS CLOSET CORRIDOR MALE CELL MALE CELL CELL CORRIDOR MALE CELL MALE CELL MALE CELL SHOWER MALE CELL CELL CORRIDOR INTAKE BOOKING ATTORNEY INTERVIEW BOOKING TOILET JUVENILE CELL JUVENILE CELL DETENTION SHOWER CELL CORRIDOR MATRON FEMALE CELL FEMALE CELL FEMALE CELL STAIR SECURE GARAGE BAY STORAGE SALLYPORT GARAGE DOOR GUNS EVIDENCE DRUGS SERGANTS MTS/COMPUTERS MALE CELL MALE CELL UP DN UP DN DN GARAGE DOORSCALE:1/8"=1'-0"1 First Floor Plan M NEW GAS DETECTION SYSTEM NEW GAS DETECTION SYSTEM NEW GAS DETECTION SYSTEM FC 12A CUH # FC 15 FC 13 FC 14 FC A HP A HP B FC B FC 17 BC 2 FC 19 FC 22 FC 20 FC 12B FC C FC 21 UH 1 LP1A-29 FC 12C UH 1 LP1A-31 UH 1 LP1A-31 UH 1 LP1A-31 UH 1 LP1A-31 UH 1 LP1A-29 UH 1 LP1A-29 UH 1 LP1A-29 GEF 3 FC 18 HP C ACCU 2 HP 1 HP 2 HP 3 GEF 2 M HP1 LP1A LPC LP1B DHP 2 XM XM FC 11 XM DAC 2 M M M GEF 1 LP1B-36 LP1B-38 LP1B-40 LP1B-42 42 42 42 ACCU 1 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E2.1 ELECTRICAL POWER FLOOR PLAN SCALE:1/8"=1'-0"1 Second Floor Plan DN CRIME PREVENTION DOMESTIC VIOLENCE SERGANT DETECTIVE DETECTIVE CONFERENCE DETECTIVE OFFICE D.A.R.E LIEUTENANT DETECTIVE STORAGE CORRIDOR DETECTIVE INTERVIEW DETECTIVE FILE STORAGE STAIRCORRIDOR PATROL LIEUTENANT FAN ROOM LIEUTENANT ADMINISTRATION MEN'S RESTROOM ELEVATOR LOBBY ELEVATOR UPPER LOBBY ADMINISTRATIVE SERVICES GUNS WOMEN'S RESTROOM CONFERENCE E.O.C STAIR CORRIDOR DEPUTY CHIEF'S OFFICE CHIEF'S OFFICE CHIEF'S TOILET DETECTIVE INTERVIEW ELECTRICAL ROOM JANITORS CLOSET DN ERV 2 ERV 1 FC 29 FC 27 BC 3 FC 24 FC 25 FC 26 HP2 LP2A FC 28 FC 30 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 E2.2 ELECTRICAL POWER FLOOR PLAN FIRE ALARM SPECIFICATION 1.FIRE DETECTION AND ALARM SYSTEM 1.1.GENERAL 1.1.1.REFER TO FRONT END ELECTRICAL SPECIFICATIONS SHEETS FOR ALL PROJECT REQUIREMENTS. 1.1.2.FOR REPLACEMENT OR MODIFIED FIRE ALARM SYSTEMS AT NO TIME DURING CONSTRUCTION SHALL THE BUILDING BE WITHOUT FIRE ALARM PROTECTION. 1.1.3.THE CONTRACTOR MUST OBTAIN A PERMIT FROM THE FIRE DEPARTMENT PRIOR TO COMMENCEMENT OF EQUIPMENT INSTALLATION. ALL WORK SHALL BE DONE IN CONFORMANCE WITH THE LOCAL FIRE DEPARTMENT INSTALLATION REQUIREMENTS AND SYSTEM INSTALLATION GUIDELINES. 1.1.4.ALL FIRE ALARM WORK BEYOND THE MASTER BOX AND INSIDE OF THE BUILDING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. ABSOLUTELY NO CONNECTIONS SHALL BE MADE TO THE MUNICIPAL FIRE ALARM CIRCUITS, EXCEPT BY THE LOCAL FIRE DEPARTMENT. 1.1.5.ALL FIRE ALARM DEVICES AND EQUIPMENT USED SHALL BE APPROVED FOR USE BY THE LOCAL FIRE DEPARTMENT. 1.1.6.FIRE ALARM SYSTEM MODIFICATIONS: MODIFICATIONS MADE TO THE BASE BUILDING FIRE ALARM SYSTEM SHALL BE MADE IN COMPLIANCE WITH ALL APPLICABLE CODES AND REQUIREMENTS. ALL NEW COMPONENTS SHALL BE UL LISTED FOR THEIR INTENDED PURPOSE AND COMPATIBLE FOR USE ON THE EXISTING SYSTEM. 1.1.7.THE ADDITION OF NEW INITIATING DEVICES OR NOTIFICATION APPLIANCES TO THE EXISTING SLC AND NAC SHALL NOT ADVERSELY EFFECT SUPERVISION. THE WIRING CLASS AND STYLE FOR THE ADDITION OF DEVICES SHALL BE CONSISTENT WITH EXISTING. 1.1.8.EXISTING BASE BUILDING DEVICES SHALL EITHER BE INCORPORATED INTO NEW FIRE ALARM DESIGN OR REMOVED. ALL PROGRAMMING ASSOCIATED WITH REMOVAL OF DEVICES SHALL BE PROVIDED BY THE CONTRACTOR. 1.1.9.NEW DEVICES SHALL BE PROGRAMMED TO INITIATE ACTION IN ACCORDANCE WITH THE EXISTING SEQUENCE OF OPERATION AS APPROVED BY THE AHJ. SYSTEM SUBMITTAL SHALL INCLUDE AN INPUT/OUTPUT MATRIX CLEARLY DEFINING THE SEQUENCE FOR EACH ADDED DEVICE. 1.1.10.THE FIRE ALARM DESIGN IS BASED ON AN EXISTING ADDRESSABLE SYSTEM. E.C SHALL COORDINATE WITH OWNER AND DETERMINE THE REQUIREMENTS OF THE EXISTING SYSTEM. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO PROVIDE AN OPERATIONAL FIRE ALARM SYSTEM THAT IS COMPATIBLE WITH THE EXISTING SYSTEMS REQUIREMENTS. 1.1.10.1.EXISTING FACP MANUFACTURER/MODEL: GAMEWELL 1.1.11.THE COMPLETED FIRE ALARM SYSTEM SHALL MEET ALL LOCAL AND STATE CODES. 1.1.12.EQUIPMENT AND COMPLETED INSTALLATION SHALL BE U.L. LISTED OR APPROVED AND SHALL MEET APPROVAL OF THE LOCAL FIRE DEPARTMENT, STATE FIRE MARSHALL, AUTHORITIES HAVING JURISDICTION AND SHALL BE IN ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, ADA CODE, NFPA 70, 72 AND 72E. 1.1.13.THE COMPLETE SYSTEM SHALL CONTAIN SMOKE DETECTION, AUDIO/VISUAL ALARMS, PULL STATIONS, DUCT SMOKE DETECTORS, WATER AND TAMPER FLOW SWITCHES AND OTHER DEVICES INCLUDING POWER SUPPLIES AS REQUIRED FOR A COMPLETE SYSTEM. 1.1.14.DEVICE ADDRESSES SHALL BE LEGIBLE WITHOUT REMOVAL OF THE DETECTOR. THE DETECTOR ADDRESS SHALL BE CONCEALED WHEN PLACED INTO THE BASE. 1.2.SEQUENCE OF OPERATIONS: REFER TO SEQUENCE OF OPERATIONS INPUT/OUTPUT MATRIX 1.3.REMOTE DEVICES 1.3.1.SMOKE DETECTORS SHALL BE ADDRESSABLE PHOTOELECTRIC TYPE (UNLESS NOTED OTHERWISE) AND SHALL OPERATE AT 24 VOLTS DC. PROVIDE DOUBLE CONTACT BASE FOR SMOKE DETECTORS USED FOR ELEVATOR RECALL AND TO OPERATE REMOTE LED'S. 1.4.5.DUCT SMOKE DETECTORS SHALL BE ADDRESSABLE PHOTOELECTRIC TYPE. COMPLETE WITH REMOTE TEST STATIONS AND SAMPLING TUBES. REMOTES TEST STATIONS SHALL HAVE RED LED INDICATING LIGHT AND STAINLESS STEEL FACEPLATE. DUCT SMOKE DETECTORS SHALL SHUT OFF ASSOCIATED AIR HANDLING UNIT UPON ACTIVATION. DETECTORS SHALL BE PURCHASED BY THE ELECTRICAL CONTRACTOR AND INSTALLED BY THE MECHANICAL CONTRACTOR. 1.4.5.1.PROVIDE AND INSTALL ALL NECESSARY WIRE, CONDUIT, RELAYS AND CONNECTIONS FROM ALL DUCT SMOKE DETECTORS TO THEIR ASSOCIATED RETURN AND SUPPLY FAN CONTROLLERS. UPON ACTIVATION OF A DUCT SMOKE DETECTOR, IN ADDITION TO SOUNDING THE GENERAL ALARM, THE DUCT SMOKE DETECTOR SHALL IMMEDIATELY SHUT DOWN THE ASSOCIATED FAN. 1.5.WIRING 1.5.1.ALL FIRE ALARM WIRE AND CABLE SHALL BE UL LISTED FOR FIRE ALARM USE. 1.5.2.THE FIRE ALARM SYSTEM SHALL BE A COMPLETE AUTOMATIC AND MANUAL, CLOSED CIRCUIT, CLASS A, 4 WIRE, CONNECTED AND LEFT IN FIRST-CLASS OPERATING CONDITION. 1.5.3.FOR FIRE ALARM WIRING IN ENCLOSED SPACES, PROVIDE PLENUM RATED, TYPE FPLP, WITH RED OUTER JACKET. INSTALLATION SHALL MEET REQUIREMENTS OF NEC ARTICLE 770 AND 725. CONDUCTORS SHALL BE SOLID COPPER #14 MINIMUM, WITH LOW SMOKE, LOW FLAME TYPE JACKET. 1.5.4.FOR FIRE ALARM WIRING IN EXPOSED AREAS, PROVIDE TYPE THHN INSULATION. WIRE SIZE SHALL BE #14 AWG MINIMUM. ALL SURFACE MOUNTED WIRING RELATED TO THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN TYPE EMT/RGS CONDUIT. 1.5.5.ALL JOINTS AND CONNECTIONS SHALL BE IN JUNCTION BOXES. ALL CONNECTIONS NOT ON APPROVED TERMINAL STRIPS SHALL BE SOLDERED AND TAPED. ALL JUNCTION BOXES SHALL BE PAINTED RED. 1.6.TWO-HOUR RESISTIVE CABLES 1.6.1.CABLES SHALL MEET IBC 2015, NFPA 70, NFPA 72, UL CATEGORY FHIT SYSTEM 40A. 1.6.2.CABLES SHALL BE EQUAL TO COMTRAN CABLE'S VITALINK FHIT SYSTEM 40A TWO-HOUR FIRE RATED CIRCUIT INTEGRITY (CI/CIC) CABLE. 1.7.MANUFACTURERS 1.7.1.COMPLETE SYSTEMS SHALL BE MANUFACTURED BY GAMEWELL TO MATCH EXISTING SYSTEM. 1.7.2.FOR EXISTING SYSTEMS BEING REUSED, DEVICES SHALL BE COMPATIBLE WITH EXISTING MANUFACTURER (GAMEWELL). 1.8.TESTING 1.8.1.THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FIRE ALARM TESTING AND CERTIFICATION CHARGES. 1.8.2.CERTIFY THE INSTALLATION WITH ACCEPTANCE TESTING. THE ELECTRICAL CONTRACTOR SHALL CONDUCT THE ACCEPTANCE TEST WITH THE LOCAL FIRE DEPARTMENT IN ACCORDANCE WITH NFPA 72. TEST INCLUDE BUT MAY NOT BE LIMITED TO THE FOLLOWING: MEGGER (INSULATION) TESTING, LOOP CONTINUITY, GROUND, SHORT, OPEN CIRCUIT, A WRITTEN REPORT SHALL BE SUBMITTED DETAILING THE RESULTS OF THE PRELIMINARY TESTS SHALL ACCOMPANY THE REQUEST FOR FINAL ACCEPTANCE TEST. 1.8.3.THE FIRM WHO HOLDS THE EXISTING SYSTEM MAINTENANCE CONTRACT SHALL PERFORM FINAL CONNECTIONS, PROGRAMMING, AND TESTING. THE CONTRACTOR SHALL CARRY ALL COSTS ASSOCIATED WITH FINAL CONNECTIONS, PROGRAMMING AND TESTING AS WELL AS DISABLING CONNECTIONS TO THE MUNICIPAL LOOP DURING FINAL CONNECTIONS AND TESTING. FIRE ALARM TYPICAL DEVICE ANNOTATION: "15" INDICATES CANDELA RATING MANUAL PULL STATION SMOKE DETECTOR "D" INDICATES DUCT SMOKE DETECTOR "R" INDICATES ELEVATOR RECALL FIRE ALARM DEVICE "FACP" INDICATES FIRE ALARM CONTROL PANEL "FABP" INDICATES FIRE ALARM BOOSTER PANEL "FATC" INDICATES FIRE ALARM TERMINAL CABINET "RTS" INDICATES REMOTE TEST STATION FIRE ALARM ANNUNCIATION DEVICE "F" INDICATES RED INDICATING BEACON, EXTERIOR MOUNTED, WEATHERPROOF "R" INDICATES REMOTE AREA LED INDICATOR F RS FACP F FIRE ALARM CONTROL PANEL BASEMENT XM XM XM F MAIN ELECTRIC ROOM FIRE ALARM RISER DIAGRAM N.T.S. FIRE ALARM RISER DIAGRAM NOTES: 1.ALL SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT (FIRE ALARM RATED FPLR METALLIC FLEXIBLE CONDUIT) AND BE COMPATIBLE WITH EXISTING INSTALLATION. 2.RISER DIAGRAM DOES NOT SHOW ENTIRE SYSTEM. REFER TO FLOOR PLANS FOR EXACT QUANTITIES AND LOCATIONS OF ALL SYSTEM DEVICES. 3.TYPICAL RELOCATION OR ADDITION OF FIRE ALARM INITIATION DEVICE. DISCONNECT AND REMOVE EXISTING SLC LOOP WIRING BACK TO EXISTING DEVICES TO REMAIN. PROVIDE NEW SLC LOOP WIRING (TO MATCH EXISTING) BETWEEN EXISTING PULL STATIONS TO REMAIN TO ACCOMMODATE DEMOLITION OF OR RELOCATION OF EXISTING DEVICES. 4.EXISTING GAMEWELL FIRE ALARM CONTROL PANEL LOCATED IN THE MAIN ELECTRIC ROOM. # 4 SEQUENCE OF OPERATIONS INPUT / OUTPUT MATRIX SYSTEM OUTPUTS CONTROL UNIT ANNUNCIATION NOTIFICATION REQUIRE LIFE SAFETY CONTROL FIRE ALARM SYSTEM OPERATION SCHEDULE ACTUATE COMMON ALARM SIGNAL INDICATORACTUATE AUDIBLE ALARM SIGNALACTUATE COMMON SUPERVISORY SIGNAL INDICATORACTUATE AUDIBLE SUPERVISORY SIGNALACTUATE COMMON TROUBLE SIGNAL INDICATORACTUATE AUDIBLE COMMON TROUBLE SIGNALACTUATE FIRE FLOOR ALARM INDICATORACTUATE EVACUATION SIGNALS ON ALL FLOORSACTUATE LOCAL AUDIBLE TEMP-3 PATTERN FIRE SIGNALACTUATE LOCAL ADA VISUAL ALARMACTUATE ELEVATOR FIRE HATDISPLAY/PRINT CHANGE OF STATUSTRANSMIT FIRE ALARM SIGNAL TO SUPERVISING STATIONTRANSMIT SUPERVISORY SIGNAL TO SUPERVISING STATIONTRANSMIT TROUBLE SIGNAL TO SUPERVISORY STATIONRELEASE MAGNETICALLY HELD SMOKE DOORSRECALL PEDESTRIAN ELEV. TO PRIMARY RECALL FLOORRECALL PEDESTRIAN ELEV. TO ALTERNATE RECALL FLOOROPEN SMOKE DAMPER AT TOP OF ELEVATOR SHAFTCLOSE FIRE/SMOKE DAMPER ON ASSOCIATED FIRE FLOORSHUT DOWN ALL ASSOCIATED HVAC EQUIPMENTOVERRIDE MUSIC SYSTEM (MUTE)OVERRIDE TELEVISION SYSTEM (TURN OFF)OVERRIDE DIMMING SYSTEM (LIGHTS TO FULL BRIGHT)SYSTEM INPUTS A B C D E F G H I J K L M N O P Q R S T U V W X 1 MANUAL FIRE ALARM BOXES ············ 2 SMOKE DETECTORS ············· 3 ELEVATOR LOBBY SMOKE DETECTORS ············· 4 ELEVATOR LOBBY SMOKE ON PRIMARY RECALL FLOOR ············· 5 ELEVATOR MACHINE SMOKE DETECTORS ·············· 6 HEAT DETECTORS ············ 7 WATERFLOW ············ 8 SPRINKLER CONTROL VALVE ···· 9 DUCT SMOKE DETECTORS ····· 10 GENERATOR RUNNING ···· 11 FIRE ALARM AC POWER FAILURE ···· 12 FIRE ALARM SYSTEM LOW BATTERY ···· 13 OPEN CIRCUIT ···· 14 GROUND FAULT ···· 15 NOTIFICATION APPLIANCE SHORT CIRCUIT ···· 16 SUPERVISORY ···· 17 TROUBLE ···· NOTES: 1. ALL EVENTS SHALL BE RECORDED AT THE FIRE ALARM CONTROL PANEL AND SHALL INDICATE TIME AND DATE OF OCCURRENCE AND LIST DEVICE INITIATED. 2. TROUBLE AND SUPERVISORY SIGNALS SHALL BE MONITORED IN ACCORDANCE WITH 780CMR 903.4.1. TYPICAL FIRE ALARM DEVICE LABELING DETAIL NOTES: 1.AT A MINIMUM, ELECTRICAL CONTRACTOR SHALL PROVIDE TYPED LABELS WITH PTOUCH MACHINE TO INDICATE ADDRESS OF FIRE ALARM DEVICE WITHIN ENCLOSED ROOM OR ROOM NUMBER IF SYSTEMS IS ZONED. LABELING SYSTEM SHALL BE APPLIED BUT NOT LIMITED TO THE FOLLOWING DEVICES: AUDIBLE/VISUAL DEVICE, VISUAL DEVICE, SMOKE DETECTOR, REMOTE TEST STATION, REMOTE ALARM INDICATOR, FLOW SWITCH, TAMPER SWITCH, ETC. ADDRESS/RM NUMBER N.T.S.1 TYPICAL DUCT SMOKE DETECTOR MOUNTING DETAIL NOTES: 1.REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATION OF ALL HVAC UNITS AND DUCTWORK. DUCT TYPE SMOKE DETECTORS SHALL BE LOCATED AS IN ACCORDANCE WITH NFPA 72 AND COORDINATED WITH MECHANICAL CONTRACTOR. 2.TO AUXILIARY CONTACTS IN RESPECTIVE AIR-HANDLING UNIT STARTER FOR UNIT SHUTDOWN ON ALARM. DUCT SMOKE DETECTOR SHALL BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL CONTRACTOR. DUCT SMOKE DETECTORS SHALL BE INSTALLED AS IN ACCORDANCE WITH INTERNATIONAL MECHANICAL CODE: ·SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM, IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND APPLIANCES. ·WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES AND SERVE ANY PORTION OF A RETURN AIR SYSTEM HAVING A DESIGN CAPACITY GREATER THAN 15,000 CFM, SMOKE DETECTORS SHALL BE INSTALLED AT EACH STORY. SUCH SMOKE DETECTORS SHALL BE LOCATED UPSTREAM OF THE CONNECTION BETWEEN THE RETURN AIR RISER AND ANY AIR DUCTS OR PLENUMS. ·SMOKE DETECTORS SHALL BE INSTALLED IN THE SUPPLY AIR SYSTEM FOR ALL MAKE-UP AIR UNITS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM AS IN ACCORDANCE WITH NFPA 90A. HVAC UNIT RF SFRETURN DUCT CP S D CM IR 120V POWER SUPPLY CIRCUIT (TYP) SUPPLY DUCT N.T.S. HVAC UNIT STARTER HVAC UNIT POWER SUPPLY FEEDER HVAC UNIT DISCONNECT 2 SEQUENCE OF OPERATIONS: CO SENSOR WILL INITIATE AUDIBLE ALERT TONE UPON REACHING SETPOINT AND: 1.DISCONNECT POWER TO THE BOILER CONTROL PANEL FOR SYSTEM SHUTDOWN. 2.SEND SUPERVISORY SIGNAL TO FIRE ALARM SYSTEM. NOTES: 1.DISCONNECT SWITCHES MOUNTED AT 6'-0" AFF AT EACH ENTRY TO THE BOILER ROOM. PROVIDE RED BOILER SHUTOFF PLATES. 2.WIRE ALL ESO DISCONNECT SWITCHES AND FIRESTAT IN SERIES TO SHUT DOWN BOILER IF ANY ONE DISCONNECT IS OPENED. 3.ALL BOILER BRANCH CIRCUIT WIRING SHALL BE WIRED THROUGH NEW CONTACTOR AS REQUIRED TO ALLOW SYSTEM SHUTDOWN VIA CO DETECTION SYSTEM OR EMERGENCY SHUTOFF SWITCH/FIRESTAT. BOILER SHUTDOWN DETAIL FIRE ALARM ADDRESSABLE ZONE MONITORING MODULE 120V Ø N 4#12-3/4"C (R) ESO DOOR #2 DOOR #1 ESO FST BRANCH CIRCUIT REQUIREMENTS PER SCHEDULE (TYP.) N.T.S. NORMALLY OPEN CONTACT. CONTACT OPEN ON LOSS OF POWER AND/OR ALARM CONDITION REMOTE CARBON MONOXIDE DETECTOR EQUAL TO HONEYWELL MODEL E3SRMCO LOCAL DISCONNECT SWITCH. PROVIDE LOCKING MEANS FOR "LOCK-OUT-TAG-OUT" CAPABILITIES. NEMA 1 ENCLOSED ELECTRICALLY HELD CONTACTOR, CONTACT QUANTITY TO MATCH CIRCUITS REQUIRED CARBON MONOXIDE DETECTOR (BASE UNIT) EQUAL TO HONEYWELL MODEL E3SARHSCO-120V FIRESTAT FURNISHED AND INSTALLED BY ATC CONTRACTOR B 1 (NEW) B 2 (NEW) CP CP CO C CO ZMM 3 FIRST FLOOR XM F S S R SECOND FLOOR XM F S S R 3S D ROOF XR/XL XR/XL S XR/XL XR/XL XR/XL S S R S XR/XL XR/XL XR/XL 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 FA0.1 FIRE ALARM LEGEND AND SPECIFICATIONS S S R S S S S S S S S S S MEN'S LOCKER ROOM ENTRY MEN'S BATHROOM FITNESS ROOM STORAGE TRAINING STORAGE WEAPONS STORAGE BOILER ROOM ELECTRICAL ROOM EMERGENCY ELECTRICAL WEIGHT ROOM ELEVATOR MACHINE ROOM ELEVATOR JANITOR'S CLOSET CORRIDOR RADIO / TELEPHONE ROOM RECOVERED PROPERTY STORAGE WOMEN'S RESTROOM WOMEN'S LOCKER ROOM SHOWER ANTENNA /RADIO STAIR 2 CORRIDOR CORRIDOR CORRIDOR ENTRY Y.P.R.A STORAGE SHOWER STORAGE STAIR STAIR UP UP UP SPRINKLER ROOM TRAINING ROOM TRAINING ROOM RECORD STORAGE SCALE:1/8"=1'-0"1 Basement Floor Plan EXISTING GAMEWELL FIRE ALARM CONTROL PANEL XM XM XM XMXR/XL XM XR/XL XR/XL XR/XL XR/XL XR/XL XM XM XR/XL XR/XL XR/XL S S S R 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 FA1.0 FIRE ALARM FLOOR PLAN S S S S S S S CELL CORRIDOR ALCOVE A/V EQUIPMENT MEN'S RESTROOM INTERVIEW INTERVIEW ROOMSTORAGE CORRIDOR ELEVATOR LOBBY ELEVATOR ENTRY WOMEN'S RESTROOM LOBBY TRAINING ROOM SHOWER VESTIBULE STAIR RECORDS FILING/WORK OFFICE RECORDS OFFICER RECORDS OFFICE PROSECUTOR STATION OFFICER CORRIDOR COMMUNICATIONS MUSTER DISPATCH BREAK ROOM DISPATCH RESTROOMELECTRICAL ROOM SHOWER CORRIDOR WOMEN'S RESTROOM CORRIDOR EVIDENCE PREP LAB MEN'S RESTROOM VESTIBULE STAIR REPORT WRITING LUNCH ROOM/ KITCHENETTE MOTORCYCLE / BICYCLE ELEC. ROOM JANITORS CLOSET CORRIDOR MALE CELL MALE CELL CELL CORRIDOR MALE CELL MALE CELL MALE CELL SHOWER MALE CELL CELL CORRIDOR INTAKE BOOKING ATTORNEY INTERVIEW BOOKING TOILET JUVENILE CELL JUVENILE CELL DETENTION SHOWERCELL CORRIDOR MATRON FEMALE CELL FEMALE CELL FEMALE CELL STAIR SECURE GARAGE BAY STORAGE SALLYPORT GARAGE DOOR GUNS EVIDENCE DRUGS SERGANTS MTS/COMPUTERS MALE CELL MALE CELL UP DN UP DN DN GARAGE DOORXR/XL XM XM XM XM XM XR/XLXR/XL XR/XL XR/XL XM SCALE:1/8"=1'-0"1 First Floor Plan S R S S S 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 FA1.1 FIRE ALARM FLOOR PLAN DN CRIME PREVENTION DOMESTIC VIOLENCE SERGANT DETECTIVE DETECTIVE CONFERENCE DETECTIVE OFFICE D.A.R.E LIEUTENANT DETECTIVE STORAGE CORRIDOR DETECTIVE INTERVIEW DETECTIVE FILE STORAGE STAIRCORRIDOR PATROL LIEUTENANT FAN ROOM LIEUTENANT ADMINISTRATION MEN'S RESTROOM ELEVATOR LOBBY ELEVATOR UPPER LOBBY ADMINISTRATIVE SERVICES GUNS WOMEN'S RESTROOM CONFERENCE E.O.C STAIR CORRIDOR DEPUTY CHIEF'S OFFICE CHIEF'S OFFICE CHIEF'S TOILET DETECTIVE INTERVIEW ELECTRICAL ROOM JANITORS CLOSET DN SCALE:1/8"=1'-0"1 Second Floor Plan S R S S S S XR/XL XR/XL XR/XL XR/XL XR/XL ERV 2 S D RTS R XM 311 Great Road, Post Office Box 1551 www.blwengineers.com T: 978.486.4301 F: 978.428.0067 Littleton, Massachusetts 01460 BLW Engineers, Inc. HVAC * ELECTRICAL * PLUMBING * FIRE PROTECTION Drawing No.: Client: Yarmouth Police Department 340 Higgins Crowell Rd Yarmouth, MA 02673 Project:YARMOUTH POLICE DEPARTMENTHVAC REPLACEMENT340 HIGGINS CROWELL RDYARMOUTH, MA 02673Project No.:21131 Scale: Checked By:JP Drawn By:SW As Noted Title: Submission: 5/19/21DD THIS MATERIAL IS CONFIDENTIAL AND MAY NOT BE DISCLOSED WITHOUT PRIOR WRITTEN AUTHORIZATION FROM BLW ENGINEERS INC. COPYRIGHT BLW ENGINEERS INC. Seal: 95% CD 6/23/21 100% CD 7/14/21 ADDENDUM #1 Revision: 8/19/21 PERMIT 9/3/21 FA1.2 FIRE ALARM FLOOR PLAN