HomeMy WebLinkAboutHVAC COMcheckCOMcheck Software Version 4.1.5.3
Mechanical Compliance Certificate
Project Title:
2018 IECC
Project Type:Alteration
Location:Yarmouth, Massachusetts
Climate Zone:5a
Construction Site:
340 Higgins Crowell Rd
Yarmouth, MA 02673
Owner/Agent:Designer/Contractor:
BLW Engineers
311 Great Rd
Littleton, MA 01460
Project Information
Energy Code:
Yarmouth Police Station
Mechanical Systems List
Quantity System Type & Description
Cooling: 2 each - Split System, Capacity = 12 kBtu/h, Air-Cooled Condenser, No Economizer, Economizer exception: Humidity
Requirements
Proposed Efficiency = 20.00 SEER, Required Efficiency: 13.00 SEER
Fan System: None
1 AC-1/ACCU-1 (Single Zone):
Heating: 1 each - Unit Heater, Hot Water, Capacity = 8 kBtu/h
No minimum efficiency requirement applies
Fan System: None
9 UH-1 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 27 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 TB-1 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 23 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 TB-2 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 17 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 TB-3 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 16 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 TB-4 (Single Zone):
VRF Condensing Unit, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 190 kBtu/h,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 168 kBtu/h,
No minimum efficiency requirement applies
Fan System: None
1 HP-1 (Single Zone):
1 HP-2 (Single Zone):
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
351 ofPage
Quantity System Type & Description
VRF Condensing Unit, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 320 kBtu/h,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 312 kBtu/h,
No minimum efficiency requirement applies
Fan System: None
VRF Condensing Unit, Air Cooled w/ Heat Recovery Heat Pump
Heating Mode: Capacity = 160 kBtu/h,
No minimum efficiency requirement applies
Cooling Mode: Capacity = 144 kBtu/h,
No minimum efficiency requirement applies
Fan System: None
1 HP-3 (Single Zone):
Split System Heat Pump
Heating Mode: Capacity = 28 kBtu/h,
Proposed Efficiency = 11.30 HSPF, Required Efficiency = 8.20 HSPF
Cooling Mode: Capacity = 24 kBtu/h,
Proposed Efficiency = 21.50 SEER, Required Efficiency: 14.00 SEER
Fan System: None
1 FC-A/HP-A (Single Zone):
Split System Heat Pump
Heating Mode: Capacity = 20 kBtu/h,
Proposed Efficiency = 12.80 HSPF, Required Efficiency = 8.20 HSPF
Cooling Mode: Capacity = 12 kBtu/h,
Proposed Efficiency = 27.00 SEER, Required Efficiency: 14.00 SEER
Fan System: None
1 FC-B/HP-B (Single Zone):
Split System Heat Pump
Heating Mode: Capacity = 20 kBtu/h,
Proposed Efficiency = 10.20 HSPF, Required Efficiency = 8.20 HSPF
Cooling Mode: Capacity = 12 kBtu/h,
Proposed Efficiency = 21.00 SEER, Required Efficiency: 14.00 SEER
Fan System: None
1 FC-C/HP-C (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 10 kBtu/h
No minimum efficiency requirement applies
Fan System: None
5 HWC-200 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 16 kBtu/h
No minimum efficiency requirement applies
Fan System: None
5 HWC-400 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 24 kBtu/h
No minimum efficiency requirement applies
Fan System: None
12 HWC-600 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 45 kBtu/h
No minimum efficiency requirement applies
Fan System: None
4 HWC-1000 (Single Zone):
Heating: 1 each - Hydronic or Steam Coil, Hot Water, Capacity = 93 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 HWC-1200 (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 6 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
4 FC-6MBH (Single Zone):
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
352 ofPage
Quantity System Type & Description
No minimum efficiency requirement applies
Fan System: None
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 8 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
1 FC-8MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 12 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
6 FC-12MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 18 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
5 FC-18MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 24 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
7 FC-24MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 30 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
2 FC-30MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 36 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
1 FC-36MBH (Single Zone):
Cooling: 1 each - VRF Zone Fan Unit, Capacity = 72 kBtu/h, No Economizer, Economizer exception: Heat Recovery System
No minimum efficiency requirement applies
Fan System: None
1 FC-72MBH (Single Zone):
Heating: Hot Water Boiler, Capacity 500 kBtu/h, Gas, with Waterloop Heat Pump
Proposed Efficiency: 90.00 % Et, Required Efficiency: 80.00 % Et
3 Boiler:
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical alteration project represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
353 ofPage
Belinda Vuto-Mechanical Engineer Belinda Vuto 09/02/2021
Inspection Checklist
Requirements: 98.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.5.3
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2018 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
354 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C403.12.2
,
C403.12.3
[FO9]3
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature and outdoor
temperature. future connection to
controls.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
355 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
356 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
357 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
358 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
359 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3510 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3511 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3512 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3513 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3514 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3515 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.11.3
[ME61]2
HVAC piping insulation insulated in
accordance with Table C403.11.3.
Insulation exposed to weather is
protected from damage and is
provided with shielding from solar
radiation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3516 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3517 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
See the Mechanical Systems list for values.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3518 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3519 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
Exception: Fans included in equipment having certified seal
for air or energy performance of the equipment package.
C403.12.1
[ME71]2
Systems that heat outside the building
envelope are radiant heat systems
controlled by an occupancy sensing
device or timer switch.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.3
[ME55]2
HVAC equipment efficiency verified.Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.2.2
[ME59]1
Natural or mechanical ventilation is
provided in accordance with
International Mechanical Code
Chapter 4. Mechanical ventilation has
capability to reduce outdoor air supply
to minimum per IMC Chapter 4.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.7.1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
Exception: Systems with energy recovery.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3520 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.7.2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.7.6
[ME141]3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403.7.6.1 and C403.7.6.2).
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.7.4
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.7.4(1)
and C403.7.4(2).
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.7.5
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.11.1
,
C403.11.2
[ME60]2
HVAC ducts and plenums insulated in
accordance with C403.11.1 and
constructed in accordance with
C403.11.2, verification may need to
occur during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3
[ME69]3
The heating of fluids in hydronic
systems that have been previously
mechanically cooled, and the cooling
of fluids that have been previously
mechanically heated are limited in
accordance with Sections C403.4.3.1-
C403.4.3.3. Single boiler systems
>500,000 Btu/h have multistaged or
modulating burner.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3521 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
1
[ME50]2
Three-pipe hydronic systems using a
common return for hot and chilled
water are not used.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3522 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3523 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.3.
3.2
[ME121]3
Closed-circuit cooling tower within
heat pump loop have either automatic
bypass valve or lower leakage positive
closure dampers. Open-circuit tower
within heat pump loop have automatic
valve to bypass all heat pump water
flow around the tower. Open- or
closed-circuit cooling towers used in
conjunction with a separate heat
exchanger have heat loss by shutting
down the circulation pump on the
cooling tower loop. Open- or closed
circuit cooling towers have a separate
heat exchanger to isolate the cooling
tower from the heat pump loop, and
heat loss is controlled by shutting
down the circulation pump on the
cooling tower loop.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.3.
3.3
[ME28]3
Two-position automatic valve
interlocked to shut off water flow
when hydronic heat pump with
pumping system >10 hp is off.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.4
[ME68]3
Hydronic systems greater than
300,000 Btu/h designed for variable
fluid flow. See section language for full
details.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3524 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.4.5
[ME26]3
Chilled water plants with multiple
chillers have capability to reduce flow
automatically through the chiller plant
when a chiller is shut down. Boiler
plants with multiple boilers have the
capability to reduce flow automatically
through the boiler plant when a boiler
is shut down.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3525 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.4.1.
4
[ME63]2
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <=
60F and cooling setpoint >= 80F.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.9.5
[ME31]3
Condenser heat recovery system that
can heat water to 85 ºF or provide
60% of peak heat rejection is installed
for preheating of service hot water.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.3.3
[ME35]1
Hot gas bypass limited to: <=240
kBtu/h – 50% >240 kBtu/h – 25%
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3526 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.2.
2
[ME54]3
HVAC hydronic heating and cooling
coils have means to balance and have
pressure test connections.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3527 ofPage
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3528 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.6
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
C405.7
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
C405.8.2,
C405.8.2.
1
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
C405.9
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3529 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3530 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3531 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3532 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.1
[FI42]3
Heat pump controls prevent
supplemental electric resistance heat
from coming on when not needed.
Complies
Does Not
Not Observable
Not Applicable
Exception: Requirement does not apply.
C403.4.1.
2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3533 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
Requirement will be met.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3534 ofPage
Project Title:
Data filename:
Yarmouth Police Station
N:\Jobs\2021 Projects\21131 Yarmouth PD HVAC Replacement Contract
653\Calculations\hvac\hvac comcheck.cck
09/02/21Report date:
3535 ofPage