HomeMy WebLinkAboutEngineer Plans - 2021PROPOSED S.A.S.
20' x 30' LEACH FIELD
W/3 DISTRIBUTION LINES
PROPOSED
PUMP CHAMBER
MgFgolJlLJ
OCT 29 2021
HEALTH DEPT.
EXIST. SEPTIC TANK
(TO REMAIN)
TOP, EL =100.20
INV.(OUT), £L:=98.87±
FEMA FLOOD ZONEDESIGNATION
FLOOD MAP NO: 25001CO569J
EFFECTIVE DATE: 07/14/21
0.2% ANNUAL CHANCE
OWNER OF RECORD
TASHA,. MARK
TASHA, CAROL—ANNE
135 UNION STREET
YARMOUTH PORT. MA 02675
GENERAL NOTES:
1. ALL CHANGES TO THIS PLAN MUST BE APPROVED BY THE LOCAL BOARD OF
HEALTH AND THE DESIGN ENGINEER,
2. ALL WORK AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE
STATE ENVIRONMENTAL CODE, TITLE V, AND ANY APPLICABLE LOCAL RULES
AND REGULATIONS.
3. THE SEWAGE DISPOSAL SYSTEM SHALL NOT BE BACKFILLED PRIOR TO
INSPECTION AND APPROVAL BY THE BOARD OF HEALTH & DESIGN ENGINEER.
4. ANY CONDITIONS ENCOUNTERED DURING CONSTRUCTION DIFFERING FROM
THOSE SHOWN HEREON SHALL BE REPORTED TO THE DESIGN ENGINEER
BEFORE CONSTRUCTION CONTINUES.
5. ALL ELEVATIONS BASED ON AN ASSUMED DATUM, BARNSTABLE GLS.±.
6. THE DESIGN ENGINEER IS NOT RESPONSIBLE FOR THE FAILURE OF THE
CONTRACTOR OR OWNER TO NOTIFY THE LOCAL BOARD OF HEALTH FOR
PROPER INSPECTIONS DURING CONSTRUCTION.
7. WATER SUPPLY PROVIDED BY TOWN WATER SERVICE..
8. THERE ARE NO PRIVATE ABUTTING WELLS WITHIN 150' OF THE PROPOSED S.A.S.
9. ALL AREAS CLEARED FOR CONSTRUCTION SHALL BE RESTORED AS SHOWN ON
THE PLAN OR AS OTHERWISE DIRECTED BY THE APPROVING AUTHORITIES.
10. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY LOCATIONS
OF ALL UNDERGROUND UTILITIES, PRIOR TO BEGINNING CONSTRUCTION.
11. WHERE REQUIRED, CONTRACTOR SHALL REMOVE ALL UNSUITABLE SOILS BENEATH
AND FOR 5' ON ALL SIDES OF THE THE S.A.S. AND REPLACE WITH CLEAN SAND
AS SPECIFIED IN 310 CMR 255(3).
12. AREAS REQUIRING STRIPOUT OF UNSUITABLE MATERIALS. SHALL BE INSPECTED BY
A LICENSED SOIL EVALUATOR PRIOR TO BACKFILL
13. THE ENGINEER IS NOT RESPONSIBLE FOR ANY UNDOCUMENTED EXISTING SEPTIC
SYSTEM COMPONENTS NOT SHOWN ON THE PLAN.
14. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO MAINTAIN THE
STABILITY OF ADJACENT STRUCTURES.
15.. THIS PLAN IS TO BE USED FOR SEPTIC SYSTEM PURPOSES ONLY AND
IS NOT TO BE CONSIDERED A PROPERTY LINE SURVEY.
MAP ID: 37-68
PROPOSED SEPTIC SYSTEM UPGRADE PLAN
5 KEN'S WAY, WEST YARMOUTH, MA
Prepared for: Mark Tasha, 135 Union Street, Yarmouth Port, MA 02675
Engineers: Surveyors: SCALE DRAWN JOB. NO.
Engineering Works, Inc. KERgineering, Inc. 1 "=20' P.T.M. 258-20
12 West Crossfield Road 2854 Cranberry Hwy. DATE CHECKED SHEET N0.
Forestdole, MA 02644 E.Wareham, MA 02538
(508) 477-5313 (508) 273-0377 10/13/21 P.T.M. 1 Of 3
LEGEND
38 �—
EXISTING CONTOUR
o;
x 30.95
EXISTING SPOT GRADE<_
Yarmouth Health Department
7.3
PROPOSED SPOT GRADE
APPROVED
-W-
EXISTING WATER SERVICE
—G—
EXISTING GAS SERVICE
b
Hama STRI" B UNDARY
3
— O. H. W.---
OVERHEAD WIRES
9.1
TEST TEST PIT
"
0 C HORIZON
9K
BENCHMARK
CBDH d
102,35
S 25'45'05" W
101.60
110.23'
VENT
4— X
_0
10T ARFA
PROPOSED S.A.S.
20' x 30' LEACH FIELD
W/3 DISTRIBUTION LINES
PROPOSED
PUMP CHAMBER
MgFgolJlLJ
OCT 29 2021
HEALTH DEPT.
EXIST. SEPTIC TANK
(TO REMAIN)
TOP, EL =100.20
INV.(OUT), £L:=98.87±
FEMA FLOOD ZONEDESIGNATION
FLOOD MAP NO: 25001CO569J
EFFECTIVE DATE: 07/14/21
0.2% ANNUAL CHANCE
OWNER OF RECORD
TASHA,. MARK
TASHA, CAROL—ANNE
135 UNION STREET
YARMOUTH PORT. MA 02675
GENERAL NOTES:
1. ALL CHANGES TO THIS PLAN MUST BE APPROVED BY THE LOCAL BOARD OF
HEALTH AND THE DESIGN ENGINEER,
2. ALL WORK AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF THE
STATE ENVIRONMENTAL CODE, TITLE V, AND ANY APPLICABLE LOCAL RULES
AND REGULATIONS.
3. THE SEWAGE DISPOSAL SYSTEM SHALL NOT BE BACKFILLED PRIOR TO
INSPECTION AND APPROVAL BY THE BOARD OF HEALTH & DESIGN ENGINEER.
4. ANY CONDITIONS ENCOUNTERED DURING CONSTRUCTION DIFFERING FROM
THOSE SHOWN HEREON SHALL BE REPORTED TO THE DESIGN ENGINEER
BEFORE CONSTRUCTION CONTINUES.
5. ALL ELEVATIONS BASED ON AN ASSUMED DATUM, BARNSTABLE GLS.±.
6. THE DESIGN ENGINEER IS NOT RESPONSIBLE FOR THE FAILURE OF THE
CONTRACTOR OR OWNER TO NOTIFY THE LOCAL BOARD OF HEALTH FOR
PROPER INSPECTIONS DURING CONSTRUCTION.
7. WATER SUPPLY PROVIDED BY TOWN WATER SERVICE..
8. THERE ARE NO PRIVATE ABUTTING WELLS WITHIN 150' OF THE PROPOSED S.A.S.
9. ALL AREAS CLEARED FOR CONSTRUCTION SHALL BE RESTORED AS SHOWN ON
THE PLAN OR AS OTHERWISE DIRECTED BY THE APPROVING AUTHORITIES.
10. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY LOCATIONS
OF ALL UNDERGROUND UTILITIES, PRIOR TO BEGINNING CONSTRUCTION.
11. WHERE REQUIRED, CONTRACTOR SHALL REMOVE ALL UNSUITABLE SOILS BENEATH
AND FOR 5' ON ALL SIDES OF THE THE S.A.S. AND REPLACE WITH CLEAN SAND
AS SPECIFIED IN 310 CMR 255(3).
12. AREAS REQUIRING STRIPOUT OF UNSUITABLE MATERIALS. SHALL BE INSPECTED BY
A LICENSED SOIL EVALUATOR PRIOR TO BACKFILL
13. THE ENGINEER IS NOT RESPONSIBLE FOR ANY UNDOCUMENTED EXISTING SEPTIC
SYSTEM COMPONENTS NOT SHOWN ON THE PLAN.
14. CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO MAINTAIN THE
STABILITY OF ADJACENT STRUCTURES.
15.. THIS PLAN IS TO BE USED FOR SEPTIC SYSTEM PURPOSES ONLY AND
IS NOT TO BE CONSIDERED A PROPERTY LINE SURVEY.
MAP ID: 37-68
PROPOSED SEPTIC SYSTEM UPGRADE PLAN
5 KEN'S WAY, WEST YARMOUTH, MA
Prepared for: Mark Tasha, 135 Union Street, Yarmouth Port, MA 02675
Engineers: Surveyors: SCALE DRAWN JOB. NO.
Engineering Works, Inc. KERgineering, Inc. 1 "=20' P.T.M. 258-20
12 West Crossfield Road 2854 Cranberry Hwy. DATE CHECKED SHEET N0.
Forestdole, MA 02644 E.Wareham, MA 02538
(508) 477-5313 (508) 273-0377 10/13/21 P.T.M. 1 Of 3
EXISTING SEPTIC TANK &
NOTE: TO PREVENT BREAKOUT, FINAL GRADE
SHALL NOT BE AT, OR BELOW, EL.=95.50
F
I--
PROPOSED PUMP CHAMBER
FOR A DISTANCE OF 15' FROM THE EDGE
PROVIDE RISERS & COVERS AS DESCRIBED:
OF THE PROPOSED S.A.S.
1)INLET COVER SET TO 6" OF GRADE.
_
2) 20" OUTLET COVER SET TO GRADE
PROPOSED D -BOX
MANHOLE COVER SHALL BE SECURED
INSTALL WATERTIGHT H-20 PROPOSED SAS
COVER SET TO FINISH GRADE INSTALL VENT AND
HgLL
BEOR00M
TO PREVENT UNAUTHORIZED ACCESS.
.
INSTALL INSPECTIONPORT MANIFOLD ALL LINES
F.G. EL.=101.1±
F.G. EL. 101.8(MIN.)
BATH
PROVIDE ENOUGH WIRE F.G. EL.=102.0±
F.G. EL.=101.1± MAINTAIN 2% GRADE MIN. OVER S.A.S.
I _ J
L- r _ _ _ _ _
SLACK TO REMOVE
PUMP
4 DIAM. INSPECTION PORT,
SECOND FLOO
- Ir MAX) 1;' x 35' ACHING FIELD W/2 4" PERFORATED N S.A.S., SOLID
' L = 5't
® ABOVE S.A.S., WITH SCREW CAP
scM 4a e ocKs <•sGH40 PVC SE T i0 WITHIN 3' OF GRADE.
'{
® 5=19 MIN.
4'SCH40 (PVC) '":.
THRUST 5 _
PftO�\AE1 qU. KENO
s
BATH BEDROOM
...
6..
�� 6" EFF.DEPTH
EL.=100.10(END)
10
INV.=100.44 I SLOPE OF 05% I�INV.
±4"
11 V.=100.61 H-20 EFFECR EPIENGTHPE
BEDROOM BEDROOM
ADD INV.=98.75
EFFLUENT 2 FLOATS
PROPOSED D—BOX
3 OUTLETS (MIN.) COIL ABSORPTION SYSTEM (PROFILE)
z ENTRY
= LIVING z
FILTER USE OUTLET
INV.=99.00± INV.=100.26
DINING ROOM
-77 KNOCK OUT
ENTRY WAY s o
ISTIN "_ -
a
& STORAGEEX
SEPTIC TANK 1000 GALLON MONOLITHIC
PUMP CHAMBER (H-10 RATED)
ENTRY ENTRY
INV.=98.87±
EXISTING (See Pump Detail, Sheet 3)
OUTSID E WI 3" OF 3/4" TO 1 1/2"
ENTRY
(FIELD VERIFY)
DRIVEWAY DRIVE Ay NATIVE STONE OR PAVED
ESTABLISH VEGETATIVE COVER
FIRST FLOOR
WITH 4" OF LOAM & SEED FOOTPRINT FOOTPRINT DRIVEWAY SURFACE
NOTES:
1) PUMP CHAMBER & D–BOX SHALL BE SET LEVEL AND TRUE
rFINISH GRADE
I EL 1016(MIN.) 10"± GRAVEL OVER
TO GRADE ON A MECHANICALLY COMPACTED 6" CRUSHED
NATIVE FILL OVER
FILTER FABRIC 1l FILTER FABRIC
41 9'�
STONE BASE, AS SPECIFIED IN 310 CMR 15.221(2).
2) INSTALL INLET & OUTLET TEES AS REQUIRED.
.`. •`• '; ' •` APPROVED
r,_A FILTER FABRIC
__ 30' _ I n
2 r SHEDS 1
3) MAX. COVER OVER SEPTIC TANK, D–BOX & S.A.S. SHALL BE 36".
_`''
BREAKOUT ELEV.=100.61 -'
71
No
4) CONTRACTOR SHALL VERIFY ALL EXISTING PIPE INVERTS PRIOR%1'8.
BOTTOM ELEV.=99.6
I
TO CONSTRUCTION.
5) EFFLUENT FILTER SHALL BE INSTALLED ON OUTLET 5' MIN. SEPARATION TO G.W. 3 6 6 4' 3�4^_t 1/2" DOUBLE
WASHED STONE
k �� ,r
NO O �„!
I $ fib• f/
TEE AS MANUFACTURED BY ZABEL OR EQUAL, FILTER
20' EFFECTIVE WIDTH
A."J• N
I I I f�1
SHALL BE INSPECTED AND CLEANED ANNUALLY.
HIGH G.W. EL: 93.9
SEPTIC SYSTEM PROFILE
— - - - - - 27,9'
57.9'
S'
',
SOIL LOG
DESIGN CRITERIA
f EXISTING-"
DATE: SEPTEMBER 30, 2020
SOIL EVALUATOR: PETER McENTEE SE#1542E
T� ff iH0USE(115).�'
NUMBER OF BEDROOMS: 4
WITNESS: PHIL RENAUD HEALTH AGENT
'
8• �. fT.OF.=102.0±'
SOIL TEXTURAL CLASS: CLASS I
ELEV. TP -2 DEPTH
4 • /
DESIGN PERCOLATION RATE: <2 MIN/IN
101.3 0",
DAILY FLOW: 440 GPD
FILL6i
f``
DESIGN FLOW: 440 GPD
100'8 B
GARBAGE GRINDER: NO
SANDY LOAM
/
LEACHING AREA REQUIRED: (440 GPD) = 594.6 SF
99.5-c 10YR 5/6 22„
1 ENCLOSED f
GPD/SF
LAYOUT
S.A.S. LAYOUT LPORCH
.74
18%36"
EXISTING SEPTIC TANK: 1000 GALLON CAPACITY
MED. SAND
PROPOSED PUMP CHAMBER: 1000 GALLON CAPACITY, H-10
2.5Y 6/6
PROPOSED SEPTIC SYSTEM UPGRADE PLAN
PROPOSED D -BOX: 1 INLET, 3 OUTLET (MIN.), H-20
LEACH FIELD
93.9 HIGH G.W. _
TIDAL
5 KEN'S WAY, WEST YARMOUTH, MA
INSTALL AN 20' X 30'
Prepared for: Mark Tasha, 135 Union Street, Yarmouth Port, MA 02675
SIDEWALL AREA: NOT APPLICABLE
93,8 STDG. G.W. __ 90"
BOTTOM AREA: 20' x 350 = 600 S.F.
Engineers:
Surveyors:
SCALE
DRAWN
JOB. NO.
TOTAL AREA: ..................................._600 S.F.
PER93RATE: <2 MIN/IN. ("C" HORIZON)
Engineering Works, Inc.
JC Engineering, Inc.
N.T.S.
P.T.M.
258-20
DATE
CHECKED
SHEET N0,
PROPERTY WITHIN 300' TO TIDAL AREA
12 West Crossfield Road
Forestdale, MA 02644
Cranberry Hwy.
E.Wareham, MA 02538
E.WG
LEACHING CAPACITY = 0.74 GPD/SF x 600 SF = 444
GPD
MONITORING WELL INSTALLED W/ TIDAL DATA LOGGING
(508) 477-5313
(508) 273-0377
10/13/21
P.T.M.
2 Of 3
PEAK TIDAL GROUNDWATER EL. -93.9
NEMA 4 JUNCTION BOX CORROSION RESISTANT
& LIQUID—TIGHT CABLE CONNECTORS SUPPORTED
BY 1-1/4" PVC CONDUIT. JOINTS TO BE MADE
PROVIDE WATERTIGHT CONCRETE RISER WITH WATERTIGHT. USE SJE RHOMBUS—JB PLUGGER
SECURED FRAME &COVER TO GRADE E ENOUGH WP
OR EQUAL. PROVIIRE
OTO
SLACK REMOVE MP
INSTALL 1' PVC CONDUIT TO HOUSE FOR WIRING
HOISTING CABLE STAINLESS STEEL WITH WATERTIGHT JOINTS. WIRE HIGH WATER ALARM
/7x19
1/8" DIAMETER. FLOAT TO SJE UFROMNCIRCUIITTXT ALARM
WIRE' STRENGTH.
ENOUGH ON CIRCUIT SEPARATE TO THE PUMP.
SLACK TO REMOVE PUMP 2" BALL VALVE (FIELD ADJUST FOR 20 GPM RATE)
DOSING & STORAGE REQUIREMENTS
INV.(IN)=98.75 (INSTALL QUICK DISCONNECT FOR EASY REMOVAL)
—' 2"SCH. 40 DISCHARGE (THROUGH RISER—SEE PROFILE)
DESIGN FLOW: 440 GPD
ALARM ON EL: 96.21 2" 90' ELBOW W/ 1/4" WEEP HOLE
DOSING REQUIRED: 4 CYCLES/DAY (SAND)
PUMP ON EL: 95.79 FOR SELF—DRAINING FORCE MAIN
440 � 4 = 110 GALLONS/CYCLE
18' 2" SWING CHECK VALVE
DISTANCE REQUIRED BETWEEN PUMP
PUMP OFF EL: 95.38
BOTTOM OF 1�
ON AND PUMP OFF FLOATS:
PUMP CHAMBER 1 8" 2" SCH. 40 PVC DISCHARGE PIPE
110 GAL/CYCLE =250 GAL/FT = 0.44 FT/CYCLE (SAY 5")
ELEV.= 94.46 ADDITIONAL 3/16" VENT HOLE (MIN.) ABOVE PUMP FLANGE
3" (To PREVENT PREMATURE PUMP BURNOUT)
STORAGE REQUIRED ABOVE WORKING LEVEL: 330 GALLONS
PROVIDE 2 FLOATS:
FLOAT NOA: PUMP ON/OFF—SJ RHOMBUS (PROVIDED WITH PUMP)
STORAGE PROVIDED:
FLOAT NO.2: ALARM ACTIVATION FLOAT—PROVIDED WITH ALARM PANEL LIBERTY LE40 SERIES PUMP .4 H.P. 115 V
INV.(IN) EL: 98.75 — PUMP ON EL: 95.79 = 2.96'
(ON SEPARATE CIRCUIT FROM PUMP SPECIFIED) WITH 2' DISCHARGE, OR EQUAL
STORAGE PROVIDED = 2.96 x 250 GAL/FT = 740.0 GALLONS
PUMP AND ACCESSORIES AVAILABLE AT:
-
CAPE COD WINWATER WORKS CO., HYANNIS, MA. (508) 862-0166
NOTE: APPROVED ALTERNATE MAY BE SUBSTITUTED.
PUMP DETAIL
24" DIA. COVERS
—4" TOP (TYP.)
8'-3-1 /2"
8'-3-1/2"
n
LET 1 OUTLET - FT - -�-i -
T-T�A
5' 31/ 3" '� �A I I I I I
BUOYANCY CALCULATIONS
F' 5' 5 1/2"
1000 GALLON MONOLITHIC PUMP CHAMBER
54-1/2' 51-1/2" — —
;REINFORCING RIB LIQUID 3" —
LEVEL \ / I \ /
3 I
BOTTOM OF UNIT EL.= 94.46, HIGH GROUNDWATER, EL.=93.9
TANK IS SET HIGHER THAN HIGH GROUNDWATER
II II
— 1J 74
CROSS SECTION A -A 4" KNOCKOUTS PLAN VIEW
(TYP.)
SPECIFICKnONS
1.) CONCRETE 4,000 PSI AFTER 28 DAYS.
SEPTIC SYSTEM UPGRADE PLAN
2.) CONSTRUCTION CONFORMS TO DEP TITLE V REGS.
PROPOSED
310 CMR SECTION 15.226.
PER ASTM C1227-93.
G
5 KENS WAY, WEST YARMOUTH, MA
3.) REINFORCEMENT APPROXIMATE WEIGHT =8,380 LBS
Prepared for: Mark Tasha, 135 Union Street, Yarmouth Port, MA 02675
4.) PROVIDE POLYMER COATING
APPROVED ALTERNATE MAY BE USED.
Engineers:
Surveyors:SCALE
DRAWN
JOB. N0.
1000 GALLON MONOLITHIC PUMP CHAMBER
Engineering Works, Inc.
KEngineering, Inc.
N.T.S.
P.T.M.
258-20
WIGGIN PRECAST CORP MODEL#1000MONTH
12 West Crossfield Road
Forestdole, MA 02644
2854 Cranberry Hwy.
E.Worehom, MA 02538
DATE
CHECKED
SHEET NO.
(508) 477-5313
(508) 273-0377
10/13/21
P.T.M.
3 Of 3