AaMUTH ANDRLT ANGLE CONSTRUCTION NOTES
ROOF A. A LADDER SHALL BE IN PLACE FOR ANY INSPECTIONS IN COMPLIANCE WITH OSHA REGULATIONS.
A B C 0 E F B. PV MODULES ARE NON-COMBUSTIBLE IN NATURE.
C. THIS SYSTEM IS A UTILITY INTERACTIVE(GRID CONNECTED)SYSTEM AND DOES NOT HAVE STORAGE BATTERIES(UNLESS SPECIFICALLY INDICATED ON SHEET PV3&PV3.1).
ADMUTH 173' D. A GROUND ELECTRODE SYSTEM WILL BE PROVIDED IN ACCORDANCE WITH NEC 690.47&250.50-250.166.GROUNDING ELECTRODE SYSTEM OF EXISTING BUILDING MAY BE
TILT ANGLE 7/12 USED WHEN BONDED AT THE SERVICE ENTRANCE.IF EXISTING SYSTEM IS INACCESSIBLE OR INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL
MODULE COUNT 11 GROUNDING ELECTRODE WILL BE USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED BET GROUND ROD WITH ACORN CLAMP.GROUNDING ELECTRODE
CONDUCTORS SHALL BE NO LESS THAN KB AWG AND NO GREATER THAN K6 AWG COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A
SOIARAcCE55 COMPLETE GROUNDING SYSTEM.
E. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
TSN AVEREAQ F. THE EXPOSED METALLIC TABS OF THE SOLAREDGE OPTIMIZERS SHALL BE BONDED AND/OR GROUNDED PER NEC 690.43(A)AND THE MANUFACTURERS'INSTRUCTIONS.
INVERTERS SOLAR EDGESE3000H-USRGM 1 G. PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER NEC 110.26.
OPTIMIZER SNAIL EDGE P401 11 H. ALTERNATE POWER SOURCE PLACARD SHALL BE PLASTIC,ENGRAVED IN A CONTRASTING COLOR(WHITE).THIS PLAQUE WILL BE PERMANENTLY ATTACHED&UV RESISTANT.
I. ALL PLAQUES AND SIGNS WILL BE INSTALLED AS REQUIRED BY 2017 NEC.
MODULE al: COUNT: MODULE I/2: COUNT: TOTAL COUNT: 1. A SMOKE DETECTOR,APPROVED AND LISTED BY THE STATE FIRE MARSHAL,SHALL BE INSTALLED IN EACH DWELLING WHEN A PERMIT FOR ALTERATIONS,REPAIRS OR
HWWHAQ{ELLSQ.PEAK DIJOBLKML-G10.aa39S 11 II ADDITIONS EXCEEDS$1,000.00.A BATTERY POWERED SMOKE DETECTOR SATISFIES THE REQUIREMENTS FOR A SMOKE DETECTOR.APPROVED COMBINED SMOKE ALARMS
AND CARBON DIOXIDE ALARMS SHALL BE ACCEPTABLE.A CARBON MONOXIDE DETECTOR SHALL BE INSTALLED IN THE SPECIFIC EXISTING DWELLING UNIT THAT HAVE
ATTACHED GARAGES OR FUEL-BURNING APPLIANCES FOR WHICH A PERMIT IS ISSUED FOR ALTERATIONS,REPAIRS OR ADDITIONS EXCEEDING$1,000.00.LISTED SINGLE-OR
SHEET INDEX APPLICABLE CODES MULTI-STATION CARBON MONOXIDE ALARMS SHALL BE INSTALLED OUTSIDE OF EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE BEDROOMS AND ON
M TITLE SHEET 2017 NATIONAL ELECTRICAL CODE INFRATOI EVERY LEVEL OF A DWELLING UNIT INCLUDING BASEMENTS.COMBINED SMOKE/CARBON MONOXIDE ALARMS MAY BE USED.THE ALARM SHALL RECEIVE ITS PRIMARY
IO2B iMERNATONAI RESIDENTIAL CODE(ARC)AS AMENDED POWER FROM THE BUILDING WIRING EXCEPT IT IS PERMITTED TO BE SOLELY BATTERY OPERATED WHERE REPAIRS OR ALTERATIONS DO NOT RESULT IN THE REMOVAL OF
PIE R00F/SITE RAN WALL AND CEILING FINISHES OR THERE IS NO ACCESS BY MEANS OF AN ATTIC.
20151NTERNATIONAL BUILDING CODE AS AMENDED K. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN THE GROUNDING ELECTRODE AND THE PANEL OR INVERTER)IF
PAT ELECTRICAL LINE DIAGRAM/DETNIS (
201S INTERNATIONAL RESIDENTIAL COM At AMENDED SMALLER THAN K6 AWG COPPER WIRE AS PER NEC 250-64B.THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS,EXCEPT FOR SPLICES OR JOINTS AS BUSBARS
P3.1(MNEEOED) ELECTRICAL UNE DIAGRAM/IXTNLS WITHIN LISTED EQUIPMENT AS PER NEC 250.64C.
RV EQUIPMENTUBELS L. ROOF COVERINGS SHALL BE DESIGNED,INSTALLED,AND MAINTAINED IN ACCORDANCE WITH THE BUILDING CODE OF THE LOCAL JURISDICTION.
M. PV SYSTEMS CONNECTION IN THE SWITCH GEAR(PANEL)SHALL BE POSITIONED AT THE OPPOSITE END FROM THE INPUT FEEDER LOCATION OR MAIN CIRCUIT LOCATION AS
N4.1 FUCA/I PER NEC 705.12(R)(2)(3)(b).
PBS ATTACHMENT RAN N. ALL EQUIPMENT SUPPLIED SHALL BE UL LISTED OR LISTED BY A LISTING AGENCY RECOGNIZED BY THE STATE IN WHICH THE SYSTEM IS CONSTRUCTED.
O. AC DISCONNECTS SHALL BE IN COMPLIANCE WITH NEC 690.17.
P/6 STRUCTURAL COMPONENT P. ALL DC CONDUCTORS SHALL BE 90.RATED THHW,THWN-2,USE-2 OR PV WIRE.ALL AC CONDUCTORS SHALL BE 75'RATED THWN WIRE.
PVT PROPERTY LINES Q. THE UTILITY DISCONNECT HAS VISIBLE BLADES.IS LOCKABLE AND IS ACCESSIBLE TO THE UTILITY 24/7.
STRUCTURAL FNGINEERNGCNS BERM) R. ALL BREAKERS SHALL BE SUITABLE FOR BACKFEED.WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION THE BREAKER SHALL NOT READ'LINE AND
LOAD'.
EQUIPMENTDATASIEETS S. COORDINATE ANY POWER OUTAGE WITH LOCAL UTILITY AND PROPERTY OWNER.NOTIFY UTILITY BEFORE ACTIVATION OF PV SYSTEM.
T. CITY BUILDING INSPECTOR SHALL INSPECT ACCESSIBLE STRUCTURAL CONNECTIONS AND THE HOUSE CURRENT SIDE OF THE SYSTEM,ALL OTHER EQUIPMENT SHALL BE UL
LISTED AND APPROVED.
OCCUPANCY&CONSTRUCTION TYPE U. PHOTOVOLTAIC MODULES SHALL NOT BE INSTALLED OVER ANY ATTIC,PLUMBING OR MECHANICAL VENT.PLUMBING VENTS TO EXTEND A MIN OF 6"ABOVE ROOF OR
OCCUPANCY R3 MODULE.NO BLDG,PLBG OR MECH VENTS TO BE COVERED,OBSTRUCTED OR ROUTED AROUND MODULES.
V. ROOF ACCESS POINT SHALL RE LOCATED IN AREAS THAT DO NOT REQUIRE THE PLACEMENT OF GROUND LADDERS OVER THE OPENINGS SUCH AS WINDOWS OR DOORS,AND
CONSTRUCTION-5B LOCATED AT A STRONG POINT OF BUILDING CONSTRUCTION.FIELD VERIFY EXACT LOCATION.
W. THE DISCHARGE OF POLLUTANTS TO ANY STORM DRAINAGE SYSTEM IS PROHIBITED.NO SOLID WASTE,PETROLEUM BYPRODUCTS,SOIL PARTICULATE,CONSTRUCTION
WASTE MATERIAL OR WASTEWATER GENERATED ON CONSTRUCTION SITE OR BY CONSTRUCTION ACTIVITIES SHALL BE PLACED,CONVEYED OR DISCHARGED INTO THE
STREET,GUTTER OR STORM DRAIN SYSTEM.
X. ALL WIRING MUST BE PROPERLY SUPPORTED BY DEVICES OR MECHANICAL MEANS DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE PERMANENTLY AND
COMPLETELY HELD OFF OF THE ROOF SURFACE.
V. PAINT SURFACE MOUNTED CONDUIT TO MATCH EXISTING STRUCTURE.VECTOR VICINITY MAP
e n a I n e e R e rg L Hee,
65/W.DALE DRAPE �E.,.G<Da0.PARE BLVD.a,..101 AN E DEDII,990.1775Q 9 wart
4.s
�� HO SE - I O ,. Ma ..... k .• q, Phase:.,
%
--,.00...• 74_,
r r«r .R r,a� ,,. -.e „r,m a .. .,�.,en �w
sivS/ONAL E
AU
02/07/2022 KQ Mw TBaE4aYLNM y,a5.n.,,..,mr...,m„
VSE Project Number:U1932-5026-221
•
Vector Structural Engineering has reviewed the existing
structure with loading fr.,the solar array end screw connections le Ore exisang framing.The design of the +✓r:r,"..,,_"T.'�i.,, h.
racking system,racking connections.and all other '" - ,
structural Is by others.Mechanical architectural,and all • ,,..
•
other nonslructural aspects of the design are by others.
Bechtel is by others,UnAlS Camped by Dean Levorsen.
r14 whake.le ,
•
,TANnx �t.; O� A
N
.., ,. gRIpNYO.d'.,
SIGNATURE: PROJECTK IPSl6O914 REV DATE DESCRIPTION GHEEr lnLE
BRIGHT PLANET SOLAR
h r•a, pB �P'103A MILLBURY ST, SYSTEM SIZE 4.345MW/DC 3NVAAC _ — SHELLEY HILL TITLE SHEET
' r6 htPlanet4d�E W AUBURN MA 01501 CONTRACTOR LICENSE: DATE: 2 5 2022 7:29:16 AM — 18SEDGEWICK PATH,
888-997-4469 YARMOUTH,MA 02673 011BI"
DATE: 2/5/2022 7:29:16 AM DESIGNER: I.RIVAS — — PV1
''s( u „,.......... Z.Z. (CCD 4 s3 (
AZIMUTH AID TILT ANGLE
ROOF
A B C D E F
ADMUTN 17r
TILT ANGLE 7/12
MODULE COUNT 11
SOLAR ACCESS
TSER AVEREAGE
INVERTERS SOLAR EDGE SE300011-USRGM 1
OPTIMIZER SOLAR EDGE P401 11
MODULE n: COUNT: MODULER: COUNT: TOTAL COUNT:
HANWINQCELLS O.PEAR Dip BLRML-G10.a1395 11 11 I x
LCHIMNEY
SYMBOL LEGEND N
0= MECHANICAL VENT
0=FLUE/PLUMBING VENT Iw 4O COMPOSITION SHINGLES
b.
1 MAIN SERVICE PANEL \ V b� 6
2 UTILITY METER AND MA SMART METER 0 O
3 AC DISCONNECT
L_ _ o
4 NOT USED
S
Q ROOF A
5 INVERTER&INTEGRATED DC DISCONNECT 4.
1J--9_1
U
5.1 NOT USED •
W 0
0IC -
O OPTIMIZER(TYPICAL FOR EACH MODULE) W
N
0 JUNCTION BOX ROOF SIZED DETERMINED IN FIELD
0 PV MODULES
OCONDUIT RUN IS SURFACE MOUNTED
(ACTUAL CONDUIT RUNS TO BE
DETERMINED IN THE FIELD)
10 NOT USED
// T
1 2 / _J 5
o, s 10. 3 .-/�/
NEC 110.26
SIGNATURE: PROJECT# DP5100914 REV DATE DESCRIPTION s12Ern�LT:
BRIGHT PLANET SOLAR ROOF/SITE PLAN
l�4. 103A MILLBURY ST, SYSTEM SIZE 4AIBTIW/DC 3RW/AC -_ _ SHELLEY HILL
BrgtPlanet° 6ia L�AUBURNMA0,50, CONTRACTOR LICENSE: DATE: 25/20227:29:17AM -- — 185EDGEWICKPATH,
888-997-4469YARMOUTH,MA 02673 '"EEL R
DATE: 2/5/2022 7:29:17 AM DESIGNER: I.RIVAS — — PV2
NOTE:PLAQUES SHALL BE ATTACHED TO THE SERVICE EQUIPMENT WITH NON CORROSIVE,POP—RIVETS,SCREWS,OR APPROVED ADHESIVE.
0 LOCATI&AC DISCONNECT N:MAIN 11 SERVICE PANEL O CONDUIT,RACEWAYS&ENCLOSURES LOCATION:MAIN PANEL
WARNING:PHOTOVOLTAIC Y' {
a6 POWER SOURCE • • pk
ELECTRIC SHOCK HAZARD r(y "o T • H1 n r o' , U•IXX)( . y
CO NOT TOUCH TERMINALS 0 LOCATION:DC DISCONNECT/INVERTER#1I.r '
TERMINALS ON BOTH THEUNEAND +Y. -rY.m P. ,T, .,_.,lo- d1 -c. f `f.
LOAD SIDES MAY BE ENERGIZED PHOTOVOLTAIC SYSTEM DC DISCONNECT TURN RAPID SHUTDOWN.
IN THE OPENPOSRICN MAXIMUM CIRCUIT CURRENT ICI 111019NUAIC MULES MOM SWITCH TO THE
METER TIE/ARE DPOSFD TO SUNLIGHT MAXIMUM SYSTEM VOLTAGE Ell " -
LOCATION:MAIN SERVICE PANEL OFF"POSITION TO ;: ••v;
OMAXIMUM RATED OUTPUT CURRENT OF THE EllSHUT DOWN PV SYSTEM 5
PV BACK—FED BREAKER CHARGE CONTROLLER OR DC-IR.DC CONVERTER
AND REDUCE ,
!:`:INVERTER OUTPUT CONNECTION SHOCK HAZARD
DO NOT RELOCATE THIS 08 LOCATION:MAIN SERVICE PANEL IN THE ARRAY
OVERCURRENT DEVICE
PV SYSTEM POINT OF CONNECTION 13 LOCATION:MAIN SERVICE PANEL/AC DISCONNECT
3
LOCATION:MAIN SERVICE PANEL SOLAR PV SYSTEM AC POINT OF CONNECTION
PV BACK—FED BREAKER
MAX AC OUTPUT CURRENT 12.5 A
r�oMINALACL.oLTAcc 240L MAIN PHOTOVOLTAIC
MAX
DUAL POWER SUPPLY THIS PANEL FED BY MULTIPLE SOURCES SYSTEM DISCONNECT
SOURCES:UTILITY GRID AND (UTIUTY AND SOLAR)
PV SOLAR ELECTRIC SYSTEM
O LOCATION:MAIN SERVICE PANEL 14 LOCATION:AC DISCONNECT
0 LOCATION:UTILITY METER
PHOTOVOLTAIC SYSTEM EQUIPPED PHOTOVOLTAIC AC DISCONNECT
THIS SERVICE METER WITH RAPID SHUTDOWN
IS ALSO SERVED BY A
PHOTOVOLTAIC SYSTEM
OLOCATION:PV SUB PANEL(IF USED) 0LOCATION:INVERTER
RAPID SHUTDOWN SWITCH FOR
PHOTOVOLTAIC SYSTEM SOLAR PV SYSTEM
COMBINER PANEL FOR ILLUSTRATION ONLY(NOT ACTUAL MSP)
DO NOT ADD LOADS PV SUB PANEL(IF USED) CONDUITS/RACEWAYS MAIN SERVICE PANEL
imi
0 T 12 DI I
O O
PLACARD 0 I I
m /D O
AC v \\
DISCONNECT 0 0, D p p
INVERTER (IF USED) m
I I
O m 0
O m
� O CO0
m
113 14 1 10.
t iO nn I I 13 0
SIGNATURE: PROJECTS BPS180914 REV DATE DESCRIPTION sHEETTirLe
BRIGHT PLANET SOLAR
I~ 1O3AMILLBURYST, SYSTEM SIZE 4.345kWAC *MC — — SHELLEY HILL EQUIPMENT
r►' BrightPlanet 5i r AUBURN MA 01501 DATE 25/20227:29:33AM — �8 SEDGEVVICK PATH, LABELS
CONTRACTOR LICENSE:888-997 4469 YARMOUTH,MA 02673 SHttI a
DATE: 2/5/2022 7:29:33 AM DESIGNER I.RIVAS — — PV4
12 PLACARD • •
CAUTION
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH
DISCONNECTS AS SHOWN
07/7\
C9
a
W
Co
EXISTING MAIN — SOLAR
SERVICE ENTRANCE INVERTER & DC
UTILITY AC DISCO — DISCONNECT
SIGNATURE: PROJECT# BPS1S0914 REV DATE DESCRIPTION s eTni�E
BRIGHT PLANET SOLAR
r~ip
Br �{ . 103A MILLBURY ST, SYSTEM SIZE 4.345kW/DC 3k59AC — — SHELLEY HILL PLACARD
B !B�Pianet �€ i,y AUBURN MA 01501 CONTRACTOR LICENSE: DATE: 2/5/20227:29:34 AM — — 18 SEDGEVVICK PATH,
888-997-4469 YARMOUTH,MA 02673 °N,°'
DATE: 2/5/2022 7:29:34 AM DESIGNER: I.RIVAS — — PV4.1
MOUNT ATTACHMENT ENDCLAMP,TYP.
III W Dili
Il II II II I II II II I
II II II 9 1 II II II 1
5'-7' II II 11 II I II II II 1
II II II II 1 11 II II I
II II II II I II II II I I
II II II II I II II II I
1—a'
STRUCTURAL FRAMING
MEMBER @ 16"O.C.
= MOUNT ATTACHMENT LOCATION
• MAXIMUM OVERHANG(CANTILEVER)IS 19e
MAXIMUM SPACING OF ANCHORS(FOOTINGS)IS 48 IN.O.C. ROOF A
FIELD VERIFY EXACT LOCATION OF STRUCTURE MEMBERS. PHOTOVOLTAIC DEAD LOAD STATEMENT �N/E CTO R
TOTAL AREA OF ARRAY=199.53 SO.FT. c net n e e a e
ARRAY GROSS WEIGHT=518.77 LBS
DEAD LOAD RATING=2.8 LBS/SO.FT. DRAPE',u nw a<oao era.car P. mow vecro„mE.cu,
EXISTING STRUCTURAL FRAMING=2x8•,18 IN.O.C. ,-N OF
eB4O
U / ;
%
MON&E
02/07/2022
VSE Project Number:U1932-5026-221
Vector Structural Engineering has reviewed the existing
structure with loading from the solar array and screw
connections to the existing homing.The design of the
rcking system,racking connection.and all other
structural is by others.Mechanical,architectural,and all
other nonstructural aspects of the design are by others.
Electrical is by others,unless stamped by Dean Levorsen.
SIGNATURE: PROJECT# EPSIRSI4 REV DATE DESCRIPTION st2E*mLE
• BRIGHT PLANET SOLAR • ATTACHMENT
(e.,v:, ~R 103A MILLBURY ST, SYSTEM SIZE 4345kW/DC 3kWMAC — — SHELLEY HILLBrigtPlanet51aAUBURNMA0,50, 18SEDGEWICKPATH, PLAN
CONTRACTOR LICENSE: DATE: 2/5/2022 7:29:35 AM — — eei ro
Sn
888-997-4469 DESIGNER. 1.RIVAs — _ YARMOUTH,MA 02673 pV5
DATE: 2/5/2022 7:29:35 AM
•
RL
TREES TO
SNAPNRACK SPEEDSEAL
SNAPNRACK RAILLESS ROOF MOUNT SYSTEM
ATTACHES TO THE SNAPNRACK S UNIVERSAL MOUNT
TRACK.IT CAN BE"FLIP-FLOPPED"IN THE `
'~\SPEEDTRACK,AS SHOWN,TO REDUCE \Li\
MODULE CANTILEVER AND ELIMINATE `j
�, MOUNT-LINK INTERFERENCE
I° ��
PARTS LIST
t •�'` ITEM QTY DESCRIPTION
Asir �, 1 1 SNAPNRACK,SPEEDSEAL TRACK,7-1/21 N,SEALING,MILL
`• /44 ./� •ei \`�� 2 1 SNAPNRACK,RL UNIVERSAL,MOUNT
IAlt
/�!APNIACK
it*
38 SPEEDSEAL TRACK �1.50—FL"
I 3,39
/ 0.33 02.39 I I 1 11.09 /�\Q I �� � ,, O
1.28 ��1�I\7
.32 .l0 11L31—III 1 , .._ ;�
I.-3.10� T �92.37" '10 �.
MOUNT"FLIP-FLOP"ABILITY
Vector Structural Engineering has reviewed the existing
'A1,H OF ss 61�"S S.LAG SCREW SPEEDSEAL TRACK structure with loading from the ingr array and cosh
a mMa king co framing.connections,
The design o/the
racking system,racking connacllbna,end ell other
A structural is by others.Mechanical,architectural,and all
�/1 other nonstructural aspects of the design are by others.\`\\ is ''e Tar WASHERt. Electrical is by others,unless clamped by Dean Lawrsen,
•
`' 1}%2"LENGTH •
��yy1, �y� -•',�� .,411. -I BOLT HE%HEAD,S.S. 'rrS/ EMp, FOAM DAM 1� ROOFING
�j (TORQUE TO SPECIFICATION) �A� / ' '�� �
�� MATERIAL ♦ /�
1k SNAPNRAIX RL UNIVERSAL ' / I/�/ '
`� %'c BONDING CLIP,S.S. O2/O7/2022 .��,/ \ /♦ `�`r"...4410'♦
O BLACK VSE Project Number:U1932-5026-221 �'' \♦�/
"S.S.MB SCREW / ROOF SHEATHING
SNAPNRACK RL UNIVERSAL SNAPNRACK RL UNIVERSAL 2}"MINIMUM EMBEDMENT
MOUNT,ASSEMBLY MOUNT TOP,BLACK
• RAFTER
V
WASHER ,�/ECTOR COMPLETED INSTALLATION
DETAIL A c n e I n e c R e
/► . era.t0, 214092 la SECTION VIEW
COIL SPRING FOR SNAPNRACK RL UNIVERSAL m.vca.ur.n eenzo www. oaac.co,.
1 SPEEDSEAL TRACK Or BOLT,S.S.
MOUNT BOTTOM DETAIL B
(OPTIONAL)
L,,,,......111000.
/
0,1"-16%1"LENGTH ,
Q BOLT,S.S) ` I �� ♦ �� R COMPOSRION SHINGLE
(TORQUE TO SPECIFICATION
\ OVER PLYWOOD
SNAPNRACK RL ' r�Ty` CLAMP
UNIVERSAL LEVELER I'
�. O ♦ • ♦ SOLAR MODULE y2 6.
SNAPNRACKER �i '♦ �'
UNIVERSAL RISER Oil
+ SEE PVS FOR STRUCTURAL
-plarsusal1�� 401#
It FORMoATIreON�
\ PILOT HOLE SPEEDSEAL MOUNT eo.�wa
Ifi% LENGTH �/ CENTER OF COURSE
SNAPNRACK ROCK-IN BOLT,S.S. ROOF RAFTER SHALL •SEALANT APPLIED UNDERNEATH,APPROVED SEALANTS
CHANNEL NUT (TORQUE TO SPECIFICATION) ROOF ATTACHMENTS SHALL ROOF SHEATHING,UNDERIAYMENT, INCLUDE:GEOCELL 2300,GEOCELL 4500,AND CHEMLINK M1
BE EMBEDDED INTO AND ROOFING MATERIAL(TIP.) LAG BOLT -.e,e.ore' �"m"`�"'"'`"°OgpR°"aou,..s...,c
SNAPNRACK RL UNIVERSAL ROOF RAFTERS OR OTHER NOTE:Shall be at
MOUNT,EXPLODED STRUCTURAL MEMBERS
least 6 inches from any
SIGNATURE PROJECT# BPS160914 REV DATE DESCRIPTION sALOr tALE -
BRIGHT PLANET SOLAR
A a,.,.,,103A MILLBURY ST, SYSTEM SIZE +.B+s w Dc 3KwAc - — SHELLEY HILL STRUCTURAL
ktii rn h Planet;'S6'U3 AUBURN MA 01501 DATE 2 5/2022 7 29:36AM 18 SEDGEWICK PATH, COMPONENTS
888-997-4469 CONTRACTOR LICENSE: YARMOUTH,MA 02673
-
s1-h t a
DATE: 2/5/2022 7:29:36 AM DESIGNER: I.RNAS PV6
. • ' . ., . ,..'....'. '''''C7Ve.''''. ;''',.-''''': .''T-- I - ; - *- - 6 ' ' '
' • t,*' '-' 11,1MV.......0...00"* , lihia4til
a,
t
J' .,T.u'ad'��' ',.•.: air,, ...
P .. `
yr z ,:%, �t
x iat a - r, r .e.
k a i
:'r'.1 1:'''':ft :c,::,:.:4:...0. ,-,"''0:::,
� , Se, G rrGk �'8th `
t �
•
i,
'
tt,
rth
SIGNATURE PROJECT# BPS1130914 En DATE DESCRIPTION
BRIGHT PLANET SOLAR
�� r. BRIGHT
LLBURY ST, SYSTEM SIZE 4.349 W DC 3654-C1.111 - — SHELLEY HILL PROPERTY
r Planet AUBURN MA 01501 — - — 18 SEDGEVVICK PATH, LINES
868-997 4469 CONTRACTOR LICENSE DATE: 2/5/2022 7:29:36 AMYARMOUTH,MA 02673
DATE: 2/5/2022 7:29:36 AM DESIGNER I.RIVAS
MAPPING INSTRUCTIONS: "`"AN NO
^T1N0
• o l i INVERTER(S)SERIAL NUMBERS
1 1.REMOVE THE'SQUARE OPTIMIZER STICKER h' #
AND PLACE NEATLY ON THE APPROPRIATE
NUMBERED SPACE. #
M.IIuM
1 2 3 4 5 p WRITE THE CORRESPONDING NUMBER ON `'''"'"`�" #
ONLINt
THE APPROPRIATE MODULE WITHIN THE ARRAY 11,__--_ ���• _- I. 1 *L_
• DO NOT MAKE ANY TIE IN CHANGES UNLESS APPROVED AND DOCUMENTED BY BPS DESIGN TEAM
• MAXIMUM WATTAGE ALLOWED IN CIRCUIT/STRING IS 6000W FOR SOLAREDGE INVERTERS 7600-11400
6 7 8 9 10 • MAXIMUM WATTAGE ALLOWED IN CIRCUIT/STRING IS 5700W FOR SOLAREDGE INVERTERS 3000-6000
' • MINIMUM OPTIMIZERS IN CIRCUIT/STRING=8(6 WITH P405/P505)
11 12 13 14 15
V-I
16 17 18 19 20
21 22 23 24 25
0
D
ROOF
26 27 28 29 30
0
31 32 33 34 35
36 37 38 39 40
41 42 43 44 45
SIGNATURE: PROJECT# BPS190914 REV DATE DESCRIPTION ° E'0'LE
BRIGHT PLANET SOLAR
r.. AUBURN MA
SYSTEM SIZE 4.345kw/DC 3RW/AC — — SHELLEYHILL OPTIMIZER
� �� Planet "x� iAUBURN MA 01501 — — 18 SEDGEWICK PATH, TRACKING
CONTRACTOR LICENSE: DATE: 2/5/2022 7:29:37 AM YARMOUTH,MA 02673
ID' 888-997-4469 SM.!n —
DATE 2/5/2022 7:29:37 AM DESIGNER. I.RNAS — — PV8
•
LEGEND / JOB HAZARD ANALYSIS /
LEYENDA ANALISIS DE RIESGOS LABORALES
•
SITE NOTES(INCLUDE ANY HAZARD,NUMBERED AND EXPLAINED):
EXCLUSION ZONE/ NOTAS DEL LUGAR(INCLUYE CUALQUIER RIESGO,NUMERADO
ZONA Y EXPLICADO):
RESTRINGIDA
xxxxxxxxxxxxx
ELECTRICAL ZONE/
ZONA ELECTRICA CLOSEST URGENT CARE/MEDICAL FACILITY:
SALA DE EMERGENCIA/HOSPITAL MAS CERCANO: r„—)
L LADDER/
ESCALERA PUBLIC PROTECTION/PROTECION PUBLICA:
❑EXCLUSION ZONES/ZONA RESTRINGIDA
❑MARKED ENTRYWAYS/ENTRADA MARCADA
A ANCHOR/
ANCLAJE L—
FALL PROTECTION/PROTECCION DE CAIDAS:
❑ANCHORS/ANCLAJE e °
❑ROPES/CARABINERS&ROPE GRAB/SOGAS CARABINERO a ROOF A
AANCHOR Y AGARRE DE SOGA
WORK ANGLES/ 0 HARNESS/ARNES
ANCLAJE ❑LANYARDS/SOGA o
TRABAJADO EN y
ANGULOS
V VEHICLES/ I PPE/EPP:
VEHICULOS 0 SAFETY GLASSES/GAFAS DE SEGURIDAD
GLOVES/GUANTES
❑HARD HATS/CASCO DE SEGURIDAD
0 ARC FLASH SUIT/HOT GLOVES/TRAJE AISLANTE/GUANTES
A HAZARD NUMBER PARA ELECTRICIDAD
& EXPLAIN/ 0 FIRST AID KIT/KIT DE PRIMEROS AUXILIOS
RIESGOS 0 COVID-19 PPE ON SITE/EPP POR COVID EN EL LUGAR
NUMERADOS 0 CREW ADHERING TO BPS COVID-19 PLAN/AJUSTE EN EL GRUPO
Y EXPLICADOS AL PLAN POR COVID-19 DE BPS
EII
TREE/ARBOL
DATE/FECHA:
E HOME CREW LEAD/LIDER DE GRUPO:
ENTRANCES/
ENTRADA DE LA CREW MEMBERS/MIEMBROS DEL GRUPO:
CASA
SIGNATURE: PROJECT# SPS180914 REV DATE DESCRIPTION Stilt LE
BRIGHT PLANET SOLAR
� x �� , SYSTEM SIZE 4.345kW0x 3E IAC - - SHELLEY HILL JOB HAZARD
`t/�B( ia,si �. Planet`, . AUBURN103A MAMILLBUR01V 501ST, CONTRACTOR LICENSE: DATE: 2/5/2022 7:29:38 AM - - 18SEDGEWICKPATH, ANALYSIS
888-997-4469 YARMOUTH,MA 02673 542E1
DATE: 2/5/2022 7:29:38 AM DESIGNER: I.RNAS - - PV9
•
BOM SHEET
ITEM(DESCRIPTION (MANUFACTURER (PART NUMBER I QUANTITY NEEDED PARTS PULLED PARTS RECEIVED
ELECTRICAL EQUIPMENT
1 SOLAR PV MODULE#1 HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10.ai HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10.a+ 11
2 INVERTER 81 SOLAR EDGE SE3000H-USRGM SOLAR EDGE SE3000H-USRGM 1
3 OPTIMIZER SOLAR EDGE P401 11
4 AC(UTIUTY)DISCONNECT#1 SQUARE D OR EQUAL D222RB,240V,60A,2P,3R 1
5 EXISTING MAIN SERVICE PANEL EATON/CUTLER HAMMER
6 MAIN SERVICE PANEL ADDITIONAL PARTS
7 NOT USED
7.1 NOT USED
7.2 NOT USED
7.3 NOT USED
8 REVENUE METER SQUARE D OR EQUAL 200A-4 JAW METER BASE 1
9 MAIN BREAKER EATON/CUTLER HAMMER 200A-2P
10 PV BREAKER(TIE IN) EATON/CUTLER HAMMER N/AA-2P 1
RACKING/MOUNTING HARDWARE
11 STANDOFF(L FEET/HOOKS/SLIDER&MOUNT) 28
12 FLASHING 28
13 LAG BOLT 28/56
14 GROUND LUGS 3
15 RAIL 10
16 SPLICES OR SKIRTS 10
17 OPTIMIZER MOUNT 11
18 MID CLAMPS 22
19 END CLAMPS OR RL UNK 11
20 J BOX PULL AS NEEDED
21 ADDITIONAL KITS REQUIRED
PICKED BY: RECEIVED BY:
SIGNATURE: PROJECTS BPS1E0914 REV DATE DESCRIPTION srat`i IMF
BRIGHT PLANET SOLAR
/' g A` 103A MILLBURY ST, SYSTEM SIZE 4.345kW/DC 31,W/AC — __ SHELLEY HILL BOM SHEET
` Bf� d F�EP'anet f + =`x AUBURN MA 01501 - - 18 SEDGEWICK PATH,
CONTRACTOR LICENSE: DATE: 2/5/2022 7:29:38 AM YARMOUTH,MA O2673
888-997-4469 seceir —
DATE 2/5/2022 7:29:38 AM DESIGNER: I.RIVAS — — PV 1 O