Concrete Reinforcing Steel Report
Briggs Engineering & Testing PROJECT:
A Division of PK Associates, Inc.PROJECT#:
INSPECTOR:
EMP.#:DATE:CODE:
PAGE OF
TEMP.:H 54F L WIND: H L √HUMID: H L √
Reinforcing steel was inspected for arrangement, cleanliness and checked against working drawings
and reference specifications of ACI-301 for the following items. Check marks indicate compliance.
All items in non-compliance are either corrected during inspection or noted below.
Size and location:Clearance to forms:
Grade Strength:Extra bars at openings:
Splice Lapping:Adequate ties:
Spacing:Concrete coverage:
Supports:Stirrup spacing:
Location and Drawing #:Bathrooms: foundation walls
Drawing #:S- 101, Dated 03/01/22
Flow rider: foundation walls
Drawing #:AQ3.02, Dated 01/25/22
Remarks:A reinforcing steel inspection was performed for the above location. All reinforcing steel
inspected conformed with the appropriate drawings/ specifications.
Bathrooms: foundation walls-
Vertical bars at 12" on center= ok.
(2) #5 Horizontal bars continuous, each face top= ok.
Corner bars= ok.
Flow rider: foundation walls-
Vertical bars, horizontal and corner bars (each face/ each way)= ok.
Note: water stop installed at required location= ok.
Note: All test results and findings contained within this report are limited to the areas
indicated.
100 Weymouth St., Unit B-1, Rockland, Ma 02370
100 Pound Rd., Cumberland, RI 02864 Approved:
Director of Field Operations:YHSean Skorohod
CC INFLATABLE PARK/ W. YARMOUTH
31987
Robert Carter
04/22/22
√
√
Sean Skorohod
√
N/A
√√
√
√
√
√