Loading...
HomeMy WebLinkAbout9 Holly Lane Air Leakage Report180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 08B3944A-E107-446B-9A62-6DF06A1A0E3F Duct Leakage Report 9 Holly Lane Yarmouth 04/21/2022 Braga Brothers 2018 IECC Energy Code Test Mode Pressurization Test Pressure 25.0 Pascals Testing Equipment Minneapolis Total CFM@25 49.00 Total Square Footage 1631.00 Maximum Allowable Leakage 65.24 or Total Duct Leakage Percentage 0.03 HVAC Duct Test 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 08B3944A-E107-446B-9A62-6DF06A1A0E3F Location Sqft Served Ring CFM@25 Gauge Duct Leakage % Unconditioned Basement 1631 C 49 0.03 180 State Rd Suite 2U, Sagamore Beach, MA 02562 • 508-833-3100 • energycodehelp.com • info@energycodehelp.com www.gocanvas.com 08B3944A-E107-446B-9A62-6DF06A1A0E3F All testing results recorded in this report have been verified by: Chris Mazzola RTIN# - 8873503 ICC - 8344213 All testing was conducted in compliance with RESNET standards and protocols, the 780 CMR 51 Massachusetts Base Code, Stretch Code requirements and ASHRAE 62.2.