HomeMy WebLinkAboutJ5951 Dennis Yarmouth Middle School WE 2021-11-26Summary Report #26
November 29, 2021
Attn:
Job No: 5951
Job Name:Dennis Yarmouth Middle School
296 Station Ave
South Yarmouth, MA 02664
Application No.:
TESTING
INSPECTION
ENGINEERING
SW
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
November 22, 2021
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Performed structural masonry inspection for grout placement. Grout sample(s)
obtained: (4) per set, (1) set(s), (4) total. See attached.
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Performed soils compaction testing. No Samples Taken. See attached.
Julen Barruetabena picked up (10) concrete cylinders and (8) grout samples from the jobsite.
The work observed was, to the best of Arsene's knowledge, in accordance with the approved plans, specifications and applicable standards of
workmanship.
November 23, 2021
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Performed soils compaction testing. No Samples Taken. See attached.
Tony Paradis reported to Nicholas Hull with PMA at the jobsite. Performed structural steel and welding inspection in the field. See attached.
The work observed was, to the best of Arsene's, Tony's knowledge, in accordance with the approved plans, specifications and applicable standards
of workmanship.
Laboratory test results are enclosed if testing was done during the period covered by this report.
Limitations: These inspections were performed in accordance with requirements, but please note this report shall not be relied upon by others, as
acceptance or guarantee of the work. Even with diligent inspection techniques, the contractor is solely liable for defects or failures to adhere to the
code.
Reviewed by:
Enea Mushi
Project Manager
12-06-2021
Date
TESTING
INSPECTION
ENGINEERING
SW
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
Technical Contact: Bruce Tie, Engineering Manager (btie@fenaghengineering.com)
Administrative Contact: Gina Salerno (gsalerno@fenaghengineering.com)
TESTING
INSPECTION
ENGINEERING
Project No: 5951
Project Name: Dennis Yarmouth Middle School
Project Location: 296 Station Ave, South Yarmouth, MA, 02664
Fenagh Representative: Arsene Ntwali
Inspection Type: Masonry Grout Placement
Pg. 1 of 1
November 22, 2021
Time In: 13:00 Time Out: 15:00
Weather: Rain
Temperature: 48°F
Permit No. :
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Observed placement of Grout, mix design #3000, 3000 PSI at 28 days, for
the 12" and 12" CMU wall, low-lift height 2 courses. Cleanouts were used, cells are clean and acceptable. consolidated by mechanical
vibration. wall(s) at Level 1 at gridlines Building A.
Set No.Slump (in.)Mix Temp (°F)Air Temp (°F)Location Qty. of Samples
1 NA NA 50 T.1/a6 4
1 set of Grout Box(s) for a total of 4 samples
Referenced Details: 1-4WET- Fine Grout Mix
Additional Notes: Grout placed on CMU blocks in building A auditorium seats.
Plans Dated: 07/02/2021
Conformance:
The Work observed was, to the best of my knowledge, in accordance with the approved plans, specifications and applicable
standards of workmanship.
Limitations: These inspections were performed in accordance with requirements, but please note this report shall not be relied upon by others, as acceptance or
guarantee of the work. Even with diligent inspection techniques, the contractor is solely liable for defects or failures to adhere to the code. Information provided herein
has not been reviewed by supervisory staff, therefore, should be considered preliminary and subject to change, unless signed by both inspector and engineer below.
Reviewed by:
Arsene Ntwali
Inspector
11-22-2021
Date Enea Mushi
Project Manager
12-06-2021
Date
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
NYk
TESTING
INSPECTION
ENGINEERING
Soils Compaction
FET Project #: 5951
Project Name: Dennis Yarmouth Middle School TAA #: NA
Inspection Address: 296 Station Ave, South Yarmouth, MA, 02664
Fenagh Representative: Arsene Ntwali
November 22, 2021
Time In: 07:00 Time Out: 13:00
Weather: Rain
Temperature: 48°F
Permit No. :
Plans Dated: 09/23/2021
Conformance:
The Work observed was, to the best of my knowledge, in accordance with the approved plans, specifications and applicable
standards of workmanship.
Limitations:These inspections were performed in accordance with requirements, but please note this report shall not be relied upon by others, as acceptance or guarantee of the work. Evenwith diligent inspection techniques, the contractor is solely liable for defects or failures to adhere to the code. Information provided herein has not been reviewed by supervisory staff,therefore, should be considered preliminary and subject to change, unless signed by both inspector and engineer below.
Reviewed by:
Arsene Ntwali
Inspector
11-22-2021
Date Enea Mushi
Project Manager
11-29-2021
Date
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Performed soils compaction testing. Equipment used was Plate
compactor , Excavator. No samples taken.
Density Std (DS):
2498
Moisture Std (MS):
476
Specified Compaction:
95%
Soils Report prepared by:
Fenagh Engineering
Source of Fill:
Native:
General Location of Fill:
Light poles between Lot
1 and 2
Nuclear Gauge:
Humbolt HS-5001EZ 5200
calibration expiration date 02/2022
Soils Report Dated:
06-07-2021
Results Reported
to:
Mitch Miller
Equipment Observed:
Compaction: Plate compactor
Excavation: Excavator
Description of material Reference CurveID Lab Log ID Max Dry Density(pcf) Optimum Moisture
Loose glacial 1 S774 115.8 10.0
Test# Test Location
Probe
Depth (in)
Test
Elev. (ft)
Ref.
Curve
Used
Test Dry Density
(lbs/cu. ft.)
Test Moisture
(%)
Compaction
(95%)
(%)
Comments
1 Light poles 6 -3 1 111.5 7.3 96 Pass
2 Light poles 6 - 2 1 111.3 7.8 96 Pass
3 Light poles 6 -1 1 111.6 7.4 96 Pass
'DLO\3LFN8S5HSRUW
-RE1XPEHU3URMHFW1DPH
)HQDJK 5HSUHVHQWDWLYH'DWH
&\OLQGHUV
6KRWFUHWH
*URXW
0RUWDU
*URXW&XEHV
3ULVPV
37&DEOHV
)LUHSURRILQJ6DPSOHV
6RLO6DPSOHV
5HEDU6DPSOHV
6WHHO3ODWHV
2WKHU
$GGLWLRQDO&RPPHQWV
-RE6LWH6KRS %DWFK 3ODQW4XDUU\2WKHUBBBBBBBB
&XUH%R[7HPSBBBBBB+LJK/RZ7HPSBBBBBBBB2XWVLGH7HPSBBBBBB
zĂƌŵŽƵƚŚDŝĚĚůĞ^ĐŚŽŽů ϱϵϱϭ
:ƵůĞŶĂƌƌƵĞƚĂďĞŹĂ ϭϭͬϮϮͬϮϬϮϭ
■
Ͳ ϱϱ
ϭϬ
ϮďŽdžĞƐ
Ͳ
TESTING
INSPECTION
ENGINEERING
Soils Compaction
FET Project #: 5951
Project Name: Dennis Yarmouth Middle School TAA #: NA
Inspection Address: 296 Station Ave, South Yarmouth, MA, 02664
Fenagh Representative: Arsene Ntwali
November 23, 2021
Time In: 09:00 Time Out: 15:00
Weather: Sunny
Temperature: 45°F
Permit No. :
Plans Dated: 09/23/2021
Conformance:
The Work observed was, to the best of my knowledge, in accordance with the approved plans, specifications and applicable
standards of workmanship.
Limitations:These inspections were performed in accordance with requirements, but please note this report shall not be relied upon by others, as acceptance or guarantee of the work. Evenwith diligent inspection techniques, the contractor is solely liable for defects or failures to adhere to the code. Information provided herein has not been reviewed by supervisory staff,therefore, should be considered preliminary and subject to change, unless signed by both inspector and engineer below.
Reviewed by:
Arsene Ntwali
Inspector
11-23-2021
Date Enea Mushi
Project Manager
11-29-2021
Date
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
Arsene Ntwali reported to Mitch Miller with PMA at the jobsite. Performed soils compaction testing. Equipment used was Plate
compactor , Excavator. No samples taken.
Density Std (DS):
2494
Moisture Std (MS):
473
Specified Compaction:
95%
Soils Report prepared by:
Fenagh Engineering
Source of Fill:
Native:
General Location of Fill:
Light poles in lot 3 and
West side of building A
Nuclear Gauge:
Humbolt HS-5001EZ 5200
calibration expiration date
02/2022
Soils Report Dated:
06-07-2021
Results Reported
to:
Mitch Miller
Equipment Observed:
Compaction: Plate compactor
Excavation: Excavator
Description of material Reference CurveID Lab Log ID Max Dry Density(pcf) Optimum Moisture
Loose glacial 1 S774 115.8 10.0
Test# Test Location
Probe
Depth (in)
Test
Elev. (ft)
Ref.
Curve
Used
Test Dry Density
(lbs/cu. ft.)
Test Moisture
(%)
Compaction
(95%)
(%)
Comments
1 Light poles 6 -2 1 110.7 6.4 96 Pass
2 Light poles 6 -2 1 110.4 6.6 95 Pass
3 Light poles 6 -1 1 111.1 6.2 96 Pass
TESTING
INSPECTION
ENGINEERING
Project No: 5951
Project Name: Dennis Yarmouth Middle School
Project Location: 296 Station Ave, South Yarmouth, MA, 02664
Fenagh Representative: Tony Paradis
Inspection Type: Field Welding
Pg. 1 of 2
November 23, 2021
Time In: 10:00 Time Out: 18:30
Weather: Partly Cloudy
Temperature: 50°F
Permit No. :
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
Tony Paradis reported to Nicholas Hull with PMA at the jobsite. Performed structural steel and welding inspection.
Reviewed welder qualification documents for the following welders:
Welder name ID #
Not available, Requested N/A
Reviewed the following WPS(s):
WPS Number
Not available, Requested
Materials/Storage :
Processes Used:
Process Type of electrode/wire Diameter Shielding Gas
SMAW E7018 1/8 N/A
FCAW E71T-1 unknown unknown
Weldments observed consisted of:
Weld Type Weld Material
to
Weld
Material from Level Location/Piece No Remarks Ref. Details
Single-pass fillet Connection plate
Wide flange
beam
Low roof
area A
N/b2, plate 27B25 to
girder 27B7 Welding Complete RFI #246
Single-pass fillet Diagonal brace Knife plate
2 and
roof
Bldg C wind brace top
connections Welding Complete 1/E31 thru
E36
Multi-pass fillet,
Flare-bevel goove
weld
Tube steel beam Tube steel
column 1 and 2 Bldg C sunshade H/c1-
c21 Welding Complete
5/E38, D-
D/E38, F-
F/E38
TESTING
INSPECTION
ENGINEERING
Project No: 5951
Project Name: Dennis Yarmouth Middle School
Project Location: 296 Station Ave, South Yarmouth, MA, 02664
Fenagh Representative: Tony Paradis
Inspection Type: Field Welding
Pg. 2 of 2
November 23, 2021
Time In: 10:00 Time Out: 18:30
Weather: Partly Cloudy
Temperature: 50°F
Permit No. :
Plans Dated: 03/01/2021
Conformance:
The Work observed was, to the best of my knowledge, in accordance with the approved plans, specifications and applicable
standards of workmanship.
Limitations:These inspections were performed in accordance with requirements, but please note this report shall not be relied upon by others, as acceptance or guarantee of the work. Evenwith diligent inspection techniques, the contractor is solely liable for defects or failures to adhere to the code. Information provided herein has not been reviewed by supervisory staff,therefore, should be considered preliminary and subject to change, unless signed by both inspector and engineer below.
Reviewed by:
Tony Paradis
Inspector
11-23-2021
Date Enea Mushi
Project Manager
11-29-2021
Date
12 Tech Circle, Natick, MA 01760 | (617) 938-3774 office | (617) 344-0478 fax
Southern California
New England
Arizona
Texas
New York
Tony Paradis reported to Nicholas Hull with PMA at the jobsite. Observed installation of 3/4” A325 TC Snug-Tight high strength bolts
on 1 at gridlines H/c1-c21 bldg C. Visually Verified TC Bolts were Fully Tensioned.
Additional Notes: VT ok for above mentioned completed welds. Proper WPS's and WPQRs for Stellar Steel Erectors were not
available for review. Nicholas with PMA will be forwarding them when he receives them.rnObserved sunshade bolted connections
per 3/E38 on Level 1 at above mentioned location. Level 2 has yet to be bolted.rnObserved Cold formed metal framing parapet on
bldg C. 18ga studs and top and btm plates, 1 screw through each flange, 8 shot pins connecting studs to each vertical support
plate.
Referenced Details: RFI #246, E31 thru E38
EZ/η ĂƚĞ >ŽĐĂƚŝŽŶ /ŶƐƉĞĐƚŽƌ /ƐƐƵĞZ&/ͬ^ƵďŵŝƚƚĂůEŽ͘ZĞƐŽůǀĞĚ͍;zͬEͿ ^ƵďͬŽŶƚƌĂĐƚŽƌ ĂƚĞZĞƐŽůǀĞĚ ŽŵŵĞŶƚϭ ϳͬϮϭͬϮϬϮϭ tĂůů͗ͬĚϯ ƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϭϬͬϮϬϮϭ^Ğƚϭсϭ͕ϴϲϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϴͬϯϭͬϮϬϮϭ^ĞƚϭсϮ͕ϴϬϬƉƐŝ^ĞƚϭсϮ͕ϵϬϬƉƐŝ^Ğƚϭсϯ͕ϰϴϬƉƐŝϮϴĚĂLJĂǀĞƌĂŐĞсϯ͕ϬϲϬƉƐŝϮ ϳͬϮϴͬϮϬϮϭ &ŽŽƚŝŶŐ͗ϭϲͬ ƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͗>Ăď>ŽŐEŽ͗͘ϭϱϱϭϵ;ϮϳϰϰͲϮϳϰϱͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϮϴĚĂLJďƌĞĂŬϬϴͬϯϭͬϮϬϮϭ^Ğƚϭсϯ͕ϯϱϬƉƐŝ^Ğƚϭсϯ͕ϱϬϬƉƐŝ^Ğƚϭсϯ͕ϲϮϬƉƐŝϱϲĚĂLJďƌĞĂŬϬϵͬϮϮͬϮϬϮϭ^ĞƚϭсƉƐŝϯ ϳͬϯϬͬϮϬϮϭ&ŽŽƚŝŶŐƐ^Ğƚηϭ͗ŽůƵŵŶůŝŶĞͬZŽǁ͗͘ϯͬĐϭϭϲ^ĞƚηϮŽůƵŵŵůŝŶĞͬZŽǁĐϱͬ,ƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϮϴĚĂLJďƌĞĂŬϬϴͬϮϳͬϮϬϮϭ^Ğƚϭсϯ͕ϬϳϬƉƐŝ^Ğƚϭсϯ͕ϯϯϬƉƐŝ^Ğƚϭсϯ͕ϰϯϬƉƐŝ^ĞƚϮсϯ͕ϯϯϬƉƐŝ^ĞƚϮсϯ͕ϱϮϬƉƐŝ^ĞƚϮсϯ͕ϱϴϬƉƐŝϱϲĚĂLJďƌĞĂŬϬϵͬϮϰͬϮϬϮϭ^Ğƚηϭсϯ͕ϳϮϬƉƐŝ^ĞƚηϮсϯ͕ϲϳϬƉƐŝϰ ϴͬϯͬϮϬϮϭ&ŽŽƚŝŶŐƐ͗ůĞǀĂƚŽƌƉŝƚĨŽƵŶĚĂƚŝŽŶƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϭϬͬϮϬϮϭ^ĞƚϭсϮ͕ϲϭϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϴͬϯϭͬϮϬϮϭ^Ğƚϭсϯ͕ϭϳϬƉƐŝϱϲĚĂLJďƌĞĂŬϵͬϮϴͬϮϬϮϭ^Ğƚϭсϯ͕ϯϯϬƉƐŝ^Ğƚϭсϯ͕ϰϵϬƉƐŝ^Ğƚϭсϯ͕ϳϬϬƉƐŝϱϲĚĂLJĂǀĞƌĂŐĞƐĞƚϭсϯ͕ϱϭϬƉƐŝϱ ϴͬϲͬϮϬϮϭ>ĞǀĞůϭtĂůůĂƚƵŝůĚŝŶŐĂŶĚͲͬĐϮƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϭϯͬϮϬϮϭ^ĞƚϭсϮ͕ϵϴϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϯͬϮϬϮϭ^Ğƚϭсϯ͕ϭϳϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϴͬϮϬϮϭ^Ğƚϭсϯ͕ϮϯϬƉƐŝ^Ğƚϭсϯ͕ϰϬϬƉƐŝϲ ϴͬϲͬϮϬϮϭ>ĞǀĞůϭtĂůůĂƚƵŝůĚŝŶŐĂŶĚͲ:͘ϳͬďϮϱƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϭϯͬϮϬϮϭ^ĞƚϮсϮ͕ϯϵϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϯͬϮϬϮϭ^ĞƚϮсϯϯϴϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϴͬϮϬϮϭ^ĞƚϭсƉƐŝϳ ϴͬϭϯͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚƵŝůĚŝŶŐ͗W͘ϭͬďϯϯƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϭϳĚĂLJďƌĞĂŬϬϴͬϯϬͬϮϬϮϭ^Ğƚϭсϯ͕ϬϵϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϭϬͬϮϬϮϭ^Ğƚϭсϯ͕ϰϲϬƉƐŝ^Ğƚϭсϯ͕ϱϭϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϬϴͬϮϬϮϭ^ĞƚϭсƉƐŝ^ĞƚϭсƉƐŝϴ ϴͬϭϯͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚƵŝůĚŝŶŐ͗:͘ϯͬďϮϰƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱйE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϮϬͬϮϬϮϭ^ĞƚϭсϮ͕ϯϮϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϭϬͬϮϬϮϭ^ĞƚϭсϮ͕ϴϰϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϬϴͬϮϬϮϭ^ĞƚϭсƉƐŝ^ĞƚϭсƉƐŝ
ϵ ϴͬϮϬͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚ&ŽƵŶĚĂƚŝŽŶ͗tĂůů͗,ͬĐϱƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͗>Ăď>ŽŐEŽ͗͘ϭϱϴϲϬ;ϯϬϮϰͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϮϳͬϮϬϮϭ^ĞƚϭсϮ͕ϴϭϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϭϳͬϮϬϮϭ^Ğƚϭсϯ͕ϰϰϬƉƐŝ^Ğƚϭсϯ͕ϱϬϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϭϱͬϮϬϮϭ^Ğƚϭсϯ͕ϵϮϬƉƐŝ^Ğƚϭсϰ͕ϬϮϬƉƐŝϭϬ ϵͬϯͬϮϬϮϭ >ĞǀĞůϭtĂůů͖hͬĂϱ ƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͖>Ăď>ŽŐEŽ͗͘ϭϲϬϲϳ;ϯϭϮϯͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϵͬϭϬͬϮϬϮϭ^ĞƚϭсϮ͕ϬϱϬƉƐŝϮϴĚĂLJďƌĞĂŬϭϬͬϬϭͬϮϬϮϭ^Ğƚϭсϯ͕ϭϬϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϮϵͬϮϬϮϭ^Ğƚϭсϯ͕ϱϭϬƉƐŝ^Ğƚϭсϯ͕ϲϯϬƉƐŝ^Ğƚϭсϯ͕ϲϲϬƉƐŝϭϭ ϵͬϵͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐ͗D͘ϱͬďϭϳƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͖>Ăď>ŽŐEŽ͗͘ϭϲϭϯϮ;ϯϭϳϱͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϵͬϭϲͬϮϬϮϭ^ĞƚϭсϮ͕ϰϬϬƉƐŝϮϴĚĂLJďƌĞĂŬϭϬͬϬϳͬϮϬϮϭ^Ğƚϭсϯ͕ϰϴϬƉƐŝ^Ğƚϭсϯ͕ϰϵϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϭͬϬϰͬϮϬϮϭ^Ğƚϭсϰ͕ϬϱϬƉƐŝ^Ğƚϭсϰ͕ϮϰϬƉƐŝϭϮ ϵͬϭϬͬϮϬϮϭ >ĞǀĞůϭ&ŽŽƚŝŶŐ͗>͘ϵͬďϮ ƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͖>Ăď>ŽŐEŽ͗͘ϭϲϭϯϯ;ϯϭϳϲͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϵͬϭϳͬϮϬϮϭ^ĞƚϭсϮ͕ϯϯϬƉƐŝϮϴĚĂLJďƌĞĂŬϭϬͬϬϴͬϮϬϮϭ^Ğƚϭсϯ͕ϰϱϬƉƐŝ^Ğƚϭсϯ͕ϰϱϬƉƐŝ^Ğƚϭсϯ͕ϰϵϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϭͬϬϱͬϮϬϮϭ^Ğƚϭсϰ͕ϬϲϬƉƐŝϭϯ ϴͬϭϯͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚƵŝůĚŝŶŐ͗^ĞƚηϭW͘ϭͬďϯϯ^ĞƚηϮ:͘ϯͬďϮϰƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͖>Ăď>ŽŐEŽ͗͘ϭϱϳϰϱ;ϮϵϰϱͲϮϵϰϲͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϮϬͬϮϬϮϭ^ĞƚϮсϮ͕ϯϮϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϭϬͬϮϬϮϭ^Ğƚϭсϯ͕ϰϲϬƉƐŝ^Ğƚϭсϯ͕ϱϭϬƉƐŝ^ĞƚϮсϮ͕ϴϰϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϬϴͬϮϬϮϭ^Ğƚϭсϯ͕ϳϲϬƉƐŝ^Ğƚϭсϯ͕ϴϱϬƉƐŝ^ĞƚϮсϯ͕ϮϲϬƉƐŝ^ĞƚϮсϯ͕ϬϯϬƉƐŝ^ĞƚϮсϯ͕ϭϱϬƉƐŝ^Ğƚ Ϯсϯ͕ϮϲϬ ƉƐŝϭϰ ϴͬϭϳͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚƵŝůĚŝŶŐ͗^͘ϭͬďϮϳƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϯϱϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϯϱϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϰƚŽϲŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰ͘ϱйƚŽϳ͘ϱй͖>Ăď>ŽŐEŽ͗͘ϭϱϳϰϱ;ϮϵϰϱͲϮϵϰϲͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϴͬϮϰͬϮϬϮϭ^ĞƚϭсϮ͕ϱϭϬƉƐŝϮϴĚĂLJďƌĞĂŬϬϵͬϭϰͬϮϬϮϭ^Ğƚϭсϯ͕ϮϴϬƉƐŝ^Ğƚϭсϯ͕ϰϯϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϬͬϭϮͬϮϬϮϭ^Ğƚϭсϰ͕ϬϳϬƉƐŝ^Ğƚϭсϰ͕ϭϭϬƉƐŝϭϱ ϵͬϮϯͬϮϬϮϭ>ĞǀĞůϭ&ŽŽƚŝŶŐƐĂƚƵŝůĚŝŶŐ͗WϳͬĂϭϴƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϱϬϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϱ͕ϬϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϱƚŽϴŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰйƚŽϳй͖>Ăď>ŽŐEŽ͗͘ϭϲϮϴϴ;ϯϮϲϰͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϬϵͬϯϬͬϮϬϮϭ^Ğƚϭсϯ͕ϱϭϬƉƐŝϮϴĚĂLJďƌĞĂŬϭϬͬϮϭͬϮϬϮϭ^Ğƚϭсϰ͕ϰϳϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϭͬϭϴͬϮϬϮϭ^Ğƚϭсϰ͕ϴϴϬƉƐŝ^Ğƚϭсϱ͕ϭϮϬƉƐŝ^Ğƚϭсϱ͕ϮϭϬƉƐŝϭϲ ϭϭͬϮͬϮϬϮϭ>ĞǀĞůϭ^ůĂďĂƚƵŝůĚŝŶŐ͗>ŝŶĞͲϭ͕ZŽǁϭͲďĞĨŽƌĞϭϲŶĞĂDƵƐŚŝ DĞĂƐƵƌĞĚ&ůŽŽƌ&ůĂƚŶĞƐƐ͕>ĞǀĞůŶĞƐƐ;ϯϰ͘ϳĂŶĚϭϴ͘ϯͿĚŝĚŶŽƚŵĞĞƚŽǀĞƌĂůůƉƌŽũĞĐƚƌĞƋƵŝƌĞŵĞŶƚ;ϯϱĂŶĚϮϱͿ E DĂƌŐƵĞƌŝƚĞ KZƚŽĚǀŝƐĞ
ϭϳ ϵͬϮϳͬϮϬϮϭ>ĞǀĞůϭtĂůůĂƚYͲW͘ϳͬĂϭϴ͕ĂϭϴͲϮϰͬtϭϳ͗^ĂŵƉůĞĚΛE͘ϰͬďϱƌƐĞŶĞEƚǁĂůŝ>ŽǁďƌĞĂŬ͗DŝdžĞƐŝŶŐϱϬϬϬ͕ĚĞƐŝŐŶƐƚƌĞŶŐƚŚŽĨϱ͕ϬϬϬƉƐŝĂƚϮϴĚĂLJƐ͕ƐƉĞĐŝĨŝĞĚƐůƵŵƉĨƌŽŵϱƚŽϴŝŶ͕͘ƐƉĞĐŝĨŝĞĚĂŝƌĐŽŶƚĞŶƚĨƌŽŵϰйƚŽϳй͖>Ăď>ŽŐEŽ͗͘ϭϲϯϯϵ;ϯϯϮϯͿE DĂƌŐƵĞƌŝƚĞKZƚŽĚǀŝƐĞϳĚĂLJďƌĞĂŬϭϬͬϬϰͬϮϬϮϭ^Ğƚϭсϯ͕ϱϭϬƉƐŝϮϴĚĂLJďƌĞĂŬϭϬͬϮϱͬϮϬϮϭ^Ğƚϭсϰ͕ϭϳϬƉƐŝϱϲĚĂLJďƌĞĂŬϭϭͬϮϮͬϮϬϮϭ^Ğƚϭсϰ͕ϳϬϬƉƐŝϵϬĚĂLJďƌĞĂŬϭϮͬϮϲͬϮϬϮϭ^ĞƚϭсƉƐŝ^ĞƚϭсƉƐŝ^ƚĂƚƵƐ͗tŽƌŬͲŝŶͲWƌŽŐƌĞƐƐ>ĞŐĞŶĚ͗^ƚĂƚƵƐ͗ůŽƐĞĚ^ƚĂƚƵƐ͗KƉĞŶ
TESTING
INSPECTION
ENGINEERING
Field Number: 6 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/23/2021
Client: PMA
Date of Sampling: 09/23/2021 Lab Log No.: 16288 (3264)
Reviewed by: CJ Martens
11/23/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 1
Information provided by Field Technician
Mix #: 5000D Supplier: Cape Cod Ready Mix Contractor: Marguerite
Set: 1 of 1 Truck #: 72
Design Strength (psi): 5,000 @28
days Ticket#: 31854
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Footings
Location: Onsite
Location for overall pour: Level 1 Footings at Building A and B
Location when sampled: P7/a18
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 70 50-90 Slump or Spread (in.): 8.0 5-8 Unit Wt (#cu ft): 143.6 143.4
Air Temperature (ºF): 72 >40 Air Content (%): 6.1 4-7 Time Sampled: 7:39 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 7:17 AM Time in Truck: 22 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 09/24/2021 Technician that received: Max Nabulsi
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 3 09/26/2021 Max Nabulsi 4.00 8.00 12.57 Lab 34,951 2,780 psi Type 2
B 7 09/30/2021 Henry Soares 4.00 8.00 12.57 Lab 44,144 3,510 psi Type 5
C 28 10/21/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Lab 56,247 4,470 psi Type 2
D 56 11/18/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Lab 65,071 5,180 psi Type 2
E 56 11/18/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Lab 61,353 4,880 psi Type 2
F 61 11/23/2021 Max Nabulsi 4.00 8.00 12.57 Lab 65,519 5,210 psi Type 2
FAILS TO MEET DESIGN STRENGTH
61 Day Avg.:5,210 psi
Remarks: Low 28-Day indication compression test result. Specimens D-F held for 56 days, E was low, F to be held for 90 days,
Client requested break sample E on 11.23.21 at 61 days.
TESTING
INSPECTION
ENGINEERING
Field Number: 4 Masonry Grout Compression Test
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/23/2021
Client: PMA
Date of Sampling: 10/19/2021 Lab Log No.: 16691 (3463)
Reviewed by: CJ Martens
11/23/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C1019, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 1
Information provided by Field Technician
Mix #: 3000 Supplier: Spec. Mix Contractor:
Set: 1 of 1 Truck #: N/A
Design Strength (psi): 3,000 @28
days Ticket#: N/A
Sample Material/Shape: ASTM C1019 Compressive Testing of Masonry Grout
(Grout Box)Type of Structure: Base Plate
Location: Onsite
Location for overall pour:
Location when sampled: Building C
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 50-90 Slump (in.): NA N/A Unit Wt (#cu ft): N/A
Air Temperature (ºF): 67 >40 Air Content (%): N/A N/A Time Sampled:
Aggregate Size (in): N/A N/A Batch Time: Time in Truck: <90 Mins <90 Mins
Information supplied by Laboratory Technician
Date Received: 10/26/2021 Technician that received: Henry Soares
Test #Age of
Test (Days)Date Technician
Dimensions (inch) X-section Total Load
(lbs)Strength (psi)Width Width Height Area (in²)
A 7 10/26/2021 Henry Soares 3.37 3.41 6.87 11.49 23,642 2,060 psi
B 28 11/16/2021 Luis Soto Soldevilla 3.49 3.49 6.75 12.18 43,870 3,600 psi
C 28 11/16/2021 Luis Soto Soldevilla 3.40 3.40 6.88 11.56 45,137 3,900 psi
D 28 11/16/2021 Luis Soto Soldevilla 3.35 3.40 6.70 11.39 41,427 3,640 psi
MEETS DESIGN STRENGTH
28 Day Avg.:3710
Remarks: Received Sample Condition: Acceptable and/or Satisfactory
TESTING
INSPECTION
ENGINEERING
Field Number: 4 Masonry Grout Compression Test
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/23/2021
Client: PMA
Date of Sampling: 11/09/2021 Lab Log No.: 17011
Reviewed by: CJ Martens
11/23/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C1019, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 1
Information provided by Field Technician
Mix #: 3000 Supplier: Spec. Mix Contractor:
Set: 1 of 1 Truck #:
Design Strength (psi): 3,000 @28
days Ticket#:
Sample Material/Shape: ASTM C1019 Compressive Testing of Masonry Grout
(Grout Box)Type of Structure: Base Plate
Location: Onsite
Location for overall pour:
Location when sampled: Building B and A
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 50-90 Slump (in.): NA N/A Unit Wt (#cu ft): N/A
Air Temperature (ºF): 59 >40 Air Content (%): N/A Time Sampled:
Aggregate Size (in): N/A Batch Time: Time in Truck: <90 Mins <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #Age of
Test (Days)Date Technician
Dimensions (inch) X-section Total Load
(lbs)Strength (psi)Width Width Height Area (in²)
A 7 11/16/2021 Luis Soto Soldevilla 3.38 3.38 6.72 11.42 44,239 3,870 psi
B 28 12/07/2021
C 28 12/07/2021
D 28 12/07/2021
7 Day Avg.:3870
Remarks: Received Sample Condition: Acceptable and/or Satisfactory
TESTING
INSPECTION
ENGINEERING
Field Number: 5 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 09/27/2021 Lab Log No.: 16339 (3323)
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 1
Information provided by Field Technician
Mix #: 5000D Supplier: Cape Cod Mix Contractor: Marguerite
Set: 1 of 1 Truck #: 68
Design Strength (psi): 5,000 @28
days Ticket#: 31894
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Wall
Location: Onsite
Location for overall pour: Level 1 Wall at Q-P.7/a18, a18-24/W
Location when sampled: N.4/b5
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 6.5 5-8 Unit Wt (#cu ft): 143.7 143.0
Air Temperature (ºF): 75 >40 Air Content (%): 6.7 4-7 Time Sampled: 8:13 AM
Aggregate Size (in): 3/4 N/A Batch Time: 7:23 AM Time in Truck: 50 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 10/01/2021 Technician that received: Henry Soares
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 10/04/2021 Henry Soares 4.00 8.00 12.57 Lab 44,058 3,510 psi Type 5
B 28 10/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Lab 52,427 4,170 psi Type 2
C 56 11/22/2021 Kevin Noel 4.00 8.00 12.57 Lab 59,038 4,700 psi Type 2
D 90 12/26/2021 4.00 8.00 12.57 Lab
E 90 12/26/2021 4.00 8.00 12.57 Lab
FAILS TO MEET DESIGN STRENGTH
56 Day Avg.:4,700 psi
Remarks: Low 28 & 56-Day indication compression test results. Specimens D & E will be held for 90-Days.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 1 of 6 Truck #: 55
Design Strength (psi): 4,000 @28
days Ticket#: 22279
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: E/c4
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 9.0 5-9 Unit Wt (#cu ft): 149.8 149.3
Air Temperature (ºF): 53 >40 Air Content (%): 1.5 0-3 Time Sampled: 7:25 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 6:33 AM Time in Truck: 52 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 51,389 4,090 psi Type 5
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:4,090 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 2 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 2 of 6 Truck #: 72
Design Strength (psi): 4,000 @28
days Ticket#: 32449
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: H/c2
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 8.0 5-9 Unit Wt (#cu ft): 150.1 149.3
Air Temperature (ºF): 53 >40 Air Content (%): 2.0 0-3 Time Sampled: 9:18 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 8:44 AM Time in Truck: 34 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 44,388 3,530 psi Type 2
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:3,530 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 3 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 3 of 6 Truck #: 57
Design Strength (psi): 4,000 @28
days Ticket#: 32452
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: D.5/c6
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 70 50-90 Slump or Spread (in.): 9.0 5-9 Unit Wt (#cu ft): 150.7 149.3
Air Temperature (ºF): 54 >40 Air Content (%): 1.7 0-3 Time Sampled: 10:26 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 9:39 AM Time in Truck: 47 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 38,656 3,080 psi Type 2
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:3,080 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 4 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 4 of 6 Truck #: 72
Design Strength (psi): 4,000 @28
days Ticket#: 32456
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: G/c12
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 70 50-90 Slump or Spread (in.): 8.75 5-9 Unit Wt (#cu ft): 149.5 149.3
Air Temperature (ºF): 55 >40 Air Content (%): 2.3 0-3 Time Sampled: 11:01 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 10:24 AM Time in Truck: 37 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 46,171 3,670 psi Type 2
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:3,670 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 5 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 5 of 6 Truck #: 64
Design Strength (psi): 4,000 @28
days Ticket#: 32458
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: F/c116
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 7.5 5-9 Unit Wt (#cu ft): 150.1 149.3
Air Temperature (ºF): 54 >40 Air Content (%): 1.6 0-3 Time Sampled: 11:33 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 10:50 AM Time in Truck: 43 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 36,210 2,880 psi Type 2
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:2,880 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/24/2021
Client: PMA
Date of Sampling: 11/08/2021 Lab Log No.: 16995
Reviewed by: CJ Martens
11/24/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 6 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 6 of 6 Truck #: 83
Design Strength (psi): 4,000 @28
days Ticket#: 32463
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building C
Location when sampled: H/c19
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 7.0 5-9 Unit Wt (#cu ft): 149.6 149.3
Air Temperature (ºF): 55 >40 Air Content (%): 1.2 0-3 Time Sampled: 1:00 PM
Aggregate Size (in): 3/4 3/4 Batch Time: 11:50 AM Time in Truck: 70 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/15/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/15/2021 4.00 8.00 12.57 Fld 36,940 2,940 psi Type 2
B 28 12/06/2021 4.00 8.00 12.57 Fld
C 28 12/06/2021 4.00 8.00 12.57 Fld
D 28 12/06/2021 4.00 8.00 12.57 Fld
E H H 4.00 8.00 12.57 Fld
7 Day Avg.:2,940 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 1 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 1 of 6 Truck #: 56
Design Strength (psi): 4,000 @28
days Ticket#: 32278
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: A/d4
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 68 50-90 Slump or Spread (in.): 6.5 6-10 Unit Wt (#cu ft): 149.7 149.3
Air Temperature (ºF): 51 >40 Air Content (%): 1.5 0-3 Time Sampled: 7:25 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 6:41 AM Time in Truck: 44 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 45,807 3,640 psi Type 5
B 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 67,425 5,360 psi Type 2
C 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 67,688 5,380 psi Type 2
D 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 65,351 5,200 psi Type 2
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:5,310 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 2 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 2 of 6 Truck #: 59
Design Strength (psi): 4,000 @28
days Ticket#: 32282
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: C/d4
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 67 50-90 Slump or Spread (in.): 7.0 6-10 Unit Wt (#cu ft): 150.2 149.3
Air Temperature (ºF): 51 >40 Air Content (%): 1.3 0-3 Time Sampled: 8:10 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 7:37 AM Time in Truck: 33 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 51,363 4,090 psi Type 2
B 28 11/25/2021 4.00 8.00 12.57 Fld 72,073 5,730 psi Type 2
C 28 11/25/2021 4.00 8.00 12.57 Fld 71,366 5,680 psi Type 2
D 28 11/25/2021 4.00 8.00 12.57 Fld 71,336 5,680 psi Type 2
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:5,700 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 3 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 3 of 6 Truck #: 65
Design Strength (psi): 4,000 @28
days Ticket#: 32286
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: B/d15
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 70 50-90 Slump or Spread (in.): 7.5 6-10 Unit Wt (#cu ft): 149.5 149.3
Air Temperature (ºF): 51 >40 Air Content (%): 1.7 0-3 Time Sampled: 8:42 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 8:15 AM Time in Truck: 27 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 47,591 3,790 psi Type 2
B 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 67,448 5,370 psi Type 2
C 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 70,062 5,570 psi Type 2
D 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 64,969 5,170 psi Type 2
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:5,370 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 4 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 4 of 6 Truck #: 83
Design Strength (psi): 4,000 @28
days Ticket#: 32290
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: D/d15
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 69 50-90 Slump or Spread (in.): 8.5 6-10 Unit Wt (#cu ft): 149.9 149.3
Air Temperature (ºF): 55 >40 Air Content (%): 1.8 0-3 Time Sampled: 9:30 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 9:04 AM Time in Truck: 26 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 43,950 3,500 psi Type 2
B 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 58,998 4,690 psi Type 3
C 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 56,488 4,490 psi Type 3
D 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 58,600 4,660 psi Type 3
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:4,610 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 5 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 5 of 6 Truck #: 68
Design Strength (psi): 4,000 @28
days Ticket#: 902718
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: B/d21
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 71 50-90 Slump or Spread (in.): 8.0 6-10 Unit Wt (#cu ft): 150.6 149.3
Air Temperature (ºF): 56 >40 Air Content (%): 1.4 0-3 Time Sampled: 10:30 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 9:42 AM Time in Truck: 48 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 50,257 4,000 psi Type 2
B 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 72,484 5,770 psi Type 3
C 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 72,838 5,790 psi Type 3
D 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 71,862 5,720 psi Type 3
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:5,760 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.
TESTING
INSPECTION
ENGINEERING
Field Number: 30 Laboratory Compression Test (4x8)
Project Name: Dennis Yarmouth Middle School Permit No.:
Project No.:5951 Sampled by: Arsene Ntwali Report Date: 11/25/2021
Client: PMA
Date of Sampling: 10/28/2021 Lab Log No.: 16789
Reviewed by: Daniel Minawi
11/25/2021
Date
ASTM Standards Used: Unless noted, material was sampled and tested in accordance with ASTM C172, C31, C143, C231, C470, C511, C1077,
C1231,C1064, C138 and E4. Compressive strength tests per ASTM C39.
Testing was performed by qualifed personnel in accordance with generally accepted industry practice, material testing consultants procedures and the above reference standards. This report is
applicable only to the items listed herein. The test performed and in this report are not intended to be considered as any guarantee or warranty of suitability for service or fitness of use of itemstested and it should not be relied on as such. The report has been prepared for the exclusive use of the client and any partial or whole reproduction without the consent of the client is prohibited.Pg. 6 of 6
Information provided by Field Technician
Mix #: 4000 Supplier: Cape Cod Ready Mix, Inc. Contractor: Silverback
Set: 6 of 6 Truck #: 62
Design Strength (psi): 4,000 @28
days Ticket#: 32296
Sample Material/Shape: ASTM C39 Compressive Strength of Cylindrical
Concrete Specimens (4x8)Type of Structure: Slab on Metal Deck
Location: Onsite
Location for overall pour: Level 2 Slab on Metal Deck at Building D
Location when sampled: C/d23
Concrete Quality Actual Req'ment Actual Req'ment Actual Req'ment
Mix Temperature (ºF): 71 50-90 Slump or Spread (in.): 8.0 6-10 Unit Wt (#cu ft): 150.0 149.3
Air Temperature (ºF): 55 >40 Air Content (%): 2.0 0-3 Time Sampled: 11:27 AM
Aggregate Size (in): 3/4 3/4 Batch Time: 10:27 AM Time in Truck: 60 minutes <90 Mins
Information supplied by Laboratory Technician
Date Received: 11/02/2021 Technician that received: WC
Test #
Age of
Test
(Days)
Date Technician Diameter Length Area (in²) Cure Loc
Ultimate Load
(lbs)
Compressive
Strength (psi)
Type of
Fracture
A 7 11/04/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 51,227 4,080 psi Type 2
B 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 70,045 5,570 psi Type 2
C 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 72,068 5,730 psi Type 2
D 28 11/25/2021 Luis Soto Soldevilla 4.00 8.00 12.57 Fld 73,046 5,810 psi Type 2
E H H 4.00 8.00 12.57 Fld
MEETS DESIGN STRENGTH
28 Day Avg.:5,700 psi
Remarks: Received Sample Condition: Acceptable and/or Satisfactory.