HomeMy WebLinkAboutSand Dollar COMlong roof ltbs 8 and 3.5-wall 6COMcheck Software Version 4.1.4.3
Envelope Compliance Certificate
Project Title:
90.1 (2016) Standard
Project Type:New Construction
Vertical Glazing / Wall Area:0%
Location:West Yarmouth, Massachusetts
Climate Zone:5a
Construction Site:
Owner/Agent:
Sand Dollar
West Yarmouth, MA
Designer/Contractor:
Project Information
Energy Code:
Performance Sim. Specs:EnergyPlus 8.1.0.009 (EPW: USA_RI_Providence-
T.F.Green.State.AP.725070_TMY3.epw)
Building Area Floor Area
1-Workshop : Nonresidential 7047
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Floor 1: Slab-On-Grade:Unheated, Vertical 4 ft., [Bldg. Use 1 -
Workshop] (d)
380 ---10.0 0.480 0.520
Roof 1: Other Metal Building Roof, [Bldg. Use 1 - Workshop] (b)7445 ------0.030 0.037
EAST
Exterior Wall 1: Other Metal Building Wall, [Bldg. Use 1 - Workshop] (b)6935 ------0.147 0.050
Window 2: Metal Frame:Fixed, Perf. Specs.: Product ID www.expi,
SHGC 0.32, VT 0.05, [Bldg. Use 1 - Workshop] (c)
32 ------0.520 0.380
Door 4: Insulated Metal, Swinging, [Bldg. Use 1 - Workshop]84 ------0.498 0.370
Door 5: Insulated Metal, Non-Swinging, [Bldg. Use 1 - Workshop]2276 ------0.038 0.310
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)'Other' components require supporting documentation for proposed U-factors.
(c)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
(d)Slab-On-Grade proposed and budget U-factors shown in table are F-factors.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 90.1 (2016) Standard requirements in COMcheck Version 4.1.4.3 and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Envelope PASSES: Design 1% better than code
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
111 ofPage
Name - Title Signature Date
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
112 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version 4.1.4.3
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 90.1 (2016) Standard
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
4.2.2,
5.4.3.1.1,
5.7
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
4.2.2,
8.4.1.1,
8.4.1.2,
8.7
[PR6]2
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the electrical systems
and equipment and document where
exceptions are claimed. Feeder
connectors sized in accordance with
approved plans and branch circuits
sized for maximum drop of 3%.
Complies
Does Not
Not Observable
Not Applicable
5.5.4.2.3
[PR7]2
In buildings > 2,500 ft2, any enclosed
spaces directly under a roof with
ceiling heights > 15 ft. and used as an
office, lobby, atrium, concourse,
corridor, storage (including
nonrefrigerated warehouse),
gymnasium, fitness/exercise area,
playing area, gymnasium seating
area, convention exhibit/event space,
courtroom, automotive service, fire
station engine room, manufacturing
corridor/transition and bay areas,
retail, library reading and stack areas,
distribution/sorting area,
transportation baggage and seating
areas, or workshop, the following
requirements apply: The daylight zone
under skylights is >= half the floor
area and (a) the skylight area to
daylight zone is >= 3 percent with a
skylight VT >= 0.40 or (b) the
minimum skylight effective aperture
>= 1 percent. The skylights have a
measured haze value > 90 percent.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
113 ofPage
Section
#
& Req.ID
Footing / Foundation
Inspection
Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
4.2.4
[FO1]2
Installed below-grade wall
insulation type and R-value
consistent with insulation
specifications reported in plans
and COMcheck reports.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
4.2.4
[FO3]2
Installed slab-on-grade insulation
type and R-value consistent with
insulation specifications reported
in plans and COMcheck reports.
R-_____
Unheated
Heated
R-_____
Unheated
Heated
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2
[FO4]2
Slab edge insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
5.5.3.5
[FO5]2
Slab edge insulation
depth/length.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.7
[FO6]1
Exterior insulation protected
against damage, sunlight,
moisture, wind, landscaping and
equipment maintenance
activities.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.7.3
[FO7]1
Insulation in contact with the
ground has <=0.3% water
absorption rate per ASTM C272.
Complies
Does Not
Not Observable
Not Applicable
6.4.4.1.5
[FO11]3
Bottom surface of floor structures
incorporating radiant heating
insulated to >=R-3.5.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
114 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
5.4.3.2
[FR1]3
Factory-built and site-assembled
fenestration and doors are
labeled or certified as meeting air
leakage requirements.
Complies
Does Not
Not Observable
Not Applicable
5.4.3.4
[FR4]3
Vestibules are installed where
building entrances separate
conditioned space from the
exterior, and meet exterior
envelope requirements. Doors
have self-closing devices, and are
>=7 ft apart (>= 16 ft apart for
adjoinging floor area >= 40000
sq.ft.). Vestibule floor area <=7
50 sq.ft. or 2 percent of the
adjoining conditioned floor area.
Complies
Does Not
Not Observable
Not Applicable
5.5.4.3a
[FR8]1
Vertical fenestration U-Factor.U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.3b
[FR9]1
Skylight fenestration U-Factor.U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.4.1
[FR10]1
Vertical fenestration SHGC value.SHGC:_____SHGC:_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.5.4.4.2
[FR11]1
Skylight SHGC value.SHGC:_____SHGC:_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.2.1,
5.8.2.3,
5.8.2.4,
5.8.2.5
[FR12]2
Fenestration products rated (U-
factor, SHGC, and VT) in
accordance with NFRC or energy
code defaults are used.
Complies
Does Not
Not Observable
Not Applicable
5.8.2.2
[FR13]1
Fenestration and door products
are labeled, or a signed and
dated certificate listing the U-
factor, SHGC, VT, and air leakage
rate has been provided by the
manufacturer.
Complies
Does Not
Not Observable
Not Applicable
5.5.3.6
[FR14]2
U-factor of opaque doors
associated with the building
thermal envelope meets
requirements.
U-_____
Swinging
Nonswinging
U-_____
Swinging
Nonswinging
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.4.3.1
[FR15]1
Continuous air barrier is
wrapped, sealed, caulked,
gasketed, and/or taped in an
approved manner, except in
semiheated spaces in climate
zones 1-6.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
115 ofPage
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
116 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
8.4.2
[EL10]2
At least 50% of all 125 volt 15- and
20-Amp receptacles are controlled by
an automatic control device.
Complies
Does Not
Not Observable
Not Applicable
8.4.3
[EL11]2
New buildings have electrical energy
use measurement devices installed.
Where tenant spaces exist, each
tenant is monitored separately. In
buildings with a digital control system
the energy use is transmitted to to
control system and displayed
graphically.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
117 ofPage
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
4.2.4
[IN2]1
Installed roof insulation type and
R-value consistent with insulation
specifications reported in plans
and COMcheck reports. For some
ceiling systems, verification may
need to occur during Framing
Inspection.
R-_____
Above deck
Metal
Attic
R-_____
Above deck
Metal
Attic
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2,
5.8.1.3
[IN3]1
Roof insulation installed per
manufacturer’s instructions.
Blown or poured loose-fill
insulation is installed only where
the ceiling slope is <= 3:12.
Complies
Does Not
Not Observable
Not Applicable
4.2.4
[IN6]1
Installed above-grade wall
insulation type and R-value
consistent with insulation
specifications reported in plans
and COMcheck reports.
R-_____
Mass
Metal
Steel
Wood
R-_____
Mass
Metal
Steel
Wood
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.2
[IN7]1
Above-grade wall insulation
installed per manufacturer’s
instructions.
Complies
Does Not
Not Observable
Not Applicable
4.2.4
[IN8]2
Installed floor insulation type and
R-value consistent with insulation
specifications reported in plans
and COMcheck reports.
R-_____
Mass
Steel
Wood
R-_____
Mass
Steel
Wood
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
5.8.1.1
[IN10]2
Building envelope insulation is
labeled with R-value or insulation
certificate has been provided
listing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.9
[IN18]2
Building envelope insulation
extends over the full area of the
component at the proposed rated
R or U value.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.4
[IN11]2
Eaves are baffled to deflect air to
above the insulation.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.5
[IN12]2
Insulation is installed in
substantial contact with the
inside surface separating
conditioned space from
unconditional space.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.6
[IN13]2
Recessed equipment installed in
building envelope assemblies
does not compress the adjacent
insulation.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.7.1
[IN15]2
Attics and mechanical rooms
have insulation protected where
adjacent to attic or equipment
access.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
118 ofPage
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
5.8.1.7.2
[IN16]2
Foundation vents do not interfere
with insulation.
Complies
Does Not
Not Observable
Not Applicable
5.8.1.8
[IN17]3
Insulation intended to meet the
roof insulation requirements
cannot be installed on top of a
suspended ceiling. Mark this
requirement compliant if
insulation is installed accordingly.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:C:\Users\gmpa\Desktop\COMcheck\COM 4.0.8.2-CC BODE- Sand dollar.cck
01/15/22Report date:
119 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
5.4.3.3
[FI1]1
Weatherseals installed on all loading
dock cargo doors in Climate Zones 4-
8.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)