Loading...
HomeMy WebLinkAboutB206 firestopHilti Firestop Systems Sheet Drawing No.HILTI, Inc. Plano, Texas USA (800) 879-8000 Date Scale Saving Lives through Innovation and Education Designed by NOTES : 1. MAXIMUM WIDTH OF JOINT = 6". 2. ANNULAR SPACE BETWEEN PENETRANTS AND PERIPHERY OF OPENING = MINIMUM 0". 3. ANNULAR SPACE BETWEEN PENETRANTS = MINIMUM 1/4". 4. T-RATING MAY NOT EQUAL F-RATING IN ACCORDANCE WITH UL 2079. 5. THE F-RATING OF THIS ENGINEERING JUDGMENT IS DEPENDENT UPON THE LOWEST F-RATING OF THE CONSTRUCTION ASSEMBLIES. 1. CONCRETE BLOCK WALL ASSEMBLY (UL/cUL CLASSIFIED) (MIN. 6" THICK) (1-HR. OR 2-HR. FIRE-RATING). 2. CONCRETE FLOOR ASSEMBLY (MINIMUM 4-1/2" THICK) (1-HR. OR 2-HR. FIRE-RATING). 3. ONE OR MORE PENETRATING ITEMS TO BE ANY OF THE FOLLOWING : A. MAXIMUM 4" NOMINAL DIAMETER STEEL CONDUIT OR EMT. B. MAXIMUM 1" NOMINAL DIAMETER METAL CLAD CABLE. 4. MINIMUM 4" THICKNESS MINERAL WOOL SAFING (MIN. 4 PCF DENSITY) COMPRESSED 50%, FLUSH WITH TOP OF FLOOR. 5. MINIMUM 1/8" (WET) THICKNESS HILTI CFS-SP WB FIRESTOP JOINT SPRAY TO COMPLETELY COVER MINERAL WOOL, OVERLAPPING MINIMUM 1/2" ONTO ADJACENT SURFACES. CROSS-SECTIONAL VIEW MAX. 6" 1 2 3 4 5 DS (REFERENCE : UL/cUL SYSTEM NO. FW-D-1013, HW-D-0098 & C-AJ-1606) 559088aJune 14, 2022 5/32" = 1" 1 of 1 THIS ENGINEERING JUDGMENT REPRESENTS A FIRESTOP SYSTEM THAT WOULD BE EXPECTED TO PASS THE STATED RATINGS IF TESTED. ENGINEERING JUDGMENT FIRESTOP DETAIL PROJECT : DYMS CB CONTRACTOR : COMMODORE BUILDERS F-RATING = 1-HR. OR 2-HR.