SCOPE OF WORK GENERAL NOTES LEGEND AND ABBREVIATIONS TABLE OFCONTENTS
PAGE# DESCRIPTION
•SYSTEM SIZE:9425W DC,7600W AC •ALL WORK SHALL COMPLY WITH MA 9th Ed.CMR 780(2015 IRC/IBC/IEBC), _ 1 SOLAR MODULES PV-1,0 COVER SHEET
•MODULES:(29)JA SOLAR:JAM60S17-325/MR MUNICIPAL CODE,AND ALL MANUFACTURERS'LISTINGS AND INSTALLATION SERVICE ENTRANCE
•INVERTERS:(1)SOLAREDGE TECHNOLOGIES: INSTRUCTIONS. A P -o-- " GI '9, PV-2.0 SITE PLAN
SE7600H-USS3 •PHOTOVOLTAIC SYSTEM WILL COMPLY WITH NEC 2020. PV 3.0 LAYOUT
•RACKING:SNAPNRACK RLU;RL UNIVERSAL,SPEEDSEAL MP MAIN PANEL
TRACK ON COMP,SEE DETAIL SNR-DC-00436 •ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH NEC 2020. ri PV-4.0 ELECTRICAL
•PHOTOVOLTAIC SYSTEM IS UNGROUNDED.NO CONDUCTORS ARE SOLIDLYUB PANEL SNR MOUNT PV-5.0 SIGNAGE
Co
SNR MOUNT&SKIRT
GROUNDED IN THE INVERTER.SYSTEM COMPLIES WITH 690.35.
•MODULES CONFORM TO AND ARE LISTED UNDER UL 1703. LC PV LOAD CENTER CHIMNEY
•INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
•RACKING CONFORMS TO AND IS LISTED UNDER UL 2703. 0 SUNRUN METER ATTIC VENT
/
1 FLUSH ATTIC VENT
•SNAPNRACK RACKING SYSTEMS,IN COMBINATION WITH TYPE I,OR TYPE II PM DEDICATED PV METER
MODULES,ARE CLASS A FIRE RATED. PVC PIPE VENT
•RAPID SHUTDOWN REQUIREMENTS MET WHEN INVERTERS AND ALL INV INVERTER(S) METAL PIPE VENT
CONDUCTORS ARE WITHIN ARRAY BOUNDARIES PER NEC 690.12(1). El T-VENT
•CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 890.31(G). AC AC DISCONNECT(S)
SATELLITE DISH
•ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT. DC
•10.23 AMPS MODULE SHORT CIRCUIT CURRENT. DC DISCONNECT(S) ' FIRE SETBACKS
•15.98 AMPS DERATED SHORT CIRCUIT CURRENT[680.8(a)&690.8(b)). CB IQ COMBINER BOX HARDSCAPE
•PV INSTALLATION COMPLIES WITH THE NEC 2017 ARTICLE 690.12(BX2). �'
CONTROLLED CONDUCTORS LOCATED INSIDE THE ARRAY BOUNDARY ARE I- INTERIOR EQUIPMENT —PL— PROPERTY LINE
LIMITED TO 80 VOLTS WITHIN 30 SECOND OF A RAPID SHUTDOWN INITIATION L J SHOWN AS DASHED
SCALE:NTS
A AMPERE sun run
AC ALTERNATING CURRENT
AFC' ARC FAULT CIRCUIT INTERRUPTER
AZIM AZIMUTH
VICINITY MAP COMP COMPOSITION #180120
DC DIRECT CURRENT
;•a",' "-k a» (E) EXISTING eeLrmEasrwDISH BIM TAUNTON,MA0170D1391
g ESS ENERGY STORAGE SYSTEM FAX
00
= EXT EXTERIOR
INT INTERIOR CUSTOMER RESIDENCE:
MAG MAGNETIC DAVID FILOSA
MSP MAIN SERVICE PANEL 70 HEMEON DR,YARMOUTH,
(N) NEW MA,02673
?', NTS NOT TO SCALE
^� OC ON CENTER TEL.(508)234-5487
" PRE-FAB PRE-FABRICATED APN:YARM-000038-000086
PSF POUNDS PER SQUARE FOOT
PV PHOTOVOLTAIC PROJECT NUMBER:
x
?o aenecn oc 223R-070FILO
„ •we.n.•nomn,aa RSD RAPID SHUTDOWN DEVICE
f
TL TRANSFORMERLESS (415)580�920 ex3
r %. TYP TYPICAL DESIGNER:
g V VOLTS DOMINGO VILLARUEL
i W WATTS SHEET
L
REV NAME DATE COMMENTS COVER SHEET
`s
REV:A 1/15/2022
.F 's.,,,, .,1.Q..c-ntei PAGE PV-1,0
ARRAY TRUE MAG PV AREA
SITE PLAN-SCALE■3164"■1'-0" • PITCH AZIM AZIM (SOFT)
f, AR-01 29° 124° 138° 416.4
AR-02 29° 34° 48' 108.6
\ LMJ
O� R (N)ARRAY AR-02
a /
9 (E)DECK
R
(E)DETACHED
d': - � STRUCTURE
.�.,* sunrun
R , e/
4,
#180120
806 EB STANdBN BLW.TAUNTON.MA 021B0-TE]1 PHONE
(E)DRIVEWAY D
FN D
R CUSTOMER RESIDENCE:
DAVID FILOSA
4✓ 70 HEMEON DR,YARMOUTH,
(E)RESIDENCE
,, MA,02673
TEL.(508) 87
APN:YARM-0000-000038-000085
PROJECT NUMBER:
(N)ARRAY AR-01 d. 223R-070FILO
(E)DETACHED �� / DESIGNER: (415)58"320 ex3
STRUCTURE \v/ DOMINGO VILLARUEL
SHEET
SITE PLAN
REV:A 1/15/2022
PAGE PV-2.O
7
) ,„,„
ROOF INFO FRAMING INFO ATTACHMENT INFORMATION DESIGN CRITERIA
Name Type Height Type Max OC Detail Max Landscape Max Landscape Max Portrait Max Portrait Configuration MAX DISTRIBUTED LOAD:3 PSF
Span Spacing OC Spacing Overhang OC Spacing Overhang SNOW LOAD:30 PSF
RL UNIVERSAL,SPEEDSEAL TRACK ON WIND SPEED:
AR-01 COMP SHINGLE-RLU 1-Story 2X4 PRE-FABRICATED TRUSSES 10'-8" 24" COMP,SEE DETAIL SNR-DC-00436 6'-0" 2'-4" 4'-0" 2'-0" STAGGERED 140 MPH 3-SEC GUST.
S.S.LAG SCREWS:
AR-02 COMP SHINGLE-RLU 1-Story 2X4 PRE-FABRICATED TRUSSES 10'-4' 24" RL UNIVERSAL,SPEEDSEAL TRACK ON 6'-0" 2-4' 4'-0" 2'-0" STAGGERED 5/16'X4.5":2.5'MIN EMBEDMENT
COMP,SEE DETAIL SNR-DC-00436 STRUCTURAL NOTES:
• INSTALLERS SHALL NOTIFY
D1-AR-01-SCALE:1/8".1%0"
AZIM:124° ENGINEERANY
POTENTIAL STRUCTURAL
_' 28' '-4'-3"-' ISSUES OBSERVED PRIOR TO
PROCEEDING W/
INSTALLATION.
• IF ARRAY(EXCLUDING SKIRT)
2-10" IS WITHIN 12"BOUNDARY
Q REGION OF ANY ROOF PLANE
a _6 TYP { e e EDGES(EXCEPT VALLEYS),
3'-3" THEN ATTACHMENTS NEED
ra a a o o n n nEl
TO BE ADDED AND
OVERHANG REDUCED WITHIN
10' t---1 3'-5" THE 12"BOUNDARY REGION
u so a a s a 0 a 0 ONLY AS FOLLOWS:
••ALLOWABLE ATTACHMENT
SPACING INDICATED ON
a e a a ❑ ❑ a .a o 6'-7" PLANS TO BE REDUCED BY
3'-3" 50%
n n n n n n n n ••ALLOWABLE OVERHANG
11"J INDICATED ON PLANS TO BE
1/5TH OF ALLOWABLE
ATTACHMENT SPACING
8'-4" 44'-9" .,--6'-1"—i
INDICATED ON PLANS
02-AR-02-SCALE:1/8"■1'-0"
___ALM:34° sun run
ATTACHMENT ALTERNATE OPTION 22'-4" #180120
DECK MOUNT DETAIL:SNR-DC-00452 ee MISS sr avo,TNaro",wAoxno-ns,
ATTACHMENT SPACING/OVERHANG r PHONE
Portrait:1'-9"/0'-6" ru o
Landscape:3'-0"/0'-8' CUSTOMER RESIDENCE:
ATTACHMENTS PATTERN=STAGGERED 8'-7" DAVID FILOSA
OFFSET ATTACHMENTS 1'-0"ROW TO ROW 70 HEMEON DR,YARMOUTH,
#14 S.S.WOOD SCREWS MUST EMBED FULLY dlikbaMA,02673
INTO DECK _ `AA OF 44.5,
3'3" �'��SAMUELsir.'y TEL.(508)234-6487
O . APN:YARM-000038-000086
4- _ BROWN -
3'1 o ..,, - - PROJECT NUMBER:
`? ""No. 3 "e 223R-070FI10
L J _1 5" 1/46,STES, DESIGNER: (415)580-6920 ex3
OAL tO DOMINGO VILLARUEL
-----6.-8"— — 11'-2" -- 24'-2" sp.em:vionozx SHEET
LAYOUT
REV:A 1/15/2022
PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
® METER#:
EVERSOURCE 2666635
UTILITY
GRID EXISTING
\1 200A MAIN
BREAKER
(END FED) SOLAREDGE TECHNOLOGIES:
..---, EXISTING SE7600H-US WITH REVENUE
200A (N)MA SMART GRADE METERING(PN
c -«— MAIN (N)LOCKABLE UTILITY SE7600H-USS3),7600 WATT
BLADE TYPEINVERTER
PANEL REVENUE
FACILITY AC DISCONNECT_ METER _ 7600 WATT INVERTER JUNCTION BOX PV MODULES
LOADS (3 (3) (3) c2� OREOUNALEr+T CO JA SOLAR:JAM60S17-325/MR
F X / (29)MODULES
owe--e —._— ® ./` _ /. —fi-- --.— 11 +( // OPTIMIZERS WIRED IN:
L t (1)SERIES OF(15)OPTIMIZERS
I 4) (1)SERIES OF(14)OPTIMIZERS
(N)40A .4-o66x0 SQUARE D 240V METER SOCKET LOAD RATED DC DISCONNECT
PV BREAKER AT DU222RB 100A CONTINUOUS WITH AFCI,RAPID SHUTDOWN L SOLAREDGE POWER OPTIMIZERS
OPPOSITE ENO 3R,60A,2P UTILITY SIDE OF ciRcurr COMPLIANT P370
OF BUSBAR NECTS TO TOP LUGS-
NOTE:TOTAL PV BACKFEED=40A 120/24OVAC NCONE AT TOP LOAD AT BOTTOM)
USED FOR INTERCONNECTION
CALCULATIONS
CONDUIT SCHEDULE
I CONDUIT CONDUCTOR NEUTRAL GROUND
1 NONE (4)10 AWG PV WIRE NONE (1)10 AWG BARE COPPER
2 3/4"EMT OR EQUIV. (4)10 AWG THHNITHWN-2 NONE (1)10 AWG THHWTHWN-2 s u n ru n
3 3/4"EMT OR EQUN. (2)8 AWG THHN/THWN-2 (1)10 AWG THHNITHWN-2 (1)8 AWG THHNITHWN-2
#180120
eo6 MY ES 8TNIDINI ELM TAUNTON.MIA,67I66.7361
PHONE o
FAX
CUSTOMER RESIDENCE:
DAVID FILOSA
70 HEMEON DR,YARMOUTH,
MA,02873
MODULE CHARACTERISTICS P370 OPTIMIZER CHARACTERISTICS: TEL(508)234-5487
JA SOLAR:JAMSOS17-325/MR: 325 W APN:YARM-000038-000086
OPEN CIRCUIT VOLTAGE: 40.87 V MIN INPUT VOLTAGE: 8 VDC
MAX POWER VOLTAGE: 33.97 V MAX INPUT VOLTAGE: 60 VDC PROJECT NUMBER:
SHORT CIRCUIT CURRENT: 10.23 A MAX INPUT ISC: 11 ADC 223R-070FIL0
MAX OUTPUT CURRENT: 15 ADC
DESIGNER: (415)5806920 ex3
SYSTEM CHARACTERISTICS-MVERTER 1 DOMINGO VILLARUEL
SYSTEM SIZE: 9425 W SHEET
SYSTEM OPEN CIRCUIT VOLTAGE: 15 V ELECTRICAL
SYSTEM OPERATING VOLTAGE: 400 V
MAX ALLOWABLE DC VOLTAGE: 480 V
REV:A 1/15/2022
SYSTEM OPERATING CURRENT: 23.56 A
SYSTEM SHORT CIRCUIT CURRENT: 30 A PAGE PV-4.O
P
AL INVERTER 1 NOTES AND SPECIFICATIONS:
•SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE NEC 2020 ARTICLE
ELECTRICAL SHOCK HAZARD PHOTOVOLTAIC DC DISCONNECT 11021(B),UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690,OR
IF REQUESTED BY THE LOCAL AHJ.
MAXIMUM SYSTEM VOLTAGE. 480 VDC •SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
TERMINALS ON LINE AND LOAD WORDS,COLORS AND SYMBOLS.
SIDES MAY BE ENERGIZED IN •LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
THE OPEN POSmoN LABEL LOCATION: METHOD AND SHALL NOT BE HAND WRITTEN.
INVERTER(S),DC DISCONNECT(S). •LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
PER CODE(S):NEC 2020:690.53 INVOLVED.
LABEL LOCATION: •SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011,PRODUCT SAFETY
INVERTER(S),AC/DC DISCONNECT(S), SIGNS AND LABELS,UNLESS OTHERWISE SPECIFIED.
AC COMBINER PANEL(IF APPLICABLE). •DO NOT COVER EXISTING MANUFACTURER LABELS.
PER CODE(S):NEC 2020:690.13(B)
WARNING: PHOTOVOLTAIC
. POWER SOURCE
LABEL LOCATION:
DUAL POWER SUPPLY INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT,
SOURCES:UTILITY GRID AT EACH TURN,ABOVE AND BELOW PENETRATIONS,
ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
AND PV SOLAR ELECTRIC PER CODE(S):NEC 2020:690.31(DX2),IFC 2012:
SYSTEM 605.11.1.4
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN
SERVICE PANEL
PER CODE(S):NEC 2020:705.12(C) CAUTION :
it
MULTIPLE SOURCES OF POWER
DO NOT RELOCATE THIS
OVERCURRENT DEVICE LABEL LOCATION:
INSTALLED WITHIN OFRAPIDSHUT DOWN �' s u n r u n
LABEL LOCATION: SWITCH PER CODE(S):NEC N2020:890.68(Cx2),IFC
ADJACENT TO PV BREAKER AND ESS 2012:805.11.1,IFC 2018:1204.5.3
OCPD(IF APPLICABLE).
PER CODE(S):NEC 2020: —4„__
705.12(B)(3X2) -.� 1
A, SOLAR PV SYSTEM EQUIPPED SOLAR PANELS ON ROOF #180120
S36 MYLES STAIWIBN SIVO,TAUITON.MA,627667331
PHOTOVOLTAIC SYSTEM WITH RAPID SHUTDOWNPHONE
COMBINER PANEL F6
DO NOT ADD LOADS — CUSTOMER RESIDENCE:
LABEL LOCATION: _ DAVID FILOSA
PHOTOVOLTAIC AC COMBINER(IF
70 HEMEON DR,YARMOUTH,
APPLICABLE). MA,02673
PER CODE(S):NEC 2020:705.12(DX2X3Xc) 3• TURN RAPID SHUTDOWN
SWITCH TO THE"OFF" 61111111011116 TEL.(508)234-5487
INNIIIII
POSITION TO SHUT DOWN 1 1 1 1 1 APN:YARM-000038-000088
PV SYSTEM DISCONNECT PV SYSTEM AND REDUCE 1 1 MAIN PANEL(INT)SHOCK HAZARD IN THE
PROJECT NUMBER:
61AXIMUP,1 AC OPERATING CURRENT 31.67 AMPS 223R-070FILO
ARRAY, IIIII INVERTER EXT
TT AGE 240 VAC: ( ) SERVICE ENTRANCE DESIGNER: (415)580-8920 ex3
NOMINAL OPERATING AC VOL
LABEL LOCATION: MA SMART METER--AC DISCONNECT(EXT) DOMINGO VILLARUEL
AC DISCONNECT(S),PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION. , - (EXT) SHEET
PER CODE(S):NEC 2020:690.54 LABEL LOCATION: SIGNAGE
ON
NO CNT MEANS TO WHICH THE PV SYSTEMS 70 HEMEON DR, YARMOUTH, MA, 02673
ARE CONNECTED. REV:A 1/15/2022
PER CODE(S):NEC 2020:690.56(C)
PER CODE(S):NEC 2020:705.10,710.10 PAGE
PV-5.0